Ground distance relay compensation in the presence of delta-hexagonal phase shifting transformer

被引:11
|
作者
Ghorbani, Amir [1 ]
Arablu, Masoud [2 ]
机构
[1] Islamic Azad Univ, Dept Elect Engn, Abhar Branch, Abhar, Iran
[2] Univ N Carolina, Dept Mech Engn & Engn Sci, Charlotte, NC 28223 USA
关键词
relay protection; power transformers; phasor measurement; fault location; load flow control; ground distance relay compensation; delta-hexagonal phase shifting transformer; PST; fault resistances; fault locations; phase-to-ground faults; power flow control; transmission lines; voltage difference; phasor measurement units; PMU; system protection centre; electromagnetic transient programme; PROTECTION; ALGORITHM;
D O I
10.1049/iet-gtd.2015.0526
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
In this study, the effects of the delta-hexagonal phase shifting transformers (PSTs) on the operation of distance relays and their trip boundaries are investigated under different fault resistances and locations. Existence of fault resistance in phase-to-ground faults creates an unreliable operation of distance relays. Trip boundaries are used to determine the fault resistance effects on the impedance calculated by the relay. Moreover, PSTs are used to control the power flow in transmission lines. Finally, a feasible method for eliminating the PSTs detrimental effects on the operation of the distance relays is presented. This method, which uses the voltage difference between the PST terminals, is getting prevalent in modifying the operation of the distance relays even under the high resistance faults. Phasor measurement units (PMUs) are used to calculate this voltage as PMU signals and a remote signal system is used to transmit them to the system protection centre. All the simulations are conducted with Electro-Magnetic Transient Program.
引用
收藏
页码:2091 / 2098
页数:8