Performance evaluation of portable water mist fire extinguishing system

被引:0
|
作者
Chang, Wen-Yao [1 ]
Fu, Ping-Kun [1 ]
Chen, Chiun-Hsun [1 ]
Shu, Yi-Liang [1 ]
机构
[1] Natl Chiao Tung Univ, Dept Engn Mech, Hsinchu, Taiwan
关键词
water mist; fire protection; portable;
D O I
暂无
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
The phase out of Halon production under the Montreal Protocol has led to intense research to find a replacement agent for fire protection. Through extensive research and testing, water mist systems have gained worldwide acceptance as an effective solution in many applications. In this article, we will introduce a portable water mist system, with longer operating time than traditional fire extinguisher and less water damage than hydrant. The operation time of traditional fire extinguisher is always ten to thirty seconds, too short for fire control and dangerous to operator. If the fire is getting larger, hydrant will be used, and always results in huge water damage, especially in high-tech facilities. So, it's necessary to find a system with longer operation time to control fire and less water used for water damage problem, especially for high-tech facilities. This portable extinguish system is designed to operate at least ten minutes, long enough for fire control, and this system uses high pressure water mist nozzle, less water used, the water damage will not be a problem. This Portable system uses a petrol engine or an electric engine to pump water for high pressure operation. The petrol one could be used out of buildings, and electric one could be used in buildings without air pollution problem, which is important to employees and high-tech manufacturing instruments. There is a mist nozzle with one hose connects to the system and this soft pipe could be 50 meters long, could easily move to the fire origin and releases mist to fire. Series of fire tests were taken for evaluating the performance of this portable system. In fire tests, air temperatures, images, combustion products and extinguish time are recorded simultaneous. The fire tests include wood stabs fire, sofa fire, petrol pan fire, motorcycle fire and car fire. In these fire tests, the portable water mist system performs well and meets what we need, longer operation time and less water damage. This portable system also has capability to cool the environment temperature and wash down combustion products and soot, it's safer to operator.
引用
收藏
页码:896 / 900
页数:5
相关论文
共 50 条
  • [1] Evaluating the performance of a portable water-mist fire extinguishing system with additives
    Chang, Wen-Yao
    Fu, Ping-Kun
    Chen, Chiun-Hsun
    Shu, Yi-Liang
    FIRE AND MATERIALS, 2008, 32 (07) : 383 - 397
  • [2] Study of fire-extinguishing performance of portable water-mist fire extinguisher in historical buildings
    Zhou Xiaomeng
    Zhou Biao
    Jin Xiang
    JOURNAL OF CULTURAL HERITAGE, 2010, 11 (04) : 392 - 397
  • [3] X-Mist: a new Korean water-mist fire extinguishing system
    不详
    NAVAL ARCHITECT, 2003, : 13 - 13
  • [4] Study on the effect of mist flux on water mist fire extinguishing
    Liu, Yang
    Fu, Zhixi
    Zheng, Guanghui
    Chen, Peng
    FIRE SAFETY JOURNAL, 2022, 130
  • [5] Study on fire extinguishing performance of ultrafine water mist in a cup burner
    LIANG TianShui 1
    2 Department of Building and Construction
    Science China Technological Sciences, 2012, (07) : 1982 - 1987
  • [6] Study on fire extinguishing performance of ultrafine water mist in a cup burner
    Liang TianShui
    Liao GuangXuan
    Lu SiuMing
    Wang XiShi
    SCIENCE CHINA-TECHNOLOGICAL SCIENCES, 2012, 55 (07) : 1982 - 1987
  • [7] Study on fire extinguishing performance of ultrafine water mist in a cup burner
    TianShui Liang
    GuangXuan Liao
    SiuMing Lu
    XiShi Wang
    Science China Technological Sciences, 2012, 55 : 1982 - 1987
  • [8] Study on fire extinguishing performance of ultrafine water mist in a cup burner
    LIANG TianShui LIAO GuangXuan LU SiuMing WANG XiShi State Key Laboratory of Fire ScienceUniversity of Science and Technology of ChinaHefei China Department of Building and ConstructionCity University of Hong KongKowloonHong KongSAR China
    Science China(Technological Sciences), 2012, 55 (07) : 1982 - 1987
  • [9] Numerical Analysis of the Characteristics of Fire-Extinguishing Performance of Water Mist Nozzle
    Kim, Hak Min
    Yeom, Jeong Kuk
    TRANSACTIONS OF THE KOREAN SOCIETY OF MECHANICAL ENGINEERS B, 2020, 44 (03) : 177 - 183
  • [10] Numerical Investigations on Water Mist Fire Extinguishing Performance: Physical and Sensitivity Analysis
    Robinet, Antonin
    Chetehouna, Khaled
    Cable, Axel
    Florentin, Eric
    Oger, Antoine
    FIRE-SWITZERLAND, 2022, 5 (06):