Disconnector switching induced transient voltage and radiated fields in a 1100 kV gas insulated substation

被引:21
|
作者
Haseeb, M. A. [1 ]
Thomas, M. Joy [1 ]
机构
[1] Indian Inst Sci, Dept Elect Engn, Bangalore 560012, Karnataka, India
关键词
Gas Insulated Substation (GIS); Very Fast Transient Overvoltage (VFTO); Electromagnetic Transient Program (EMTP); Ultra High Voltage (UHV) substation; Electro Magnetic Compatibility (EMC); GIS;
D O I
10.1016/j.epsr.2018.04.001
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Very fast transient overvoltages (VFTO) generated in a gas insulated substation (GIS) during disconnector switching operations are one of the major concerns in insulation design of the GIS. Such over voltages can cause malfunctioning of the protection and control circuits in addition to initiating faults inside the gas insulated bus ducts especially in the presence of metallic particles. In this paper, VFTOs have been estimated at various locations using EMTP in a 1100 kV rated GIS during disconnector switching operations. For the substation studied, the maximum computed overvoltage is 1.76 p.0 without considering the trapped charge on the bus bar and it reaches 2.54 p.0 with a trapped charge of -1 p.u. Major frequency components in the computed VFTO lie in the range of 800 kHz to 15 MHz. Studies on mitigation of VFTO by the use of damping resistors in the disconnector showed that a resistance close to 500 Q gives the best results. For the bus sections with trapped charge, increasing the resistance value above 500 Q results in a negative peaking of VFTO. Transient radiated fields through the bushings of the GIS are also studied for electro magnetic compatibility (EMC) design of the substation. (C) 2018 Elsevier B.V. All rights reserved.
引用
收藏
页码:86 / 94
页数:9
相关论文
共 50 条
  • [1] Measurement of transient enclosure voltage in a 220kV gas insulated substation
    Cai, Yuanji
    Guan, Yonggang
    Liu, Weidong
    2015 IEEE INTERNATIONAL INSTRUMENTATION AND MEASUREMENT TECHNOLOGY CONFERENCE (I2MTC), 2015, : 115 - 120
  • [2] Influence of Switching Conditions on Very Fast Transient Over-voltage in 500kV Gas Insulated Substation
    Liu, Qing
    Zhang, Yufeng
    ICEMS 2008: PROCEEDINGS OF THE 11TH INTERNATIONAL CONFERENCE ON ELECTRICAL MACHINES AND SYSTEMS, VOLS 1- 8, 2008, : 4451 - 4454
  • [3] Study on the Influence of Disconnector Characteristics on Very Fast Transient Overvoltages in 1100-kV Gas-Insulated Switchgear
    Chen, Wei-Jiang
    Wang, Hao
    Han, Bin
    Wang, Lei
    Ma, Guo-Ming
    Yue, Gong-Chang
    Li, Zhi-Bing
    Hu, Hao
    IEEE TRANSACTIONS ON POWER DELIVERY, 2015, 30 (04) : 2037 - 2044
  • [4] Computation of EMI fields in a high voltage gas insulated substation during switching operations
    Rao, MM
    Thomas, MJ
    Singh, BP
    2003 IEEE SYMPOSIUM ON ELECTROMAGNETIC COMPATIBILITY, SYMPOSIUM RECORD, VOLS 1 AND 2, 2003, : 743 - 748
  • [5] Experimental study of effect of Disconnector speed on Very Fast transient Over Voltages in a 420kV Gas Insulated Substation
    Rao, J. V. G. Rama
    Ramakrishna, A.
    JOURNAL OF ELECTRICAL SYSTEMS, 2020, 16 (02) : 142 - 151
  • [6] Analysis of electromagnetic transients in secondary circuits due to disconnector switching in 400 kV air-insulated substation
    Filipovic-Grcic, B.
    Uglesic, I.
    Milardic, V.
    Filipovic-Grcic, D.
    ELECTRIC POWER SYSTEMS RESEARCH, 2014, 115 : 11 - 17
  • [7] Measurement of Magnetic Fields in a 220kV Gas Insulated Substation
    Ellithy, Khaled A.
    2010 IEEE PES TRANSMISSION AND DISTRIBUTION CONFERENCE AND EXPOSITION: SMART SOLUTIONS FOR A CHANGING WORLD, 2010,
  • [8] Overvoltages in Secondary Circuits of Air-Insulated Substation Due to Disconnector Switching
    Bajramovic, Zijad
    Turkovic, Irfan
    Mujezinovic, Adnan
    Carsimamovic, Adnan
    Muharemovic, Aida
    2012 IEEE INTERNATIONAL CONFERENCE ON POWER SYSTEM TECHNOLOGY (POWERCON), 2012,
  • [9] Exposure to electric and magnetic fields at 110 kV gas insulated substation (GIS)
    Sauramäki, T
    Keikko, T
    Kuusiluoma, S
    Korpinen, L
    IEEE/PES TRANSMISSION AND DISTRIBUTION CONFERENCE AND EXHIBITION 2002: ASIA PACIFIC, VOLS 1-3, CONFERENCE PROCEEDINGS: NEW WAVE OF T&D TECHNOLOGY FROM ASIA PACIFIC, 2002, : 1226 - 1229
  • [10] The influence of gas insulated substation structural parameters on transient enclosure voltage waveform
    Han, Mingming
    Li, Qingquan
    Liu, Hongshun
    Yang, Luming
    Diangong Jishu Xuebao/Transactions of China Electrotechnical Society, 2015, 30 (22): : 239 - 246