Oil health index calculation and incipient fault diagnosis in power transformers using fuzzy logic

被引:3
|
作者
Manoj, T. [1 ]
Ranga, C. [1 ]
机构
[1] Natl Inst Technol NIT, Dept Elect Engn, Srinagar 190006, Jammu & Kashmir, India
关键词
transformer oil; condition monitoring; dissolved gas analysis; health index; incipient faults; DISSOLVED-GAS ANALYSIS; AGING CHARACTERISTICS; PAPER DETERIORATION; NATURAL ESTER; INSULATION; SYSTEM; PERFORMANCE; UNCERTAINTY; DGA;
D O I
10.1784/insi.2022.64.1.28
中图分类号
TH7 [仪器、仪表];
学科分类号
0804 ; 080401 ; 081102 ;
摘要
In this paper, a new fuzzy logic (FL) model is proposed for assessing the health status of power transformers. In addition, the detection of incipient faults is achieved where two or more faults exist simultaneously. The process is carried out by integrating a fuzzy logic model with the conventional International Electric Committee (IEC) ratio codes method. As transformer oil insulation deteriorates, excess percentages of dissolved gases such as hydrogen, methane, ethane, acetylene and ethylene are induced within the trasnformer. The status of oil health is generally assessed using these gas concentrations. Therefore, in the proposed model, 31 fuzzy rules are designed based on the severity levels of these gases in order to determine the health index (HI) of the oil. Similarly, any incipient faults along with their severity are also detected using the proposed fuzzy logic model with 22 expert rules. To validate the proposed fuzzy logic model, the data for dissolved gases in 50 working transformers operated by the Himachal Pradesh State Electricity Board (HPSEB), India, are collected. Over the years, calculations for the health index have been performed using conventional dissolved gas analysis (DGA) interpretation methods. The shortcomings of these methods, such as non-reliability and inaccuracy, are successfully overcome using the proposed model. The detection of incipient faults is normally performed using key gas, Rogers ratios, the Duval triangle, Dornenburg ratios, modified Rogers ratios and the IEC ratio codes methods. The shortcomings of these conventional ratio code methods in identifying incipient faults in some typical cases, ie multiple incipient fault cases, are overcome by the proposed fuzzy logic model.
引用
收藏
页码:28 / 37
页数:10
相关论文
共 50 条
  • [1] Oil health index calculation and incipient fault diagnosis in power transformers using fuzzy logic
    Manoj, T.
    Ranga, C.
    [J]. Insight: Non-Destructive Testing and Condition Monitoring, 2022, 64 (01): : 28 - 37
  • [2] Calculation of a Health Index for Oil-Immersed Transformers Rated Under 69 kV Using Fuzzy Logic
    Abu-Elanien, Ahmed E. B.
    Salama, M. M. A.
    Ibrahim, M.
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2012, 27 (04) : 2029 - 2036
  • [3] Incipient Fault Diagnosis of Transformer by DGA Using Fuzzy Logic
    Apte, Sandip
    Somalwar, Rahul
    Wajirabadkar, Ashwini
    [J]. 2018 IEEE INTERNATIONAL CONFERENCE ON POWER ELECTRONICS, DRIVES AND ENERGY SYSTEMS (PEDES), 2018,
  • [4] Integrated Fuzzy Approach for Incipient Fault Detection in Power Transformers
    Patel, R. N.
    Thakur, H. S.
    [J]. 2016 IEEE INDUSTRIAL ELECTRONICS AND APPLICATIONS CONFERENCE (IEACON), 2016, : 211 - 218
  • [5] Diagnosis of Power Transformers Faults using Fuzzy Logic Method
    Atalar, Fatih
    Kuntman, Ayten
    [J]. 2016 NATIONAL CONFERENCE ON ELECTRICAL, ELECTRONICS AND BIOMEDICAL ENGINEERING (ELECO), 2016, : 28 - 32
  • [6] A Fuzzy System for Detection of Incipient Fault in Power Transformers Based on Gas-in-Oil Analysis
    de Aquino, Ronaldo R. B.
    Lira, Milde M. S.
    Filgueiras, Taciana
    Ferreira, Heldemarcio
    Nobrega Neto, Otoni
    Silva, Agnaldo M. S.
    Asfora, Viviane K.
    [J]. 2010 IEEE INTERNATIONAL CONFERENCE ON FUZZY SYSTEMS (FUZZ-IEEE 2010), 2010,
  • [7] Multiparameter-Based Fuzzy Logic Health Index Assessment for Oil-Immersed Power Transformers
    Mharakurwa, Edwell Tafara
    Goboza, Rutendo
    [J]. ADVANCES IN FUZZY SYSTEMS, 2019, 2019
  • [8] Incipient Fault Diagnosis in Power Transformers by Clustering and Adapted KNN
    Islam, Md Mominul
    Lee, Gareth
    Hettiwatte, Sujeewa Nilendra
    [J]. PROCEEDINGS OF THE 2016 AUSTRALASIAN UNIVERSITIES POWER ENGINEERING CONFERENCE (AUPEC), 2016,
  • [9] A New Fuzzy Logic Method for Transformer Incipient Fault Diagnosis
    Su, Charles Q.
    [J]. 2016 IEEE INTERNATIONAL CONFERENCE ON FUZZY SYSTEMS (FUZZ-IEEE), 2016, : 324 - 327
  • [10] A Fault Diagnosis Method Combined Fuzzy Logic with CMAC Neural Network for Power Transformers
    Zhao, Xiaoxiao
    Yun, Yuxin
    [J]. PROCEEDINGS OF THE 2009 CHINESE CONFERENCE ON PATTERN RECOGNITION AND THE FIRST CJK JOINT WORKSHOP ON PATTERN RECOGNITION, VOLS 1 AND 2, 2009, : 710 - 714