Performance comparison of several energy storage devices in deregulated AGC of a multi-area system incorporating geothermal power plant

被引:85
|
作者
Tasnin, Washima [1 ]
Saikia, Lalit Chandra [1 ]
机构
[1] Natl Inst Technol Silchar, Elect Engn Dept, Silchar, Assam, India
关键词
AUTOMATIC-GENERATION CONTROL; REDOX FLOW BATTERIES; CASCADE CONTROLLER; RENEWABLE ENERGY; THERMAL SYSTEM; OPTIMIZATION; ENVIRONMENT; OPERATION;
D O I
10.1049/iet-rpg.2017.0582
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
This study highlights an attempt of comparing the performance of several energy storage (ES) devices like battery ES, flywheel ES, capacitive ES, superconducting magnetic ES, ultra-capacitors and redox flow battery (RFB) in automatic generation control under bilateral deregulated scenario. The considered system comprises gas and thermal generations wherein a geothermal power plant (GTPP) is also incorporated. Gas and thermal systems are provided with appropriate generation rate constraints. A new fractional order (FO) cascade controller named as FO proportional-integral-FO proportional-derivative (FOPI-FOPD) is proposed as secondary controller and its performance is compared with commonly used classical controllers. A novel stochastic algorithm, sine cosine algorithm, has been used to optimise controller gains and other parameters. Analyses of dynamic responses reveal the superiority of FOPI-FOPD over others in terms of settling time, peak deviation and magnitude of oscillation. The effect due to GTPP introduction has been examined and the responses disclose that the integration of GTPP leads to better dynamics. Performances of various ES devices in the presence of FOPI-FOPD controller are also compared and dynamic responses of RFB found superior to others. For a more realistic scenario, analysis is done considering time delay and some practical plants of Nevada, USA.
引用
收藏
页码:761 / 772
页数:12
相关论文
共 50 条
  • [1] Comparative performance of different energy storage devices in AGC of multi-source system including geothermal power plant
    Tasnin, Washima
    Saikia, Lalit Chandra
    [J]. JOURNAL OF RENEWABLE AND SUSTAINABLE ENERGY, 2018, 10 (02)
  • [2] Performance comparison of several classical controllers in AGC for multi-area interconnected thermal system
    Saikia, Lalit Chandra
    Nanda, J.
    Mishra, S.
    [J]. INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2011, 33 (03) : 394 - 401
  • [3] Deregulated AGC of multi-area system incorporating dish-Stirling solar thermal and geothermal power plants using fractional order cascade controller
    Tasnin, Washima
    Saikia, Lalit Chandra
    Raju, More
    [J]. INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2018, 101 : 60 - 74
  • [4] Design and analysis of optimal AGC regulator for multi-area power systems with TCPS and energy storage unit in deregulated environment
    Mishra, Ram Naresh
    Kumar, Narendra
    Chaturvedi, Devendra Kumar
    [J]. OPTIMAL CONTROL APPLICATIONS & METHODS, 2024, 45 (04): : 1456 - 1502
  • [5] Utilization of energy storage devices with optimal controller for multi-area hydro-hydro power system under deregulated environment
    Rangi, Sandeep
    Jain, Sheilza
    Arya, Yogendra
    [J]. SUSTAINABLE ENERGY TECHNOLOGIES AND ASSESSMENTS, 2022, 52
  • [6] Constrained discrete mode control of supercapacitor energy storage system for improved AGC of a multi-area power system with effects of wind power
    Nisa, Sabah Un
    Mufti, Mairaj Ud-Din
    [J]. International Journal of Power Electronics, 2021, 14 (03) : 386 - 403
  • [7] Comparative Performance Assessment of Different Energy Storage Devices in Combined LFC and AVR Analysis of Multi-Area Power System
    Kalyan, CH. Naga Sai
    Goud, B. Srikanth
    Reddy, Ch. Rami
    Bajaj, Mohit
    Sharma, Naveen Kumar
    Alhelou, Hassan Haes
    Siano, Pierluigi
    Kamel, Salah
    [J]. ENERGIES, 2022, 15 (02)
  • [8] Utilization and performance comparison of several HESSs with cascade optimal-FOD controller for multi-area multi-source power system under deregulated environment
    Rangi, Sandeep
    Jain, Sheilza
    Arya, Yogendra
    [J]. JOURNAL OF ENERGY STORAGE, 2024, 94
  • [9] Performance Improvement of AGC Using Novel Controllers in a Multi-Area Solar Thermal System under Deregulated Environment
    Rajendran, Madhuvanthani
    Govindasamy, Sundar
    [J]. ELECTRIC POWER COMPONENTS AND SYSTEMS, 2024, 52 (06) : 847 - 862
  • [10] Performance Comparison of FOA Optimized Several Classical Controllers for Multi-area Multi-sources Power System
    Acharyulu, B. V. S.
    Swamy, S. K.
    Mohanty, Banaja
    Hota, P. K.
    [J]. SOFT COMPUTING IN DATA ANALYTICS, SCDA 2018, 2019, 758 : 417 - 426