Fault Detection Utilizing Convolution Neural Network on Timeseries Synchrophasor Data From Phasor Measurement Units

被引:8
|
作者
Alqudah, Mohammad [1 ]
Pavlovski, Martin [1 ]
Dokic, Tatjana [3 ]
Kezunovic, Mladen [3 ]
Hu, Yi [4 ]
Obradovic, Zoran [2 ]
机构
[1] Temple Univ, Ctr Data Analyt & Biomed Informat, Philadelphia, PA 19122 USA
[2] Temple Univ, Philadelphia, PA 19122 USA
[3] Texas A&M Univ, College Stn, TX 77843 USA
[4] Quanta Technol, Raleigh, NC 27607 USA
关键词
Phasor measurement units; Convolutional neural networks; Convolution; Fault detection; Feature extraction; Support vector machines; Frequency measurement; Big data applications; event detection; machine learning; phasor measurement units; power system faults; dimensionality reduction; smart grids; time series analysis; neural networks; convolutional neural networks; EVENT DETECTION;
D O I
10.1109/TPWRS.2021.3135336
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
An end-to-end supervised learning method is proposed for fault detection in the electric grid using Big Data from multiple Phasor Measurement Units (PMUs). The approach consists of preprocessing steps aimed at reducing data noise and dimensionality, followed by utilization of six classification models considered for detecting faults. Three of the models were variants of Convolutional Neural Network (CNN) architectures that consider a single type of measurement (voltage, current or frequency) at all PMUs or all types together also at all PMUs. CNN based models were compared to traditional methods of Logistic Regression (LR), Multi-layer Perceptron (MLP) and Support Vector Machine (SVM). Evaluation was conducted on two-year data measured by PMUs at 37 locations in a large electric grid. The response variable for classification were extracted from the grid-wide outage event log. Experiments show that CNN-based models outperformed traditional methods on one year out-of-sample outage detection over the entire grid.
引用
收藏
页码:3434 / 3442
页数:9
相关论文
共 50 条
  • [1] Robust algorithm to estimate fault synchrophasor from fault-transient synchrophasor in phasor data concentrator
    Das, Sarasij
    Sidhu, Tarlochan
    [J]. IET GENERATION TRANSMISSION & DISTRIBUTION, 2015, 9 (02) : 124 - 132
  • [2] Fault Diagnosis to Nuclear Power Plant System Based on TimeSeries Convolution Neural Network
    Li, XianLing
    Han, DongJiang
    Dai, XinFa
    Lv, ShuYu
    Tao, Mo
    Zheng, Wei
    Tang, YiBin
    [J]. WIRELESS COMMUNICATIONS & MOBILE COMPUTING, 2022, 2022
  • [3] False Data Injection Detection for Phasor Measurement Units
    Almasabi, Saleh
    Alsuwian, Turki
    Awais, Muhammad
    Irfan, Muhammad
    Jalalah, Mohammed
    Aljafari, Belqasem
    Harraz, Farid A.
    [J]. SENSORS, 2022, 22 (09)
  • [4] Transmission Line Fault Detection and Identification in an Interconnected Power Network using Phasor Measurement Units
    Khan, Abdul Qayyum
    Ullah, Qudrat
    Sarwar, Muhammad
    Gul, Sufi Tabassum
    Iqbal, Naeem
    [J]. IFAC PAPERSONLINE, 2018, 51 (24): : 1356 - 1363
  • [5] Detection of Bad Data in Phasor Measurement Units Using Distributed Approach
    Thomas, Polly
    Skariah, Emil Ninan
    Varghese, Sheena Thomas
    [J]. 2017 INNOVATIONS IN POWER AND ADVANCED COMPUTING TECHNOLOGIES (I-PACT), 2017,
  • [6] Research on Bearing Fault Detection Based on Convolution Neural Network
    Li, Xiaolei
    Ding, Pengli
    Shi, Xiaobing
    [J]. 2017 CHINESE AUTOMATION CONGRESS (CAC), 2017, : 5130 - 5134
  • [7] Low-Resolution Fault Localization Using Phasor Measurement Units with Community Detection
    Jamei, Mahdi
    Scaglione, Anna
    Peisert, Sean
    [J]. 2018 IEEE INTERNATIONAL CONFERENCE ON COMMUNICATIONS, CONTROL, AND COMPUTING TECHNOLOGIES FOR SMART GRIDS (SMARTGRIDCOMM), 2018,
  • [8] Neural network-based power system dynamic state estimation using hybrid data from SCADA and phasor measurement units
    Goleijani, Sassan
    Ameli, Mohammad Taghi
    [J]. INTERNATIONAL TRANSACTIONS ON ELECTRICAL ENERGY SYSTEMS, 2018, 28 (02):
  • [9] Voltage Instability Detector Based on Phasor Measurement Units Using Artificial Neural Network
    Ali, Ahmed K.
    El-Amary, Noha H.
    Ibrahim, A. M.
    Mekhamer, Said F.
    [J]. 2015 WORKSHOP ON ENGINEERING APPLICATIONS - INTERNATIONAL CONGRESS ON ENGINEERING (WEA), 2015,
  • [10] Accurate Fault Detection Of Distribution Network With Optimal Placement of Phasor Measurement Unit
    Ray, Papia
    Beura, Subal
    [J]. PROCEEDINGS OF THE 2019 INTERNATIONAL CONFERENCE ON INTELLIGENT SUSTAINABLE SYSTEMS (ICISS 2019), 2019, : 76 - 81