Fast Transient Overvoltage Analysis in Current Transformers due to Disconnector Switching Operation

被引:0
|
作者
Gadotti, Filipe R. [1 ,2 ]
Cabral, Sergio H. L. [3 ]
Schuartz, Felipe M. [1 ,2 ]
机构
[1] WEG Transmissao & Distribuicao, Blumenau, Brazil
[2] Univ Reg Blumenau, Elect Engn, Blumenau, Brazil
[3] Univ Reg Blumenau, Dept Elect Engn & Telecommun, Blumenau, Brazil
关键词
Transient analysis; Current transformer; Energy spectral density; Electric arc; Overvoltage; SUBSTATIONS;
D O I
暂无
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
This paper presents the results of a computer simulation analysis combining the application of energy spectral density techniques and evaluation of the rate of rise for checking the voltage withstand of the dielectric system of a current transformer under the incidence of a set of fast transient voltage surges caused by switching operations of an adjacent disconnector. This sort of occurrence has become a critical issue in the electrical power system, being a possible cause of the high number of failures of operating current transformers 550 kV class. The adopted approach is rather new and differs from any of those applied to the analyses of the incidence of VFTO - Very Fast Transient Overvoltage by representing a contribution to the discussions for updating current transformer testing standards.
引用
收藏
页码:58 / 63
页数:6
相关论文
共 50 条
  • [1] Influence of Switching Properties of the Disconnector on Very Fast Transient Overvoltage
    Zhan, Huamao
    Duan, Shaofeng
    Yao, Linzhi
    Zhao, Lin
    [J]. 2017 IEEE ELECTRICAL INSULATION CONFERENCE (EIC), 2017, : 412 - 416
  • [2] Influence of the Switching Speed of the Disconnector on Very Fast Transient Overvoltage
    Shu Yinbiao
    Han Bin
    Lin Ji-Ming
    Chen Weijiang
    Ban Liangeng
    Xiang Zutao
    Chen Guoqiang
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2013, 28 (04) : 2080 - 2084
  • [3] SUPPRESSION OF FAST TRANSIENT OVERVOLTAGE DURING GAS DISCONNECTOR SWITCHING IN GIS
    OZAWA, J
    YAMAGIWA, T
    HOSOKAWA, M
    TAKEUCHI, S
    KOZAWA, H
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 1986, 1 (04) : 194 - 201
  • [4] Measuring of Very Fast Transient Overvoltage and Very Fast Transient Current Generated by Disconnector Operating
    Liu, Bin
    Tong, Yue
    Deng, Xiao-pin
    Feng, Xiang-xiang
    [J]. 2014 INTERNATIONAL CONFERENCE ON POWER SYSTEM TECHNOLOGY (POWERCON), 2014, : 1349 - 1354
  • [5] Study on suppression of switching overvoltage caused by operation of disconnector in GIS
    School of Electrical Engineering, Xi'an Jiaotong University, Xi'an 710049, China
    [J]. Gaoya Dianqi, 2006, 1 (18-20+24):
  • [6] Research on Very Fast Transient Overvoltage During Switching of Disconnector in 550kV GIS
    Zhao, Lin
    Ye, Liya
    Wang, Shaoan
    Yang, Yong
    Jiang, Peng
    Zou, Xiaofeng
    [J]. 2018 3RD IEEE INTERNATIONAL CONFERENCE ON INTEGRATED CIRCUITS AND MICROSYSTEMS (ICICM), 2018, : 114 - 118
  • [7] Analysis on switching overvoltage of 500 kV GIS disconnector
    Ren Hongtao
    [J]. ENERGY REPORTS, 2022, 8 : 169 - 176
  • [8] TRANSIENT OVERVOLTAGE DUE TO ELECTROMAGNETIC INTERFERENCE AT SWITCHING OPERATION IN POWER SYSTEMS
    MIYAZI, I
    KITO, Y
    [J]. ELECTRICAL ENGINEERING IN JAPAN, 1965, 85 (11) : 50 - &
  • [9] Study on fluid model of disconnector arc applied in very fast transient overvoltage
    Hao, Sha
    Xu, Jianyuan
    Lin, Xin