Influences of dry-wet hybrid rain zone on the heat and mass transfer characteristics of wet cooling towers: A case study

被引:11
|
作者
Zhang, Zhengqing [1 ]
Wang, Mingyong [2 ]
Wang, Youhao [1 ]
He, Suoying [1 ]
Gao, Ming [1 ]
机构
[1] Shandong Univ, Sch Energy & Power Engn, Shandong Engn Lab High Efficiency Energy Conserva, Jinan 250061, Shandong, Peoples R China
[2] Xian Thermal Power Res Inst CO LTD, Xian 710054, Peoples R China
基金
中国国家自然科学基金;
关键词
Heat and mass transfer; Wet cooling tower; Dry-wet hybrid rain zone; Case study; THERMAL PERFORMANCE; NUMERICAL-SIMULATION; FIELD; FILLINGS; CAPACITY; IMPROVE; SYSTEM; WALLS; FLOW;
D O I
10.1016/j.csite.2022.101784
中图分类号
O414.1 [热力学];
学科分类号
摘要
To study the influences of the dry-wet hybrid rain zone (DWHR) on the heat and mass transfer characteristics for the super-large natural draft wet cooling towers (S-NDWCTs) and provide the relevant reference data for the optimal design, a case study is conducted based on the numerical model. The simulation results show that, after adopting the DWHR, the average gas-water ratio on the bottom of the fillings increases by 4.22%, the volumetric heat transfer coefficient of the fillings zone, rain zone, and spraying zone increase by 1.69%, 2.31%, and 16.1% respectively, on average. Additionally, after adopting the DWHR, the contact heat transfer ratio increases, and the evaporation loss coefficient decreases obviously under the high crosswind speed but changes little under the low or middle crosswind speed. The research can provide an innovative method and theoretical guidance for the design of the S-NDWCTs.
引用
收藏
页数:11
相关论文
共 50 条
  • [1] Numerical Simulation on the Effect of Dry-wet Hybrid Cooling in Rain Zone on Heat and Mass Transfer Performance for the Super-large Wet Cooling Towers
    Wang N.
    Zhang Z.
    Zou J.
    Gao M.
    He S.
    Sun F.
    Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering, 2020, 40 (15): : 4927 - 4934
  • [2] Study on Orthogonal Optimization for the Super-large Wet Cooling Tower With Dry-wet Hybrid Rain Zone
    Zhang Z.
    Wang M.
    Zhang D.
    Chen R.
    He S.
    Gao M.
    Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering, 2022, 42 (22): : 8224 - 8231
  • [3] Synergistic optimization of partition water distribution, non-equidistant fillings and dry-wet hybrid rain zone for wet cooling towers
    Yang, Jichong
    Gao, Ming
    Wang, Mingyong
    Wang, Weishu
    He, Suoying
    Jiang, Guangxu
    Sun, Gengsheng
    APPLIED THERMAL ENGINEERING, 2023, 231
  • [4] ECONOMICS OF DRY-WET COOLING-TOWERS
    CROLEY, TE
    PATEL, VC
    CHENG, MS
    JOURNAL OF THE POWER DIVISION-ASCE, 1976, 102 (02): : 147 - 163
  • [5] HEAT TRANSFER CHARACTERISTICS OF A DRY AND WET/DRY ADVANCED CONDENSER FOR COOLING TOWERS.
    Fricke, H.D.
    McIlroy, K.
    Webster, D.J.
    Electric Power Research Institute, Coal Combustion Systems Division, (Report) EPRI CS, 1982,
  • [6] THERMODYNAMIC MODELS OF DRY-WET COOLING-TOWERS
    CROLEY, TE
    PATEL, VC
    CHENG, MS
    JOURNAL OF THE POWER DIVISION-ASCE, 1976, 102 (01): : 1 - 19
  • [7] ANALYSIS OF DIFFERENT TYPES OF DRY-WET COOLING TOWERS.
    Cheng, Mow-Soung
    Croley, Thomas E.II.
    Patel, V.C.
    1600, Univ of Iowa, Iowa Inst of Hydraul Res, Iowa City
  • [8] CAPACITIVE POND AS AN IMPROVEMENT FOR COMBINATION DRY-WET COOLING-TOWERS
    SHEFF, JR
    TRANSACTIONS OF THE AMERICAN NUCLEAR SOCIETY, 1978, 28 (JUN): : 598 - 599
  • [9] Hybrid Cooling Towers in Economic Comparison with Wet and Dry Cooling Towers.
    Alt, W.
    Maeule, R.
    VGB-Kraftwerkstechnik, 1987, 67 (08): : 763 - 768
  • [10] An exploratory research on performance improvement of super-large natural draft wet cooling tower based on the reconstructed dry-wet hybrid rain zone
    Zhang, Zhengqing
    Gao, Ming
    Dang, Zhigang
    He, Suoying
    Sun, Fengzhong
    INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2019, 142