Single-phase auto-reclosure studies: secondary arc model research including a 500kV line experimental circuit

被引:0
|
作者
Camara, Alessandra S. B. [1 ]
Goncalves, Ricardo A. A. [1 ]
Rodrigues, Marcelo G. [2 ]
Oliveira, F. Orsino [2 ]
Portela, Carlos M. [3 ]
Tavares, Maria Cristina [4 ]
机构
[1] Furnas Centrais Eletr R Real Grandeza 219 Botafog, BR-22281900 Rio De Janeiro, Brazil
[2] CEPEL Elect Power Res Ctr, BR-26053121 Rio De Janeiro, Brazil
[3] Univ Fed Rio de Janeiro, COPPE, BR-21945 Rio De Janeiro, Brazil
[4] Univ Estadual Campinas, DSCE FEE, Sao Paulo, Brazil
基金
巴西圣保罗研究基金会;
关键词
D O I
暂无
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Brazitian electrical transmission system has radial sub-systems and not much meshed long EHV/HV tines, a profile that suggests single-phase auto-reclosure (SPAR) as usual procedure. Since year 2000, the national electrical energy regulatory agency (ANEEL) has required the use of SPAR in the design, construction and operation of new transmission lines. Analysis of SPAR success is basically related to secondary arc extinction in a reasonably short time. So, secondary arc modeling became an important issue on defining optimized solutions. In 2003, FURNAS, UFRJ and CEPEL - transmission utility, university and research center, respectively - started a research project related to secondary are modeling. A test infra-structure was set up at CEPEL's high power laboratory, including an out door real 500 kV line piece, with three towers and two spans and necessary measuring devices (electrical parameters, visual - films - and wind records), where arcs have been generated and monitored. The main purpose of this research project is to obtain and validate a robust model of the primary and secondary arcs in a transmission line, allowing to investigate the interaction between the arc and the "network", at arc terminals, and the evaluation of SPAR procedure success (or not). This work presents: the basic aspects of the laboratorial work conception; some difficulties related to the accuracy quality of arc parameters evaluation, of some usual measurement and data processing procedures; the adopted solutions to overcome such difficulties. The results already obtained support the basic conception of a gray type arc model, developed previously, allowed the establishment of adequate research type procedures for measurements and data processing, supplied a huge amount of data for arc modeling, giving basis to obtain arc parameters in an important range of conditions. New results are still expected to complete the range of conditions covered by the research project.
引用
收藏
页码:490 / +
页数:2
相关论文
共 6 条
  • [1] Single-Phase Auto-Reclosure Studies: Some Basic Aspects on Main Elements Representation
    Camara, Alessandra S. B.
    Portela, Carlos M. J. C.
    Tavares, Maria Cristina D.
    ICHVE 2008: 2008 INTERNATIONAL CONFERENCE ON HIGH VOLTAGE ENGINEERING AND APPLICATION, 2008, : 482 - 485
  • [2] Research on protective relaying and single-phase reclosure of 750 kV transmission line
    Li, Bin
    Li, Yongli
    He, Jiali
    Zheng, Yuping
    Sheng, Kun
    Guo, Zheng
    Dianli Xitong Zidonghua/Automation of Electric Power Systems, 2004, 28 (13): : 73 - 76
  • [3] Compensation of secondary arc currents during single-phase automatic reclosure of transmission line with single conductor transposition cycle
    Levinshtein, M.L.
    Khakimov, F.Z.
    Power engineering New York, 1988, 26 (05): : 41 - 47
  • [4] Research on Suppression of Secondary Arc Current under Different Fault Locations for 500kV Transmission Line
    Cui Ruochen
    Yin Zhongdong
    Wang Miaomiao
    Li Ke
    2010 ASIA-PACIFIC POWER AND ENERGY ENGINEERING CONFERENCE (APPEEC), 2010,
  • [5] Single-phase autoreclosure studies considering a robust and reliable secondary arc model based on a gray-box model
    Camara, Alessandra S.
    Portela, Carlos M.
    Tavares, Maria Cristina
    ICHVE 2008: 2008 INTERNATIONAL CONFERENCE ON HIGH VOLTAGE ENGINEERING AND APPLICATION, 2008, : 486 - +
  • [6] Investigation of Single Phase Reclosing Using Arc Model on the 500 kV Transmission Line from Mae Moh to Tha Ta Ko
    Ngamsanroaj, K.
    Premrudeepreechacharn, S.
    2009 ASIA-PACIFIC POWER AND ENERGY ENGINEERING CONFERENCE (APPEEC), VOLS 1-7, 2009, : 3595 - +