Effects of different operating conditions of Gonen geothermal district heating system on its annual performance

被引:8
|
作者
Aslan, Asiye [1 ]
Yuksel, Bedri [2 ]
Akyol, Tugrul [2 ]
机构
[1] Balikesir Univ, Gonen Vocat Sch, TR-10900 Gonen Balikesir, Turkey
[2] Balikesir Univ, Dept Mech Engn, TR-10100 Balikesir, Turkey
关键词
Geothermal energy; Performance analysis; District heating system; ENERGY; EXERGY; TURKEY;
D O I
10.1016/j.enconman.2013.12.066
中图分类号
O414.1 [热力学];
学科分类号
摘要
In this paper, the effects of different operating conditions of the Gonen geothermal district heating system (GDHS) on its annual energy and exergy performance are investigated. The system parameters such as temperature, pressure and flow rate are monitored by using fixed and portable measuring instruments over a one-year period. Thus the main differences in the annual system operation are detected. The measurements show that the Gonen GDHS has six different operating cases depending on the outside temperature throughout the year. The energy and exergy analysis of the system is carried out for each case using the actual system parameters at the corresponding reference temperatures, which are 3.86, 7.1, 8:88, 11.83, 15.26 and 20.4 degrees C. The highest and lowest energy (57.32%, 35.64%) and exergy (55.76%, 41.42%) efficiencies of the overall system are calculated at the reference temperatures of 15.26 C and 3.86 degrees C, respectively. Besides, taking the six case-based energy and exergy analyses into account, the annual average energy and exergy efficiencies are determined to be 45.24% and 47.33%, respectively. (C) 2014 Elsevier Ltd. All rights reserved.
引用
收藏
页码:554 / 567
页数:14
相关论文
共 50 条
  • [1] Investigation of the energetic and exergetic performance of the Gonen geothermal district heating system
    Ozgener, L.
    Hepbasli, A.
    Dincer, I.
    [J]. PROCEEDINGS OF THE INSTITUTION OF MECHANICAL ENGINEERS PART A-JOURNAL OF POWER AND ENERGY, 2006, 220 (A7) : 671 - 679
  • [2] Energy analysis of different types of buildings in Gonen geothermal district heating system
    Aslan, Asiye
    Yuksel, Bedri
    Akyol, Tugrul
    [J]. APPLIED THERMAL ENGINEERING, 2011, 31 (14-15) : 2726 - 2734
  • [3] Exergoeconomic analysis of the Gonen geothermal district heating system for buildings
    Oktay, Z.
    Dincer, I.
    [J]. ENERGY AND BUILDINGS, 2009, 41 (02) : 154 - 163
  • [4] Energy and exergy analysis of the Gonen geothermal district heating system, Turkey
    Ozgener, L
    Hepbasli, A
    Dincer, I
    [J]. GEOTHERMICS, 2005, 34 (05) : 632 - 645
  • [5] Investigation of seasonal variations in the energy and exergy performance of the Gonen geothermal district heating system
    Yuksel, Bedri
    Aslan, Asiye
    Akyol, Tugrul
    [J]. APPLIED THERMAL ENGINEERING, 2012, 36 : 39 - 50
  • [6] Geothermal district heating in Turkey: The Gonen case study
    Oktay, Zuhal
    Aslan, Asiye
    [J]. GEOTHERMICS, 2007, 36 (02) : 167 - 182
  • [7] Assessment of Total Operating Costs for a Geothermal District Heating System
    Gokgedik, Harun
    Incili, Veysel
    Arat, Halit
    Kecebas, Ali
    [J]. Energy Systems and Management, 2015, : 293 - 303
  • [8] Influence of Different Operating Conditions of a District Heating and Cooling System on Heat Transportation Losses of a District Heating Network
    Zwierzchowski, Ryszard
    Niemyjski, Olgierd
    [J]. 3RD WORLD MULTIDISCIPLINARY CIVIL ENGINEERING, ARCHITECTURE, URBAN PLANNING SYMPOSIUM (WMCAUS 2018), 2019, 471
  • [9] PERFORMANCE INVESTIGATION OF GEOTHERMAL DISTRICT HEATING SYSTEMS
    Kalinci, Yildiz
    Tavman, Ismail
    Hepbasli, Arif
    [J]. PROCEEDINGS OF SEBUA-12 ICHMT INTERNATIONAL SYMPOSIUM ON SUSTAINABLE ENERGY IN BUILDINGS AND URBAN AREAS, 2012,
  • [10] Effect of Operating Conditions on Water Injector of District Heating Supply System
    Zhang, Kun
    Zhang, Bo
    Shen, Sheng-qiang
    [J]. MECHANICAL ENGINEERING AND MATERIALS, PTS 1-3, 2012, 152-154 : 1041 - +