Experimental characterization of the ITER TF structure cooling in HELIOS test facility

被引:2
|
作者
Hoa, C. [1 ]
Rousset, B. [1 ]
Lacroix, B. [2 ]
Nicollet, S. [2 ]
Vallcorba, R. [3 ]
Bessette, D. [4 ]
Vostner, A. [4 ]
Gauthier, F. [5 ]
机构
[1] Univ Grenoble Alpes, INAC SBT, F-38000 Grenoble, France
[2] CEA, IRFM, F-13108 St Paul Les Durance, France
[3] CEA, IRFU, F-91191 Gif Sur Yvette, France
[4] ITER Org, F-13115 St Paul Les Durance, France
[5] Soditech Ingn, F-06150 Cannes, France
来源
关键词
D O I
10.1088/1757-899X/101/1/012148
中图分类号
O414.1 [热力学];
学科分类号
摘要
During ITER plasma operation, large thermal loads are generated in the stainless steel Toroidal Field (TF) coil casing. To minimize the impact on the temperature of the TF Cable in Conduit Conductor (CICC), these heat loads are intercepted by case cooling channels which are implemented at the interface to the winding pack. One of the design options for the case cooling channels consists of a stainless steel pipe inserted in a rectangular groove which is machined in the casing and filled by a charged resin of high thermal conductivity. A higher number of cooling pipes is arranged at the plasma facing wall of the case, thus providing a better shielding to the TF conductor at high field. To assess the efficiency of the cooling pipes and their thermal coupling with the charged resin, experimental characterizations have been performed. First of all, the thermal resistance vs temperature of some of the individual components of a TF coil has been measured on representative samples in a cryogenic bench. Further characterizations have been performed on an integrated mock-up of the TF cooling scheme at cryogenic temperature in HELIOS test facility at CEA Grenoble. The mock-up consists of a piece of TF casing that can be heated uniformly on its surface, one cooling channel implemented in the groove which is filled with the charged resin, the filler, the ground insulation, the radial plate and one insulated CICC. The cooling pipe and the CICC are cooled by supercritical helium at 4.4 K and 5 bar; the instrumentation consists of temperature, pressure and mass flow sensors. Both stationary and transient operating modes have been investigated to assess the thermal efficiency of the case cooling design. The experimental tests are presented and the first results are discussed and analyzed in this document.
引用
收藏
页数:8
相关论文
共 50 条
  • [1] The test facility for the ITER TF model coil
    Komarek, P
    Salpietro, E
    FUSION ENGINEERING AND DESIGN, 1998, 41 : 213 - 221
  • [2] Test facility for the ITER TF model coil
    Komarek, P.
    Salpietro, E.
    Fusion Engineering and Design, 1998, 41 (Pt B): : 213 - 221
  • [3] ITER CRYOGENIC SYSTEM VALIDATION TESTS AT HELIOS TEST FACILITY
    Vallcorba, R.
    Rousset, B.
    Poncet, J-M.
    Chang, H. S.
    Forgeas, A.
    Maekawa, R.
    Serio, L.
    Bonnay, P.
    Bon-Mardion, M.
    Girard, A.
    Hoa, C.
    Lagier, B.
    Michel, F.
    Roussel, P.
    ADVANCES IN CRYOGENIC ENGINEERING, VOLS 57A AND 57B, 2012, 1434 : 1415 - 1423
  • [4] Test Results of RF ITER TF Conductors in the SULTAN Test Facility
    Tronza, V. I.
    Lelekhov, S. A.
    Stepanov, B.
    Bruzzone, P.
    Kaverin, D. S.
    Shutov, K. A.
    Vysotsky, V. S.
    IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, 2014, 24 (03)
  • [5] Assembly in the test facility, acceptance and first test results of the ITER TF Model coil
    Fillunger, H
    Hurd, F
    Maix, RK
    Salpietro, E
    Ciazynski, D
    Duchateau, JL
    Libeyre, P
    Martinez, A
    Bobrov, E
    Herz, W
    Marchese, V
    Süsser, M
    Ulbricht, A
    Wüchner, F
    Zahn, G
    della Corte, A
    Ricci, M
    Theisen, E
    Kraft, G
    Bourquard, A
    Beaudet, F
    Schellong, B
    Zanino, R
    Savoldi, L
    IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, 2002, 12 (01) : 595 - 599
  • [6] Design of a cooling system for the cold test of the ITER TF coils before installation
    Zahn, G. R.
    Duchateau, J. L.
    Fietz, W. H.
    Gravil, B.
    Heller, R.
    Millet, F.
    Nicollet, S.
    Chesny, P.
    ICEC 20: PROCEEDINGS OF THE TWENTIETH INTERNATIONAL CRYOGENIC ENGINEERING CONFERENCE, 2005, : 87 - 90
  • [7] Experimental characterization of the gas injection nozzle for the ITER Neutral Beam Test Facility neutralizer
    Hanke, Stefan
    Hauer, Volker
    Day, Christian
    Dalla Palma, Mauro
    Sartori, Emanuele
    Dal Bello, Samuele
    Zaccaria, Pierluigi
    Zhang, Mingxing
    FUSION ENGINEERING AND DESIGN, 2017, 123 : 276 - 280
  • [8] Water Degradation in ITER Neutral Beam Test Facility Cooling Circuits
    Gasparrini, C.
    Cavallini, C.
    Zaupa, M.
    Maniero, M.
    Zucchetti, S.
    Badocco, D.
    Zorzi, F.
    Dalla Palma, M.
    Fellin, F.
    Zaccaria, P.
    IEEE TRANSACTIONS ON PLASMA SCIENCE, 2022, 50 (11) : 3947 - 3951
  • [9] Mechanical test on the ITER TF jacket
    Qin, Jinggang
    Wu, Yu
    Weiss, Klaus-Peter
    Wu, Zhixiong
    Li, Laifeng
    CRYOGENICS, 2012, 52 (7-9) : 336 - 339
  • [10] Modelization of the thermal coupling between the ITER TF coil conductor and the structure cooling circuit
    Gauthier, F.
    Bessette, D.
    Hoa, C.
    Rousset, B.
    Lacroix, B.
    CRYOGENICS, 2016, 80 : 294 - 304