Empirical Reliability Models for Generator Circuit-Breakers

被引:0
|
作者
Palazzo, Mirko [1 ]
Delfanti, Maurizio [2 ]
机构
[1] ABB Switzerland Ltd, Brown Boveri Str 5, CH-8050 Zurich, Switzerland
[2] Politecnico Milano, I-420156 Milan, Italy
关键词
generator circuit-breaker; major failure; reliability; service experience;
D O I
暂无
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
The objective of this paper is to present an empirical reliability model for air-blast and SF6 generator circuit-breakers (GenCBs) which can be used to perform availability studies of different power station layouts. The main achievement of this work is an analytical formula which allows to model the reliability of air-blast GenCBs with an hazard rate that depends on the age of equipment. For SF6 GenCBs the hazard rate can be reasonably considered as constant. The investigation shows that SF6 GenCBs with hydro-mechanical spring operating mechanism is the most reliable technology for GenCB application. Specifically the average failure frequency of air-blast GenCBs is 2.7 times higher than that of SF6 GenCBs with pneumatic drive and even 5.6 times higher compared to SF6 GenCBs with hydro-mechanical spring operating mechanism. The average failure frequency of HVCBs is 2.5 times higher than that of SF6 GenCBs with hydro-mechanical spring operating mechanism according to the results of a failure survey conducted by a CIGRE working group on SF6 HVCBs. The reliability of different types of operating mechanism has been compared too. The results of the analysis show that a hydro-mechanical spring operating mechanism surveyed for GenCB applications is more reliable than spring, hydraulic or pneumatic operating mechanisms installed on HVCBs.
引用
下载
收藏
页数:7
相关论文
共 50 条
  • [1] GENERATOR CIRCUIT-BREAKERS FOR TODAY AND TOMORROW
    GARZON, RD
    IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1980, 99 (04): : 1315 - 1315
  • [2] SYNTHETIC TESTING METHOD FOR GENERATOR CIRCUIT-BREAKERS
    THURIES, E
    VANDOAN, P
    DAYET, J
    JOYEUXBOUILLON, B
    IEEE TRANSACTIONS ON POWER DELIVERY, 1986, 1 (01) : 179 - 184
  • [3] WHATS NEW ABOUT GENERATOR CIRCUIT-BREAKERS
    KOLARIK, PL
    IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1980, 99 (04): : 1316 - 1316
  • [4] RELIABILITY OF HIGH-VOLTAGE CIRCUIT-BREAKERS
    HOFFMANN, D
    ELEKTROTECHNISCHE ZEITSCHRIFT-ETZ, 1979, 100 (16-1): : 896 - 900
  • [5] SYNTHETIC TESTING OF CIRCUIT-BREAKERS EQUIPPED WITH A LOW OHMIC PARALLEL RESISTOR (WITH SPECIAL RESPECT TO GENERATOR CIRCUIT-BREAKERS)
    FROHLICH, KJ
    IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1985, 104 (08): : 2283 - 2288
  • [6] RELIABILITY OF HIGH-VOLTAGE CIRCUIT-BREAKERS
    KOPPL, G
    ERNI, H
    BROWN BOVERI REVIEW, 1973, 60 (04): : 128 - 133
  • [7] RELIABILITY PERFORMANCE EVALUATION OF POWER CIRCUIT-BREAKERS
    RAI, JS
    GROVER, MS
    QUINTANA, VH
    IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1978, 97 (02): : 328 - 328
  • [8] Cascading reliability model for HV circuit-breakers
    Choonhapran, P.
    Balzer, G.
    2007 IEEE LAUSANNE POWERTECH, VOLS 1-5, 2007, : 1770 - 1775
  • [9] Circuit-Breakers
    Scott, WM
    JOURNAL OF THE FRANKLIN INSTITUTE, 1904, 158 : 185 - 208
  • [10] Revision of TRV requirements for the application of generator circuit-breakers
    Palazzo, Mirko
    Popov, Marjan
    Marmolejo, Alejandro
    Delfanti, Maurizio
    ELECTRIC POWER SYSTEMS RESEARCH, 2016, 138 : 66 - 71