Analysis of Properties Characteristic for Acoustic Emission Signals Recorded On-Line in Power Oil Transformers

被引:12
|
作者
Witos, F. [1 ]
Olszewska, A. [1 ]
Szerszen, G. [1 ]
机构
[1] Silesian Tech Univ, Dept Optoelect, PL-44100 Gliwice, Poland
关键词
PARTIAL DISCHARGES; SENSOR; PD;
D O I
10.12693/APhysPolA.120.759
中图分类号
O4 [物理学];
学科分类号
0702 ;
摘要
Investigation results of properties characteristic for acoustic emission signals recorded in two selected power oil transformers are presented. Signals were put to the filtration, whereas components coming from partial discharges have been left. The calculations concerned: phase time characteristics, averaging phase characteristics, averaging short time Fourier transform spectrograms, amplitude distributions of signals, values of acoustic emission descriptor with acronym ADC. On the ground of calculated basic characteristics and maps of ADC descriptor three areas have been selected on lateral walls of transformer tanks. Acoustic emission signals recorded in these areas were analyzed from the point of view how is influence of propagation path on these properties.
引用
收藏
页码:759 / 762
页数:4
相关论文
共 50 条
  • [1] Analysis of Properties of Chosen Acoustic Emission Descriptors Describing Acoustic Signals Measured by Means of Acoustic Emission Method within Oil Transformers
    Witos, F.
    Olszewska, A.
    [J]. ACTA PHYSICA POLONICA A, 2010, 118 (06) : 1267 - 1271
  • [2] Location of Partial Discharge Sources and Analysis of Signals in Chosen Power Oil Transformers by Means of Acoustic Emission Method
    Olszewska, A.
    Witos, F.
    [J]. ACTA PHYSICA POLONICA A, 2012, 122 (05) : 921 - 926
  • [3] The system useful for analysis of acoustic emission signals generated by partial discharges within power oil transformers insulation
    Witos, Franciszek
    Olszewska, Aneta
    [J]. PRZEGLAD ELEKTROTECHNICZNY, 2012, 88 (11B): : 154 - 157
  • [4] Thermographic analysis of power oil transformer surface hot spot areas combined with analysis of acoustic signals recorded on line
    Lisowka-Lis, Agnieszka
    Witos, Franciszek
    Szerszen, Grzegorz
    [J]. 14TH CONFERENCE ON INTEGRATED OPTICS: SENSORS, SENSING STRUCTURES, AND METHODS, 2019, 11204
  • [5] Location and Identification of Acoustic Signals Recorded in Power Oil Transformers within the Band of 20-180 kHz
    Olszewska, A.
    Witos, F.
    [J]. ACTA PHYSICA POLONICA A, 2011, 120 (04) : 709 - 712
  • [6] Analysis of on-line power cable signals
    Hepburn, Donald M.
    Zhou, Chengke
    Song, Xiaodi
    Zhang, Guobin
    Michel, Matthieu
    [J]. PROCEEDINGS OF 2008 INTERNATIONAL CONFERENCE ON CONDITION MONITORING AND DIAGNOSIS, 2007, : 1175 - +
  • [7] On-line diagnostics of power transformers
    Mentlik, V.
    Prosr, P.
    Pihera, J.
    Polansky, R.
    Trnka, P.
    [J]. CONFERENCE RECORD OF THE 2006 IEEE INTERNATIONAL SYMPOSIUM ON ELECTRICAL INSULATION, 2006, : 546 - +
  • [8] Acoustic emission analysis for on-line wear control
    Paller, G
    Schwab, M
    [J]. MATERIALWISSENSCHAFT UND WERKSTOFFTECHNIK, 1995, 26 (10) : 550 - 552
  • [9] On-Line Partial Discharge Monitoring System for Power Transformers Based on the Simultaneous Detection of High Frequency, Ultra-High Frequency, and Acoustic Emission Signals
    Sikorski, Wojciech
    Walczak, Krzysztof
    Gil, Wieslaw
    Szymczak, Cyprian
    [J]. ENERGIES, 2020, 13 (12)
  • [10] Application of Acoustic Emission and Thermal Imaging to Test Oil Power Transformers
    Witos, Franciszek
    Olszewska, Aneta
    Opilski, Zbigniew
    Lisowska-Lis, Agnieszka
    Szerszen, Grzegorz
    [J]. ENERGIES, 2020, 13 (22)