Faulty Operation of Coils' and Humidifier Valves in a Typical Air-Handling Unit: Experimental Impact Assessment of Indoor Comfort and Patterns of Operating Parameters under Mediterranean Climatic Conditions

被引:2
|
作者
Rosato, Antonio [1 ]
Guarino, Francesco [1 ]
El Youssef, Mohammad [1 ]
Capozzoli, Alfonso [1 ]
Masullo, Massimiliano [1 ]
Maffei, Luigi [1 ]
机构
[1] Univ Campania Luigi Vanvitelli, Dept Architecture & Ind Design, Via San Lorenzo 4, I-81031 Aversa, Italy
关键词
heating; ventilation and air-conditioning systems; air-handling unit; heating coil valve stuck; cooling coil valve stuck; humidifier valve stuck; faulty experimental data; fault impact scenario; fault detection and diagnosis; energy management and efficiency; SYSTEMS; PERFORMANCE; DIAGNOSTICS; STRATEGY; DESIGN;
D O I
10.3390/en15186781
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Data-driven Automated Fault Detection and Diagnosis (AFDD) are recognized as one of the most promising options to improve the efficiency of Air-Handling Units (AHUs). In this study, the field operation of a typical single-duct dual-fan constant air volume AHU is investigated through a series of experiments carried out under Mediterranean (southern Italy) climatic conditions considering both fault-free and faulty scenarios. The AHU performances are analyzed while artificially introducing the following five different typical faults: (1) post-heating coil valve stuck at 100% (always open); (2) post-heating coil valve stuck at 0% (always closed); (3) cooling coil valve stuck at 100% (always open); (4) cooling coil valve stuck at 0% (always closed); (5) humidifier valve stuck at 0% (always closed). The measured faulty data are compared against the corresponding fault-free performance measured under the same boundary conditions with the aim of assessing the faults' impact on both thermal/hygrometric indoor conditions, as well as patterns of 16 different key operating parameters. The results of this study can help building operators and facility engineers in identifying faults' symptoms in typical AHUs and facilitate the related development of new AFDD tools.
引用
收藏
页数:38
相关论文
共 3 条
  • [1] Experimental assessment of ground-truth faults in a typical single-duct dual-fan air-handling unit under Mediterranean climatic conditions: Impact scenarios of sensors? offset and fans? failure
    Rosato, Antonio
    Guarino, Francesco
    El Youssef, Mohammad
    Capozzoli, Alfonso
    Masullo, Massimiliano
    Maffei, Luigi
    [J]. ENERGY AND BUILDINGS, 2022, 275
  • [2] Healthy and Faulty Experimental Performance of a Typical HVAC System under Italian Climatic Conditions: Artificial Neural Network-Based Model and Fault Impact Assessment
    Rosato, Antonio
    Guarino, Francesco
    Sibilio, Sergio
    Entchev, Evgueniy
    Masullo, Massimiliano
    Maffei, Luigi
    [J]. ENERGIES, 2021, 14 (17)
  • [3] Experimental assessment of the impact of natural ventilation on indoor air quality and thermal comfort conditions of educational buildings in the Eastern Mediterranean region during the heating period
    Heracleous, C.
    Michael, A.
    [J]. JOURNAL OF BUILDING ENGINEERING, 2019, 26