Particle Effect on Breakdown Voltage of Mineral and Ester Based Transformer Oils

被引:0
|
作者
Wang, X. [1 ]
Wang, Z. D. [1 ]
机构
[1] Univ Manchester, Sch Elect & Elect Engn, Manchester M60 1QD, Lancs, England
关键词
D O I
暂无
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
ac breakdown voltage tests are usually used for quality check of mineral oils during transformer operation. When studying ester-based oils, previous experimental research including the ones carried out at University of Manchester laboratories, were based on 'as-received' oil samples and particle effects were not quantified. Similarly, water effects on oils determined previously were also ambiguous since water can be combined with particles to reduce breakdown voltages. This paper used mineral and ester-based transformer oils, i.e. 10 Gemini X as mineral oil, Mide17131 as synthetic ester-based oil and FR3 as nature ester-based oil, in the forms of "as-received" and processed", and their AC breakdown strengths were comparatively studied. Weibull distributions of ac breakdown voltages of three oils were discussed. It can be seen from the results that particle effects on ac oil breakdown voltages are dominant for "as-received" mineral oil and the 'processed' mineral oil has a distinctly different breakdown characteristic from 'as-received' mineral oil in terms of the effect of water contents.
引用
收藏
页码:386 / 390
页数:5
相关论文
共 50 条
  • [1] Statistical analysis of the AC breakdown voltages of ester based transformer oils
    Martin, D.
    Wang, Z. D.
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2008, 15 (04) : 1044 - 1050
  • [2] Lightning impulse polarity effect in ester oils and mineral oil for transformer applications
    Sharma, Pavitra
    Agarwal, Ritika
    Uppal, Anjali
    Narasimhan, C. S.
    Morde, Girish A.
    Velandy, Jeyabalan
    4TH INTERNATIONAL CONFERENCE ON CONDITION ASSESSMENT TECHNIQUES IN ELECTRICAL SYSTEMS (CATCON 2019), 2019,
  • [3] Comparative study of statistical breakdown in mineral, synthetic and natural ester oils under AC voltage
    Dang, Viet-Hung
    Beroual, A.
    Perrier, C.
    2011 IEEE INTERNATIONAL CONFERENCE ON DIELECTRIC LIQUIDS (ICDL), 2011,
  • [4] Comparative Study of Statistical Breakdown in Mineral, Synthetic and Natural Ester Oils under AC Voltage
    Dang, Viet-Hung
    Beroual, A.
    Perrier, C.
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2012, 19 (05) : 1508 - 1513
  • [5] Solubility Study of Different Gases in Mineral and Ester-based Transformer Oils
    Mueller, A.
    Jovalekic, M.
    Tenbohlen, S.
    PROCEEDINGS OF 2012 IEEE INTERNATIONAL CONFERENCE ON CONDITION MONITORING AND DIAGNOSIS (IEEE CMD 2012), 2012, : 937 - 940
  • [6] Prediction of insulating transformer oils breakdown voltage considering barrier effect based on artificial neural networks
    Sherif S. M. Ghoneim
    Sobhy S. Dessouky
    Adel A. Elfaraskoury
    Ahmed B. Abo Sharaf
    Electrical Engineering, 2018, 100 : 2231 - 2242
  • [7] Prediction of insulating transformer oils breakdown voltage considering barrier effect based on artificial neural networks
    Ghoneim, Sherif S. M.
    Dessouky, Sobhy S.
    Elfaraskoury, Adel A.
    Sharaf, Ahmed B. Abo
    ELECTRICAL ENGINEERING, 2018, 100 (04) : 2231 - 2242
  • [8] A Comparison of the Voltage Withstand Properties of Ester and Mineral Oils
    Azcarraga, C. G.
    Cavallini, A.
    Piovan, U.
    IEEE ELECTRICAL INSULATION MAGAZINE, 2014, 30 (05) : 6 - 14
  • [9] Breakdown Voltage Prediction by Utilizing the Behavior of Natural Ester for Transformer Applications
    Pakianathan, P. Samuel
    V. Maheswari, R.
    INTELLIGENT AUTOMATION AND SOFT COMPUTING, 2023, 35 (03): : 2717 - 2736
  • [10] Impulse Breakdown Voltages of Ester-based Transformer Oils Determined by Using Different Test Methods
    Liu, Q.
    Wang, Z. D.
    Perrot, F.
    CEIDP: 2009 ANNUAL REPORT CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA, 2009, : 575 - +