Impulse Voltage Distribution and Frequency Response of Intershield Windings

被引:17
|
作者
Bagheri, Mehdi [1 ]
Phung, B. T. [2 ]
Naderi, Mohammad Salay [3 ]
机构
[1] Nazarbayev Univ, Dept Elect Engn, Astana, Kazakhstan
[2] Univ New South Wales, Sch Elect Engn & Telecommun, Sydney, NSW, Australia
[3] Niroo Res Inst, Tehran, Iran
关键词
intershield winding; impulse voltage distribution; frequency response; DIAGNOSTICS; DEFORMATION;
D O I
10.1109/MEI.2016.7552374
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Impulse voltage distributions in continuous disk windings are nonlinear, due to the small series capacitance of the winding. Consequently, transformer manufacturers often design large power transformers with interleaved windings to increase series capacitance, but in doing so reduce the value of the initial impulse voltage distribution coefficient α given by α = √(Cg/Cs), (1) where Cg is the shunt capacitance and Cs is the series capacitance of the winding. Sometimes fully interleaved windings are employed because they are more reliable, ensuring that the transformer will operate properly under lightning strike. However, fully interleaved windings require longer assembly times, and manual welding is necessary. Manufacturers have therefore been using series combinations of continuous and interleaved windings, known as multiple-α type windings [1]. However, this approach also has disadvantages, e.g., the design and analysis of performance under normal and abnormal transient conditions are complicated, and the impedances of continuous disks differ from those of interleaved disks [2], causing reflection of surge traveling waves at connection points. Transformer designers may therefore have to adjust inter-disk distances and repeat transient simulation studies several times, to find an optimum arrangement. © 2006 IEEE.
引用
收藏
页码:32 / 40
页数:9
相关论文
共 50 条