Polymer oxidation and water treeing

被引:39
|
作者
Bulinski, AT [1 ]
Crine, JP
Noirhomme, B
Densley, RJ
Bamji, S
机构
[1] Natl Res Council Canada, Ottawa, ON, Canada
[2] Inst Rech Hydro Quebec, Varennes, PQ J3X 1S1, Canada
关键词
D O I
10.1109/94.708273
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
In order to determine whether or not oxidation of polymer influences water treeing, more than 200 vented and bow-tie trees from 31 field-aged cables were investigated. Micro-IR spectroscopy analysis has not shown any consistent excess of carbonyl content in water trees as compared with the adjacent non-treed regions of the insulation. Although the levels of carbonyl content of the bulk of the polymer within the treed regions are similar to those in untreed regions of the polymer, vented trees are more susceptible to oxidation if subjected to high temperatures in the presence of oxygen. It was observed that vented trees initiate at similar rates in XLPE in either a nitrogen or air atmosphere. This indicates that tree initiation is rather independent of the presence of oxygen. However, the tree growth rate is slower in nitrogen than in air, the actual difference being affected by the type of ionic solution used. This further suggests that some, not yet known, chemical reactions between oxygen, XLPE and ions play an important role during water tree propagation. The IR absorption band at (1585 cm(-1), typical of carboxylates, was detected in some water trees. It should be noted that the large absorption band of water at (1640 cm(-1) often masks the smaller carboxylate band. Under laboratory conditions carboxylate groups were detected on oxidized nontreed XLPE surfaces. These results do not imply that carboxylates are responsible for tree propagation but confirm only that carboxylate groups are formed during XLPE oxidation. Thermal pre-oxidation of XLPE, to the levels measured in typical field-aged cables, has little or no effect on the initiation and growth of vented water trees. Very high levels of pre-oxidation las determined by the carbonyl content), at least 80x the average oxidation level measured in typical field-aged cable, retard the growth of vented water trees. However, these high levels of oxidation negatively affect the dielectric properties of the insulation.
引用
收藏
页码:558 / 570
页数:13
相关论文
共 50 条
  • [1] Water treeing and molecular properties of the polymer
    Patsch, R
    Jung, JC
    Motori, A
    Montanari, GC
    [J]. IEEE 1996 ANNUAL REPORT - CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA, VOLS I & II, 1996, : 795 - 798
  • [2] A STUDY OF OXIDATION AND WATER TREEING IN POLYETHYLENE
    MUTO, H
    BAMJI, SS
    BULINSKI, AT
    DENSLEY, RJ
    [J]. IEEE 1989 ANNUAL REPORT: CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA, 1989, : 247 - 252
  • [3] INFLUENCE OF POLYMER MORPHOLOGY ON WATER TREEING
    RAHARIMALALA, V
    POGGI, Y
    FILIPPINI, JC
    [J]. IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 1994, 1 (06) : 1094 - 1103
  • [4] OXIDATION OF POLYTHENE AS A POSSIBLE PRELUDE TO WATER TREEING
    RYE, J
    BROWN, P
    EELES, WT
    [J]. JOURNAL OF PHYSICS D-APPLIED PHYSICS, 1975, 8 (01) : L16 - L17
  • [5] COMPARISON OF WATER TREEING IN AN AMORPHOUS AND IN A SEMICRYSTALLINE POLYMER
    POGGI, Y
    RAHARIMALALA, V
    FILIPPINI, JC
    [J]. POLYMER, 1991, 32 (16) : 2980 - 2983
  • [6] Treeing and water treeing resistance of ethylene styrene copolymers
    Akiyama, K
    Ohki, Y
    Umeshima, Y
    Ikeda, M
    [J]. JOINT CONFERENCE OF 96' AICDEI / 4T-JCCEID, 1996, : 61 - 64
  • [7] Electrical Treeing in Polymer Nanocomposites
    Alapati, Sridhar
    Thomas, M. Joy
    [J]. INTERNATIONAL JOURNAL OF EMERGING ELECTRIC POWER SYSTEMS, 2009, 10 (02):
  • [8] A water treeing model
    Crine, JP
    Jow, J
    [J]. IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2005, 12 (04) : 801 - 808
  • [9] Thermodynamics of Water Treeing
    Wang, Zuoqian
    Evans, James W.
    Wright, Paul K.
    [J]. IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2011, 18 (03) : 840 - 846
  • [10] THERMODYNAMICS OF WATER TREEING