Energy, exergy and exergoeconomic analysis of an ultra low-grade heat-driven ammonia-water combined absorption power-cooling cycle for district space cooling, sub-zero refrigeration, power and LNG regasification

被引:55
|
作者
Ayou, Dereje S. [1 ]
Eveloy, Valerie [1 ]
机构
[1] Khalifa Univ, Dept Mech Engn, POB 127788, Abu Dhabi, U Arab Emirates
关键词
Combined absorption power-cooling cycle; District cooling; Liquefied natural gas; Exergoeconomic; Low-grade heat; Waste cold; LIQUEFIED NATURAL-GAS; COLD ENERGY; WASTE-HEAT; THERMOECONOMIC ANALYSIS; THERMODYNAMIC ANALYSIS; PERFORMANCE ANALYSIS; SMALL-CAPACITY; RANKINE-CYCLE; SYSTEM DRIVEN; KALINA CYCLE;
D O I
10.1016/j.enconman.2020.112790
中图分类号
O414.1 [热力学];
学科分类号
摘要
An ultra low-grade waste heat (<= 100 degrees C) driven ammonia-water combined absorption power-cooling (APC) cycle-based multi-generation system with liquefied natural gas (LNG) cold exergy recovery is thermodynamically and exergoeconomically investigated for sustainable district cooling (DC) at two different temperature levels, and electricity generation in coastal hot climate regions serviced by LNG regasification terminals. At 70 degrees C heat source temperature, the system yields a specific net equivalent power output of 51.4 kWh/ton(LNG) at a cooling-to-power ratio of 7.3, and effective first-law and effective exergy efficiencies of 39% and 36%, respectively. Per million ton per annum (MTPA) LNG regasification capacity, the system would deliver 9.4 MW of space cooling, 6.5 MW of sub-zero refrigeration, and 2.2 MW of electricity for the district, while saving 8.4 ktons of natural gas and 19.3 kt of CO2-equivalent emissions per year, compared with conventional cooling, power and regasified LNG provision systems. The LNG refrigeration heat exchanger and APC absorber-evaporator are the most important components from exergoeconomic viewpoints. In addition to enhancing overall cooling and power generation capacity, the use of LNG as a cold source/sink reduces the minimum APC driving heat source temperature and rectification requirements, relative to an ambient water-cooled absorber sink. Additional benefits include the avoided use of conventional refrigerants, and reduced impact of LNG regasification on marine ecosystems.
引用
收藏
页数:25
相关论文
共 8 条
  • [1] A novel cooling and power cycle based on the absorption power cycle and booster-assisted ejector refrigeration cycle driven by a low-grade heat source: Energy, exergy and exergoeconomic analysis
    Wang, Yazi
    Chen, Tian
    Liang, Yingbo
    Sun, Huaibo
    Zhu, Yiping
    ENERGY CONVERSION AND MANAGEMENT, 2020, 204
  • [2] Thermodynamic Analysis of a New Combined Cooling and Power System Coupled by the Kalina Cycle and Ammonia-Water Absorption Refrigeration Cycle
    Wang, Haojin
    Wang, Jianyong
    Liu, Zhuan
    Chen, Haifeng
    Liu, Xiaoqin
    SUSTAINABILITY, 2022, 14 (20)
  • [3] A new combined cooling and power system based on ammonia-water absorption refrigeration cycle: Thermodynamic comparison and analysis
    Wang, Jianyong
    Liu, Zhuan
    Wang, Haojin
    Liu, Xiaoqin
    ENERGY CONVERSION AND MANAGEMENT, 2022, 270
  • [4] Exergy analysis of a combined power cycle using low-grade heat source and LNG cold energy
    Kim, Kyung Chun
    Ha, Jong Man
    Kim, Kyoung Hoon
    INTERNATIONAL JOURNAL OF EXERGY, 2015, 17 (03) : 374 - 400
  • [5] Energetic, exergetic and economic analysis and multi-objective optimization of two novel ammonia-water absorption combined power and cooling cycles driven by low-grade heat sources
    Feng, Chunyu
    Yu, Zeting
    Liang, Wenxing
    Wang, Daohang
    ENERGY CONVERSION AND MANAGEMENT, 2021, 248
  • [6] Thermodynamic analysis of a Kalina-based combined cooling and power cycle driven by low-grade heat source
    Cao, Liyan
    Wang, Jiangfeng
    Wang, Hongyang
    Zhao, Pan
    Dai, Yiping
    APPLIED THERMAL ENGINEERING, 2017, 111 : 8 - 19
  • [7] Performance enhancement of combined cycle power plant using inlet air cooling by exhaust heat operated ammonia-water absorption refrigeration system
    Singh, Omendra Kumar
    APPLIED ENERGY, 2016, 180 : 867 - 879
  • [8] Parameter analysis of an ammonia-water power cycle with a gravity assisted thermal driven "pump" for low-grade heat recovery
    Wang, Z. X.
    Du, S.
    Wang, L. W.
    Chen, X.
    RENEWABLE ENERGY, 2020, 146 : 651 - 661