New one terminal digital algorithm for adaptive reclosing and fault distance calculation on transmission lines

被引:44
|
作者
Radojevic, ZM [1 ]
Shin, JR [1 ]
机构
[1] Konkuk Univ, Dept Elect Engn, Seoul 143701, South Korea
关键词
arc resistance; electric power systems; fault location; numerical algorithms; protection; spectral analysis; transmission lines;
D O I
10.1109/TPWRD.2005.860285
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper presents a new numerical spectral domain algorithm devoted to blocking unsuccessful automatic reclosing onto permanent faults and fault distance calculation. Are voltage amplitude and fault distance are calculated from the fundamental and third harmonies of the terminal voltages and currents phasors. The electric arc is modeled with its voltage waveshape defined numerically on the basis of a number of arc voltage records obtained in the high-voltage laboratory. From the calculated arc voltage amplitude, it can be concluded whether the fault is a transient arcing fault or a permanent arcless fault. If the fault is permanent, automatic reclosure should be blocked. The algorithm can be applied for adaptive autoreclosure, distance protection, and fault location. The results of algorithm testing through computer simulation and real field record are given.
引用
收藏
页码:1231 / 1237
页数:7
相关论文
共 50 条
  • [1] Improved digital algorithm for adaptive reclosing for transmission lines with shunt reactors
    Luo, Xunhua
    Huang, Chun
    Jiang, Yaqun
    [J]. IET GENERATION TRANSMISSION & DISTRIBUTION, 2016, 10 (09) : 2066 - 2070
  • [2] Digital signal processing algorithm for arcing faults detection and fault distance calculation on transmission lines
    Djuric, MB
    Radojevic, ZM
    Terzija, VV
    [J]. INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 1997, 19 (03) : 165 - 170
  • [3] A new digital algorithm for adaptive reclosure of transmission lines
    M. B. Djurić
    Z. M. Radojević
    [J]. Electrical Engineering, 1999, 82 : 105 - 109
  • [4] A new digital algorithm for adaptive reclosure of transmission lines
    Djuric, MB
    Radojevic, ZM
    [J]. ELECTRICAL ENGINEERING, 1999, 82 (02) : 105 - 109
  • [5] Numerical algorithm for fault distance calculation and blocking unsuccessful reclosing onto permanent faults
    Radojevic, ZM
    Lee, CJ
    Shin, JR
    Park, JB
    [J]. 2005 IEEE POWER ENGINEERING SOCIETY GENERAL MEETING, VOLS, 1-3, 2005, : 757 - 762
  • [6] Test of a fast adaptive reclosing algorithm for transmission lines using a programmable hardware
    Dias, Ozenir
    Magrin, Fabiano
    Tavares, Maria Cristina
    [J]. JOURNAL OF ENGINEERING-JOE, 2018, (15): : 1354 - 1359
  • [7] A New Practical Fault Location Algorithm for Two-terminal Transmission Lines
    Ma, Zhou
    Li, Xiaoning
    Zhang, Xiaoming
    [J]. MANUFACTURING SCIENCE AND TECHNOLOGY, PTS 1-8, 2012, 383-390 : 4377 - +
  • [8] Online Calculation for the Optimal Reclosing Time of Transmission Lines
    Wang, Xinpu
    Yang, Jun
    Liu, Pei
    Liu, Wenqing
    Yan, Jun
    Tang, Yufei
    He, Haibo
    [J]. ELECTRIC POWER COMPONENTS AND SYSTEMS, 2016, 44 (17) : 1904 - 1916
  • [9] New digital algorithm for adaptive reclosing based on the calculation of the faulted phase voltage total harmonic distortion factor
    Radojevic, Zoran M.
    Shin, Joong-Rin
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2007, 22 (01) : 37 - 41
  • [10] An accurate fault location algorithm for parallel transmission lines using one-terminal data
    Song Guobing
    Jiale, Suonan
    Ge Yaozhong
    [J]. INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2009, 31 (2-3) : 124 - 129