Research on cable partial discharge detection and location system based on optical fibre timing

被引:2
|
作者
Zhang, Jianjun [1 ]
Peng, Fang [1 ]
Xie, Anming [1 ]
Fei, Yang [1 ]
机构
[1] Guodian Dadu River Dagangshan Hydropower Dev Co Lt, Simian 625409, Sichuan, Peoples R China
关键词
cable; partial discharge; optical fibre timing; double terminal positioning; online monitoring; location; detection; power system; sensor; type recognition; SEMICONDUCTING LAYER; WAVE-PROPAGATION; PD DETECTION;
D O I
10.1504/IJCAT.2022.127805
中图分类号
TP39 [计算机的应用];
学科分类号
081203 ; 0835 ;
摘要
Partial discharge (PD) is an important index to reflect the running state of cables. According to the characteristics and propagation mechanism of cable partial discharge signal, a cable partial discharge detection and location system based on optical fibre time synchronisation technology and travelling wave double terminal location principle is developed. The system has high detection sensitivity, high reliability, real-time detection, diagnosis and positioning of cable discharge power supply. The experimental results show that the positioning accuracy of the cable partial discharge source can be effectively improved based on the fibre timing and double terminal positioning technology, and the positioning accuracy can reach 1%; the method studied in this paper can meet the requirements of the accurate location of the partial discharge source of the cable, Gil and other equipment.
引用
收藏
页码:298 / 307
页数:10
相关论文
共 50 条
  • [1] Partial discharge detection and location in cable joint
    Wu, XY
    Xie, HK
    Peng, ZR
    Pang, QP
    1998 INTERNATIONAL SYMPOSIUM ON ELECTRICAL INSULATING MATERIALS, PROCEEDINGS, 1998, : 721 - 723
  • [2] Partial Discharge Detection and Defect Location Method in GIS Cable Terminal
    Li, Songyuan
    Song, Pengxian
    Wei, Zhanpeng
    Li, Xu
    Tang, Qinghua
    Meng, Zhengzheng
    Li, Ji
    Liu, Songtao
    Wang, Yuhuai
    Li, Jin
    ENERGIES, 2023, 16 (01)
  • [3] Design of Partial Discharge Detection System for XLPE Cable Based on Zigbee Technology
    Huang, S. B.
    Wang, J. B.
    He, S. H.
    Zhan, Q. H.
    Zhang, Y. M.
    Xu, Y. P.
    PROCEEDINGS OF THE 4TH INTERNATIONAL CONFERENCE ON INFORMATION TECHNOLOGY AND MANAGEMENT INNOVATION, 2015, 28 : 254 - 260
  • [4] Partial Discharge Location for Power Cable Based on the Time Reversal Technique
    Xie M.
    Zhou K.
    He M.
    Zhao S.
    Zhang F.
    Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering, 2018, 38 (11): : 3402 - 3409
  • [5] An optical fiber sensing method for partial discharge in the HVDC cable system
    Liu, Zhiheng
    Wang, Yongqing
    Chen, Xiao
    Meng, Xiaokai
    Liu, Xiuling
    Yao, Jianquan
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2021, 128
  • [6] Research on partial discharge detection based on distributed optical fiber acoustic sensor
    Sun, Yuwei
    Lv, Anqiang
    Xie, Zhiyuan
    Kong, Yan
    MEASUREMENT SCIENCE AND TECHNOLOGY, 2024, 35 (08)
  • [7] Partial discharge detection technology based on the fibre Bragg grating
    Ye, H.F.
    Qian, Y.
    Liu, Y.D.
    Chen, R.L.
    Sheng, G.H.
    Jiang, X.C.
    Australian Journal of Electrical and Electronics Engineering, 2014, 11 (02): : 217 - 225
  • [8] Research on the On-line Monitoring System for Partial Discharge of Cable Joint
    Li, Yanqing
    Jia, Zihang
    Zhao, Liang
    Liang, Jianfeng
    MECHATRONICS, ROBOTICS AND AUTOMATION, PTS 1-3, 2013, 373-375 : 986 - +
  • [9] A Thermal Excitation Based Partial Discharge Detection Method for Cable Accessory
    Li, Zerui
    Zhou, Kai
    Xu, Xiangdong
    Meng, Pengfei
    Fu, Yao
    Zeng, Zijin
    IEEE TRANSACTIONS ON POWER DELIVERY, 2023, 38 (04) : 2703 - 2710
  • [10] Research on Partial Discharge Location Method of DC Wall Bushing Based on Partial Discharge Transfer Ratio
    Pan, Zhicheng
    Zhang, Jinyin
    Xie, Zhicheng
    Deng, Jun
    2023 5TH ASIA ENERGY AND ELECTRICAL ENGINEERING SYMPOSIUM, AEEES, 2023, : 191 - 194