Condition monitoring system for circuit breaker based on substation automation system

被引:0
|
作者
Tang, Z. [1 ]
Zou, Y. [1 ]
机构
[1] HUST, Wuhan, Peoples R China
关键词
D O I
10.1109/UPEC.2006.367603
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Condition monitoring of circuit breaker is preference for cost saving in power utilities. However, extensive condition monitoring of circuit breaker is a hard task considering its tremendous number. Circuit breaker time, which is composed of opening time and arcing time, as well as its variation trends, can be used as an index to represent condition of mechanical and dielectric component of circuit breaker. Since the digital relay and digital fault recorder that can record dynamic process of circuit breaker operation, it is especially attractive to extract this data for circuit breaker information without hardware investment. In order to deduce circuit breaker time with transient data logged in substation automation system, a substation automation information management system is developed in this paper. The transient data follows transient data transformation standard (COMTRADE) is concentrated in controlling center. The information management system parses the composition and format of the logged data according COMTRADE, hence calculate and visualize the circuit breaker time and its variation trends.
引用
收藏
页码:861 / 865
页数:5
相关论文
共 50 条
  • [1] Condition Monitoring System for Circuit Breaker Based on Substation Automation System
    Tang, Zhong
    2008 3RD INTERNATIONAL CONFERENCE ON INTELLIGENT SYSTEM AND KNOWLEDGE ENGINEERING, VOLS 1 AND 2, 2008, : 1448 - 1452
  • [2] Design and Development of Condition Monitoring System for Circuit Breaker Based on Vibration Signal
    Liang, Zhirui
    2015 5TH INTERNATIONAL CONFERENCE ON ELECTRIC UTILITY DEREGULATION AND RESTRUCTURING AND POWER TECHNOLOGIES (DRPT 2015), 2015, : 1483 - 1487
  • [3] Research on Intelligent Communication System for Circuit Breaker Condition Monitoring
    Deng, Qinghong
    Zhang, Hao
    Liao, Minfu
    Zhang, Haoxue
    Fu, Yifan
    Gai, Lujie
    2018 INTERNATIONAL SYMPOSIUM ON POWER ELECTRONICS AND CONTROL ENGINEERING (ISPECE 2018), 2019, 1187
  • [4] Research of On-line Monitoring System of the Condition of Circuit Breaker Based on ARM and FPGA
    Huang, Jian
    Rao, Peilei
    Hu, Xiaoguang
    Xiao, Jin
    2009 IEEE INTERNATIONAL CONFERENCE ON CONTROL AND AUTOMATION, VOLS 1-3, 2009, : 201 - 205
  • [5] Incorporating a Condition Monitoring Based Aging Failure Model of a Circuit Breaker in Substation Reliability Assessment
    Zhong, Jun
    Li, Wenyuan
    Billinton, Roy
    Yu, Juan
    IEEE TRANSACTIONS ON POWER SYSTEMS, 2015, 30 (06) : 3407 - 3415
  • [6] Integrated Substation Automation and Monitoring System
    Lakshmi, S. Gowri
    Kumar, S. Suresh
    2013 IEEE INTERNATIONAL CONFERENCE ON COMPUTATIONAL INTELLIGENCE AND COMPUTING RESEARCH (ICCIC), 2013, : 654 - 657
  • [7] Design of trip current monitoring system for circuit breaker condition assessment
    Stephen, B.
    Strachan, S. M.
    McArthur, S. D. J.
    McDonald, J. R.
    Hamilton, K.
    IET GENERATION TRANSMISSION & DISTRIBUTION, 2007, 1 (01) : 89 - 95
  • [8] A practical circuit breaker monitoring system
    Sheng, S
    Li, KK
    Chan, WL
    Zeng, XJ
    Duan, XZ
    CONFERENCE RECORD OF THE 2005 IEEE INDUSTRY APPLICATIONS CONFERENCE, VOLS 1-4, 2005, : 867 - 872
  • [9] Substation Automation Matlab and OPC Driven Substation Monitoring System
    Dahal, Ujjwal Deep
    Cheten, Dhendup
    2016 INTERNATIONAL CONFERENCE ON MICROELECTRONICS, COMPUTING AND COMMUNICATIONS (MICROCOM), 2016,
  • [10] Circuit Breaker Diagnostic System Using Digital Substation IED
    Baek, Minwoo
    Son, Jinwoo
    Gu, Chiwuk
    Kim, Taehee
    2022 6TH INTERNATIONAL CONFERENCE ON ELECTRIC POWER EQUIPMENT - SWITCHING TECHNOLOGY (ICEPE-ST), 2022, : 401 - 405