Bus Voltage Sensitivity Index Based Approach Against Voltage Collapse in Distribution Systems

被引:1
|
作者
Nweke, John N. [1 ]
Salau, Ayodeji Olalekan [2 ]
Ogbuefi, Uche C. [3 ]
机构
[1] Fed Polytech Kaura Namoda, Dept Elect Engn Technol, Kaura Namoda, Nigeria
[2] Afe Babalola Univ, Dept Elect Elect & Comp Engn, Ado Ekiti, Nigeria
[3] Univ Nigeria, Dept Elect Engn, Nsukka, Nigeria
关键词
Weak bus; Sensitivity; Voltage collapse; Optimization;
D O I
10.1109/DASA53625.2021.9682359
中图分类号
TP18 [人工智能理论];
学科分类号
081104 ; 0812 ; 0835 ; 1405 ;
摘要
The implementation of voltage collapse mitigation measures in power distribution systems was investigated through a bus voltage sensitivity index (BVSI) optimization method in this paper. Bus sensitivity analysis in a power system network uses voltage performance index optimization approaches to find weak buses that are vulnerable to voltage collapse. This paper proposed a method to identify those weak buses. Through the evaluation of headroom capacity of the network, the identified weak buses are then optimally connected with distributed generation (DG). This will have an impact on network voltage improvement, power loss reduction, and overall network reliability. The IEEE 14 bus distribution network system is used to test the effectiveness of the proposed method. The results suggest that among all of the identified candidate buses, buses 12 and 14 are vulnerable to system voltage failure. However, bus 14 has the highest sensitivity index, hence the best optimal location for DG. The results also show that those susceptible buses for voltage collapse were improved and power loss was reduced to 10.32% after the mitigation measures were applied.
引用
收藏
页数:5
相关论文
共 50 条
  • [1] Voltage Collapse Based Critical Bus Ranking
    Shankar, Shobha
    Ananthapadmanabha, T.
    [J]. ADVANCED COMPUTING, PT III, 2011, 133 : 400 - +
  • [2] Voltage Sensitivity Analysis Based Bus Voltage Regulation in Transmission Systems with UPFC Series Converter
    Song, Pengcheng
    Xu, Zheng
    Luo, Chenxi
    Cai, Hui
    Xie, Zhenjian
    [J]. IECON 2017 - 43RD ANNUAL CONFERENCE OF THE IEEE INDUSTRIAL ELECTRONICS SOCIETY, 2017, : 483 - 488
  • [3] VOLTAGE COLLAPSE PROXIMITY INDEX DETERMINATION USING VOLTAGE PHASORS APPROACH
    GUBINA, F
    STRMCNIK, B
    [J]. IEEE TRANSACTIONS ON POWER SYSTEMS, 1995, 10 (02) : 788 - 793
  • [4] VOLTAGE COLLAPSE PROXIMITY INDEX DETERMINATION USING VOLTAGE PHASORS APPROACH - DISCUSSION
    WUNDERLICH, S
    FISCHL, R
    GUBINA, F
    STRMCNIK, B
    [J]. IEEE TRANSACTIONS ON POWER SYSTEMS, 1995, 10 (02) : 794 - 794
  • [5] Effective Implementation of Mitigation Measures against Voltage Collapse in Distribution Power Systems
    Salau, Ayodeji Olalekan
    Nweke, John N.
    Ogbuefi, Uche C.
    [J]. PRZEGLAD ELEKTROTECHNICZNY, 2021, 97 (10): : 65 - 68
  • [6] VOLTAGE COLLAPSE PREDICTION USING AN IMPROVED SENSITIVITY APPROACH
    CRISAN, O
    LIU, M
    [J]. ELECTRIC POWER SYSTEMS RESEARCH, 1994, 28 (03) : 181 - 190
  • [7] Enhanced Voltage Stability Assessment Index Based Planning Approach for Mesh Distribution Systems
    Kazmi, Syed Ali Abbas
    Janjua, Abdul Kashif
    Shin, Dong Ryeol
    [J]. ENERGIES, 2018, 11 (05)
  • [8] Line collapse proximity index for prediction of voltage collapse in power systems
    Tiwari, Rajive
    Niazi, K. R.
    Gupta, Vikas
    [J]. INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2012, 41 (01) : 105 - 111
  • [9] Voltage phasors approach to voltage instability in distribution systems
    Strmcnik, Bostjan
    Gubina, Ferdinand
    [J]. Elektrotehniski Vestnik/Electrotechnical Review, 1994, 61 (1-2): : 13 - 17
  • [10] STUDY OF VOLTAGE COLLAPSE AT CONVERTER BUS IN ASYNCHRONOUS MTDC AC SYSTEMS
    PADIYAR, KR
    RAMAN, VK
    [J]. INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 1993, 15 (01) : 45 - 53