Coordinated Control Strategy for a Hybrid Wind Farm with DFIG and PMSG under Symmetrical Grid Faults

被引:14
|
作者
Li, Jiawei [1 ]
Yao, Jun [1 ]
Zeng, Xin [1 ]
Liu, Ruikuo [1 ]
Xu, Depeng [1 ]
Wang, Caisheng [2 ]
机构
[1] Chongqing Univ, Sch Elect Engn, State Key Lab Power Transmiss Equipment & Syst Se, Chongqing 400044, Peoples R China
[2] Wayne State Univ, Dept Elect & Comp Engn, Detroit, MI 48202 USA
来源
ENERGIES | 2017年 / 10卷 / 05期
基金
中国国家自然科学基金;
关键词
wind power generation; hybrid wind farm; symmetrical grid faults; low voltage ride through (LVRT); reactive current limit; current allocation principle; FED INDUCTION GENERATOR; POWER-SYSTEMS; RIDE-THROUGH; TURBINES;
D O I
10.3390/en10050669
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
This paper presents a coordinated control strategy for a hybrid wind farm with doubly-fed induction generator (DFIG)-and direct-driven permanent-magnet synchronous generator (PMSG)-based wind turbines under symmetrical grid faults. The proposed low-voltage ride-through (LVRT) strategy is based on a novel current allocation principle and is implemented for individual DFIG-or PMSG-based wind turbines. No communication equipment between different wind power generators is required. By monitoring the local voltages and active power outputs of the corresponding wind generators, the proposed control strategy can control the hybrid wind farm to provide the maximum reactive power to support the grid voltage during a symmetrical grid fault. As a result, the reduction in the active power output from the hybrid wind farm can be decreased, which also helps avoid generator over-speed issues and supply active power support for the power grid. In addition, the reactive current upper limits of DFIG-and PMSG-based sub-wind farms are investigated by considering different active power outputs and different grid voltage dip depths, and the feasible regions of the two types of sub-wind farms for meeting the LVRT requirements are further studied. Finally, the effectiveness of the proposed coordinated LVRT control strategy for the hybrid wind farm is validated by simulation and experimental results.
引用
收藏
页数:21
相关论文
共 50 条
  • [1] Coordinated control of a hybrid wind farm with DFIG-based and PMSG-based wind power generation systems under asymmetrical grid faults
    Yao, Jun
    Pei, Jinxin
    Xu, Depeng
    Liu, Ruikuo
    Wang, Xuewei
    Wang, Caisheng
    Li, Yu
    [J]. RENEWABLE ENERGY, 2018, 127 : 613 - 629
  • [2] Coordinated control of a hybrid wind farm with PMSG and FSIG during asymmetrical grid fault
    Yao, Jun
    Li, Jiawei
    Guo, Lisha
    Liu, Ruikuo
    Xu, Depeng
    [J]. INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2018, 95 : 287 - 300
  • [3] A Coordinated Control of Grid connected PMSG based Wind Energy Conversion System Under Grid Faults
    Dey, Papan
    Datta, Manoj
    Fernando, Nuwantha
    [J]. 2017 IEEE 3RD INTERNATIONAL FUTURE ENERGY ELECTRONICS CONFERENCE AND ECCE ASIA (IFEEC 2017-ECCE ASIA), 2017, : 597 - 602
  • [4] Study on Coordinated Voltage Control Strategy of DFIG Wind Farm
    Chen, Hui-fen
    Qiao, Ying
    Lu, Zong-xiang
    [J]. 2012 IEEE POWER AND ENERGY SOCIETY GENERAL MEETING, 2012,
  • [5] Coordinated Control Strategy for Grid Connected DFIG wind System under Voltage Imbalance
    Ramalingeswar, J. T.
    Subramanian, K.
    [J]. 2017 IEEE INTERNATIONAL CONFERENCE ON POWER, CONTROL, SIGNALS AND INSTRUMENTATION ENGINEERING (ICPCSI), 2017, : 1946 - 1951
  • [6] ESS equipped DFIG wind farm with coordinated power control under grid fault conditions
    Najaty Mazgar, Farshid
    Tarafdar Hagh, Mehrdad
    Tohidi, Sajjad
    [J]. JOURNAL OF POWER ELECTRONICS, 2021, 21 (01) : 173 - 183
  • [7] ESS equipped DFIG wind farm with coordinated power control under grid fault conditions
    Farshid Najaty Mazgar
    Mehrdad Tarafdar Hagh
    Sajjad Tohidi
    [J]. Journal of Power Electronics, 2021, 21 : 173 - 183
  • [8] Coordinated Control of DFIG Subjected to Grid Faults
    Liu, Sumei
    Zhang, Li
    Bi, Tianshu
    Jing, Haiwei
    Xue, Ancheng
    Yang, Qixun
    [J]. 2014 INTERNATIONAL CONFERENCE ON POWER SYSTEM TECHNOLOGY (POWERCON), 2014, : 2891 - 2896
  • [9] Coordinated Rotor-Side Control Strategy for Doubly-Fed Wind Turbine under Symmetrical and Asymmetrical Grid Faults
    Yan, Quanchun
    Yuan, Chao
    Gu, Wen
    Liu, Yanan
    Tang, Yiming
    [J]. Energy Engineering: Journal of the Association of Energy Engineering, 2023, 120 (01): : 49 - 68
  • [10] Capacity Configuration and Coordinated Operation of a Hybrid Wind Farm With FSIG-Based and PMSG-Based Wind Farms During Grid Faults
    Yao, Jun
    Guo, Lisha
    Zhou, Te
    Xu, Depeng
    Liu, Ruikuo
    [J]. IEEE TRANSACTIONS ON ENERGY CONVERSION, 2017, 32 (03) : 1188 - 1199