Condition Evaluation of Stator Winding Insulation of Vintage High Voltage Turbine Generator

被引:0
|
作者
Kumar, P. G. S. [1 ]
Reddy, K. Malla [1 ]
机构
[1] MRTG Power Diagnost Tests Pvt Ltd, Hyderabad, Andhra Pradesh, India
关键词
Condition assessment; dielectric insulation; partial discharges; tan delta; turbine generator;
D O I
暂无
中图分类号
TP301 [理论、方法];
学科分类号
081202 ;
摘要
Degradation of dielectric insulation system happens in turbine generators in service. Thermal, electrical, ambient and mechanical forces attack the potential barrier of power windings and reduce the electrical strength. Sudden failure and forced outage can be averted by condition assessment of generator insulation. This paper presents state-of-art diagnosis tools to evaluate the dielectric insulation properties of stator winding of generators. Degradation mechanism in insulation is dealt with physical model and electrical equivalent circuit. Test results of 25 MW, 11 KV TG of four decades old are analyzed to evaluate the insulation properties. Correlation is made between tan delta, partial discharge, corona probe data with visual examination. Corrective actions are listed to improve the insulation performance. Utility is advised to monitor the machine parameters on load and repeat dielectric tests to avoid forced outages due to insulation failure. It is suggested to plan rewinding with state of art of insulation technology to enhance the life of machine.
引用
收藏
页数:6
相关论文
共 50 条
  • [1] The evaluation of the condition of high-voltage system with using accelerated voltage time tests and design of main wall insulation thickness for stator bar of generator stator winding
    Bezdekovsky, Jiri
    Krupauer, Petr
    [J]. PROCEEDINGS OF THE INTERNATIONAL CONFERENCE 2016 CONFERENCE ON DIAGNOSTICS IN ELECTRICAL ENGINEERING (DIAGNOSTIKA), 2016, : 11 - 14
  • [2] Condition Monitoring of Turbine Generator Using Stator Winding Temperature
    Qian, Fang
    Feng, Yutong
    Ling, Jun
    [J]. 2018 IEEE INTERNATIONAL CONFERENCE ON PROGNOSTICS AND HEALTH MANAGEMENT (ICPHM), 2018,
  • [3] Assessment of insulation condition in gas turbine generator stator windings
    Kim, Hee-Dong
    Yang, Gyu-Hyun
    Ju, Young-Ho
    [J]. Transactions of the Korean Institute of Electrical Engineers, 2010, 59 (08): : 1423 - 1428
  • [4] Diagnosis of stator winding insulation of large generator
    Xie, HK
    Bo, Y
    Hao, YP
    [J]. PROCEEDINGS OF THE 7TH INTERNATIONAL CONFERENCE ON PROPERTIES AND APPLICATIONS OF DIELECTRIC MATERIALS, VOLS 1-3, 2003, : 274 - 277
  • [5] Condition Assessment Program on Aged High Voltage Insulation of In-Service Turbine Generator
    Kumar, P. G. S.
    Kumar, K. Kalyan
    [J]. 2015 INTERNATIONAL CONFERENCE ON CONTROL COMMUNICATION & COMPUTING INDIA (ICCC), 2015, : 265 - 270
  • [6] Turbo generator stator winding condition assessment
    Arshad, M
    Khaliq, A
    Islam, SM
    [J]. 2004 International Conference on Power System Technology - POWERCON, Vols 1 and 2, 2004, : 1399 - 1403
  • [7] Assessing the condition of hydrogenerator stator winding insulation using the ramped high direct-voltage test method
    Rux, L
    McDermid, W
    [J]. IEEE ELECTRICAL INSULATION MAGAZINE, 2001, 17 (06) : 27 - 33
  • [8] Analysis on aging condition of stator winding insulation of generator based on the moment characteristics of partial discharge
    Zhang, Xiao-Hong
    Zhang, Liang
    Yue, Bo
    Xie, Heng-Kun
    [J]. Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering, 2002, 22 (05): : 94 - 98
  • [9] Turbine Generator Rotor and Stator Winding Hipot Testing
    Ilie, Relu
    Stone, G. C.
    [J]. IEEE ELECTRICAL INSULATION MAGAZINE, 2012, 28 (02) : 29 - 37
  • [10] Electrostatic field analysis of high voltage generator stator insulation systems
    Emery, FT
    Pavlik, D
    [J]. 2000 ANNUAL REPORT CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA, VOLS. I & II, 2000, : 510 - 513