Novel Application of Magnetoresistive Sensors for High-Voltage Transmission-Line Monitoring

被引:45
|
作者
Sun, X. [1 ]
Lui, K. S. [1 ]
Wong, K. K. Y. [1 ]
Lee, W. K. [1 ]
Hou, Y. [1 ]
Huang, Q. [2 ]
Pong, P. W. T. [1 ]
机构
[1] Univ Hong Kong, Dept Elect & Elect Engn, Hong Kong, Hong Kong, Peoples R China
[2] Univ Elect Sci & Technol China, Sch Automat Engn, Chengdu 61173, Peoples R China
关键词
Galloping; magnetoresistive (MR) sensors; overhead transmission lines; sagging; smart grid; CONDUCTOR SAG;
D O I
10.1109/TMAG.2011.2158085
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
High-voltage transmission lines are responsible for transmission of electric power. Their sag and electric current are important parameters for transmission-line monitoring. In this paper, a simple and promising method based on magnetoresistive sensors is proposed for transmission-line monitoring. This is a noncontact method and its installation is simple without the need for power cut. The method involves measuring emanated magnetic field from a line conductor at the ground level and, then, calculating the source position and current inversely. A proof-of-concept laboratory setup was constructed and a series of experiments were carried out for demonstration. This method can handle complicated transmission-line configuration by integrating the stochastic optimization approach into the inverse electromagnetic calculation. It was tested with the computational simulation of a 500 kV transmission-line configuration. The result shows the feasibility of using this transmission-line monitoring method in reality.
引用
收藏
页码:2608 / 2611
页数:4
相关论文
共 50 条