Partial Discharge Activities in Transformer Insulation under Steep Front Voltages

被引:0
|
作者
Khanali, M. [1 ]
Jayaram, S. H. [1 ]
机构
[1] Univ Waterloo, Elect & Comp Engn, Waterloo, ON N2L 3G1, Canada
关键词
transformer insulation; wind energy; partial discharge activity; dissolved gas analysis; hydrogen content; distorted voltage waveform;
D O I
暂无
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Gassing problems and premature insulation failures of wind turbine transformers have been documented lately, indicating concerns with insulation reliability of power electronic converter-fed devices. This fact shows that the transformer insulation system degrades under high dV/dt voltages generated in wind energy plants at a faster rate than those operated under power frequency AC voltages of the same amplitude. To study such degradation processes, unlike the cases of AC or DC voltages, under high dV/dt voltages, interferences coming from the pulse generator and fast oscillatory input voltages pose substantial challenges. In this work, a method to evaluate the effect of voltage waveform characteristics such as rate of rise (ROR) on the extent of partial discharge activities, based on the changes in hydrogen content in the transformer oil/paper insulation system is investigated.
引用
收藏
页码:204 / 207
页数:4
相关论文
共 50 条
  • [1] Partial Discharge Activities of Pressboard/oil Insulation under AC plus DC Voltages
    Jiang, Tianyan
    Cavallini, A.
    Montanari, G. C.
    Li, Jian
    PROCEEDINGS OF THE 2013 IEEE INTERNATIONAL CONFERENCE ON SOLID DIELECTRICS (ICSD 2013), VOLS 1 AND 2, 2013, : 267 - 270
  • [2] THE ELECTRICAL BREAKDOWN CHARACTERISTICS OF OIL-PAPER INSULATION UNDER STEEP-FRONT IMPULSE VOLTAGES
    VANDERMAAR, AJ
    WANG, M
    NEILSON, JB
    SRIVASTAVA, KD
    IEEE TRANSACTIONS ON POWER DELIVERY, 1994, 9 (04) : 1926 - 1935
  • [3] UHF Technique for Identification of Partial Discharge in a Composite Insulation Under AC and DC voltages
    Sarathi, R.
    Koperundevi, G.
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2008, 15 (06) : 1724 - 1730
  • [4] Breakdown processes in transformer insulation under LI voltages
    Liu, RS
    Jaksts, A
    ICDL: 2005 IEEE INTERNATIONAL CONFERENCE ON DIELECTRIC LIQUIDS, 2005, : 75 - 78
  • [5] Understanding Surface Discharge Activity in Copper Sulphide Diffused Transformer Insulation under Harmonic AC Voltages
    Sarathi, R.
    Sheema, I. P. Merin
    2013 2ND INTERNATIONAL CONFERENCE ON ELECTRIC POWER EQUIPMENT - SWITCHING TECHNOLOGY (ICEPE-ST), 2013,
  • [6] Partial discharge pattern analysis of modeled insulation defects in transformer insulation
    Massingue, Feliciano
    Meijer, Sander
    Agoris, Pantelis D.
    Smit, Johan J.
    Lopez-Roldan, Jose
    CONFERENCE RECORD OF THE 2006 IEEE INTERNATIONAL SYMPOSIUM ON ELECTRICAL INSULATION, 2006, : 542 - +
  • [7] Very fast front transient voltages & dielectric withstand effects on transformer insulation
    Raja, K
    Devaux, F
    Lelaidier, S
    Girodet, A
    2002 ANNUAL REPORT CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA, 2002, : 506 - 509
  • [8] Partial discharge process in transformer oil and electrical insulation paper under DC stress
    Sha, Yanchao
    Zhou, Yuanxiang
    Nie, Dexin
    Wu, Zhirong
    Deng, Jiangang
    Lu, Licheng
    Gaodianya Jishu/High Voltage Engineering, 2014, 40 (01): : 80 - 86
  • [9] Partial discharge behavior on PI film with microgap under steep-front step voltage
    Kimura, K
    Itaya, S
    Hikita, M
    CONFERENCE RECORD OF THE 2002 IEEE INTERNATIONAL SYMPOSIUM ON ELECTRICAL INSULATION, 2002, : 1 - 4
  • [10] Partial discharge diagnosis of stator insulation using damped AC voltages
    Gulski, E.
    Meijer, S.
    van Breen, H. J.
    Seitz, P. P.
    de Vries, F.
    Petzold, F.
    CONFERENCE RECORD OF THE 2006 IEEE INTERNATIONAL SYMPOSIUM ON ELECTRICAL INSULATION, 2006, : 6 - +