摘要
The problem of pulse voltage measurements in the nanoseconds range has become of great importance with ongoing problems related to the construction of pulse fusion generators as well as with simulations of electromagnetic pulses related to the atmospheric nuclear explosion. Ultrafast pulses in the nanoseconds range can be measured by the capacitive voltage divider. The problem that arises with ultrafast voltage occurrence is inductivity. Under conditions of the nanoseconds pulse increase rate, conductors of about few centimeters should be regarded as inductivity. Therefore, capacitive divider can be treated as an equivalent RLC circuit. The ohmic resistance R in that equivalent circuit originates from the characteristic impedance (either 50 Omega or 75 Omega) and, depending on its design, it can introduce an additional parasite inductivity. The aim of this paper is to consider and analyze the constructive solutions of capacitive voltage divider for measuring ultrafast voltage occurrence. Three types of capacitive divider will be constructed for that purpose. The high-voltage capacitor of each divider will be gas capacitor (in order to avoid both electrostatic and electrodynamic influence on measurement accuracy). The variations between divider types will be made for low-voltage capacitor. The designed low-voltage capacitors will be: 1 - in the shape of 10 mica capacitors connected in a parallel with a discrete ending resistor of 50 Omega; 2 - in the form of gas trimmer capacitor with a discrete ending resistor of 50 Omega, and 3 - the continual mica capacitor with waveguide resistor of 50 Omega (L=0). Ultrafast pulse response will be measured with dividers constructed in such manner, and will be compared with the corresponding response obtained from the numerical simulations.
引用
收藏
页数:5
相关论文
共 50 条
  • [1] Design of capacitive voltage divider for measuring ultrafast voltages
    Kovacevic, Uros D.
    Stankovic, Koviljka D.
    Kartalovic, Nenad M.
    Loncar, Boris B.
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2018, 99 : 426 - 433
  • [2] HIGH-VOLTAGE PULSE MEASUREMENT WITH A PRECISION CAPACITIVE VOLTAGE DIVIDER
    BRADY, MM
    DEDRICK, KG
    REVIEW OF SCIENTIFIC INSTRUMENTS, 1962, 33 (12): : 1421 - &
  • [3] A Square Patch Capacitive Voltage Divider for Measuring High-Voltage Ultrawideband Pulses in a Coaxial Pulse Forming Line
    Ryu, Jiheon
    Kwon, Hae-Ok
    Park, Seung Hyuk
    Yim, Dong Woo
    IEEE TRANSACTIONS ON INSTRUMENTATION AND MEASUREMENT, 2016, 65 (03) : 680 - 684
  • [4] Development of a Broadband Capacitive Voltage Divider for Measuring Nanosecond Impulse
    Zhang, Lu
    Sun, Lei
    Han, Yan H.
    Wang, Sen
    Guo, Can
    Wang, Chen X.
    2018 2ND IEEE CONFERENCE ON ENERGY INTERNET AND ENERGY SYSTEM INTEGRATION (EI2), 2018,
  • [5] Characterization of a capacitive voltage divider✩
    Zamora, J. A.
    Aguilera, E.
    Soto, E.
    ELECTRIC POWER SYSTEMS RESEARCH, 2023, 223
  • [6] PRECISION CAPACITIVE VOLTAGE DIVIDER FOR IMPULSE VOLTAGE MEASUREMENTS
    SCHWAB, AJ
    PAGEL, JHW
    IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1972, PA91 (06): : 2376 - &
  • [7] Design and performance of capacitive divider for high-voltage pulse measurement
    Institute of Fluid Physics, China Academy of Engineering Physics, Mianyang 621900, China
    Gaodianya Jishu, 2007, 12 (39-43):
  • [8] Measuring LEMP electric field in the GTEM cell with capacitive voltage divider
    Zhou, X
    Fan, LS
    Zhang, XJ
    Wei, GH
    ICEMI 2005: Conference Proceedings of the Seventh International Conference on Electronic Measurement & Instruments, Vol 2, 2005, : 556 - 559
  • [9] Voltage Measuring System Including a Series Damped Capacitive Divider.
    Macura, Pavel
    1600, (72):
  • [10] SIMPLE NANOSECOND CAPACITIVE VOLTAGE DIVIDER
    WONG, CS
    REVIEW OF SCIENTIFIC INSTRUMENTS, 1985, 56 (05): : 767 - 769