Soil temperature affected by heat exchanger when ground-coupled source heat pump running

被引:2
|
作者
Zhou Zhi-hua [1 ]
Zhang Zhi-hong [2 ]
Liu Xiao-hai [3 ]
Zhang Shi-hua [1 ]
机构
[1] Tianjin Univ, Sch Environm Sci & Technol, Tianjin 300072, Peoples R China
[2] Hebei Inst Architecture & Civil Engn, Urban Construct Dept, Zhangjiakou 075024, Peoples R China
[3] China Construct Design Int, Beijing 100029, Peoples R China
关键词
ground-coupled source heat pump; heat exchanger; effective radius; temperature;
D O I
10.1007/s11771-007-0394-4
中图分类号
TF [冶金工业];
学科分类号
0806 ;
摘要
By using some temperature sensors in-stalled during construction, the original temperature under ground was tested in certain office building in Tianjin. Temperatures around heat exchangers in different depths and different distances were also tested during heat pump running. The results indicate that the effective radius of heat exchanger in winter is 1.5-2.5 m, and the space between exchangers of 5 in can satisfy system's running. But in order to ensure the heat pump run steadily for a long time, soil temperature should be maintained stably. Heat load in winter should be more than cool load in summer in Tianjin.
引用
收藏
页码:202 / 204
页数:3
相关论文
共 50 条
  • [1] Ground-coupled heat pump system with a buried underfloor heat exchanger
    Den Braven, Karen R.
    Drown, David C.
    [J]. American Society of Mechanical Engineers, Advanced Energy Systems Division (Publication) AES, 1992, 28 : 97 - 101
  • [2] Dynamic Soil Temperature of Ground-Coupled Heat Pump System in Cold Region
    You, Tian
    Wu, Wei
    Wang, Baolong
    Shi, Wenxing
    Li, Xianting
    [J]. PROCEEDINGS OF THE 8TH INTERNATIONAL SYMPOSIUM ON HEATING, VENTILATION AND AIR CONDITIONING, VOL 2: HVAC&R COMPONENT AND ENERGY SYSTEM, 2014, 262 : 439 - 448
  • [3] The study of soil temperature change rule around buried pipes in ground-coupled source heat pump
    Zhou, Zhihua
    Zhang, Juerong
    Zhang, Shihua
    [J]. Taiyangneng Xuebao/Acta Energiae Solaris Sinica, 2009, 30 (11): : 1487 - 1490
  • [4] THE INFLUENCE OF SOIL HEAT IMBALANCE ON GROUND-COUPLED HEAT PUMP SYSTEM AND STRATEGY
    Fan, Rui
    Gao, Yan
    Song, Yingqian
    Long, Weiding
    [J]. PROCEEDINGS OF THE ASME INTERNATIONAL MECHANICAL ENGINEERING CONGRESS AND EXPOSITION - 2010, VOL 5, PTS A AND B, 2012, : 1183 - 1188
  • [5] Numerical modelling of transient soil temperature distribution for horizontal ground heat exchanger of ground source heat pump
    Kayaci, Nurullah
    Demir, Hakan
    [J]. GEOTHERMICS, 2018, 73 : 33 - 47
  • [6] Ground-coupled heat pump and energy storange
    [J]. 1600, ASHRAE (55):
  • [7] GROUND-COUPLED HEAT-PUMP RESEARCH
    BOSE, J
    PARKER, J
    [J]. ASHRAE JOURNAL-AMERICAN SOCIETY OF HEATING REFRIGERATING AND AIR-CONDITIONING ENGINEERS, 1983, 25 (05): : 59 - 59
  • [8] THE GROUND-COUPLED HEAT PUMP TECHNOLOGY IN CHINA
    Fang, Zhaohong
    Diao, Nairen
    Cui, Ping
    Yu, Mingzhi
    [J]. PROCEEDINGS OF THE FIRST INTERNATIONAL CONFERENCE ON SUSTAINABLE URBANIZATION (ICSU 2010), 2010, : 735 - 740
  • [9] Ground-Coupled Heat Pump and Energy Storage
    Lohrenz, Ed
    Almeida, Sergio
    [J]. ASHRAE JOURNAL, 2013, 55 (04) : 14 - +
  • [10] The modeling of ground-coupled heat pump systems
    Qu, Yun-Xia
    Li, An-Gui
    Zhang, Lin-Hua
    Fang, Zhao-Hong
    [J]. Xi'an Jianzhu Keji Daxue Xuebao/Journal of Xi'an University of Architecture and Technology, 2007, 39 (02): : 235 - 239