Structural changes in EPDM subjected to ageing in high voltage transmission lines

被引:14
|
作者
Sorichetti, P. A.
Matteo, C. L.
Lambri, O. A.
Manguzzi, G. C.
Salvatierra, L. M.
Herrero, O.
机构
[1] Fac Catolica Quim Ingn, Rosario, Argentina
[2] Univ Buenos Aires, Fac Ingn, Dept Fis, RA-1053 Buenos Aires, DF, Argentina
[3] Consejo Nacl Invest Cient & Tecn, RA-1033 Buenos Aires, DF, Argentina
[4] Univ Nacl Rosario, Fac Ciencias Exactas Ingn & Agrimensura, Escuela Ingn Elect, RA-2000 Rosario, Argentina
[5] Consejo Nacl Invest Cient & Tecn, Inst Fis, Rosario, Argentina
关键词
insulation material; ethylene-propylene-diene monomer; insulator testing; high voltage ageing; crystallinity;
D O I
10.1109/TDEI.2007.4339477
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This work presents a study of the structural changes in aged EPDM (ethylene-propylene-diene monomer) from outdoor high voltage transmission lines. Samples were taken from failed and non-failed insulators after up to ten years in service on a 33 kV line. Infrared absorption, hydrophobicity index, dynamical mechanical analysis (DMA) and dielectric relaxation (DR) were employed as experimental techniques. The same experimental techniques were also applied to new samples of EPDM that were subjected to high electric fields (up to 14 kV/mm) for several hours. Results from DMA and DR techniques are in good agreement and, together with previous results from neutron irradiation techniques, suggest that the experimental data obtained from outdoor-aged and laboratory tested samples may be explained by a decrease in the degree of crystallinity due to the interaction between electrical and mechanical effects in the dielectric The proposed model is based on the disentanglement of the crystallites by forces originated in the interaction of the electric field with the polar groups located in the amorphous phase of the polymer matrix. An alternative explanation, based on a relaxation process appearing at the interfaces between the filler (ATH) and the polymer matrix conflicts with several experimental results presented in this work.
引用
收藏
页码:1170 / 1182
页数:13
相关论文
共 50 条
  • [1] Calculation of electrostatically induced field in humans subjected to high voltage transmission lines
    Talaat, M.
    ELECTRIC POWER SYSTEMS RESEARCH, 2014, 108 : 124 - 133
  • [2] Corona loss analysis of high voltage DC transmission lines in close proximity of high voltage AC transmission lines
    Beijing Key Laboratory on High Voltage and EMC , Changping District, Beijing 102206, China
    Zhongguo Dianji Gongcheng Xuebao, 31 (211-218):
  • [3] TRANSIENTS IN PNEUMATIC TRANSMISSION LINES SUBJECTED TO LARGE PRESSURE CHANGES
    FUNK, JE
    ROBE, TR
    INTERNATIONAL JOURNAL OF MECHANICAL SCIENCES, 1970, 12 (03) : 245 - &
  • [4] TRANSIENTS IN PNEUMATIC TRANSMISSION LINES SUBJECTED TO LARGE PRESSURE CHANGES
    FUNK, JE
    ROBE, TR
    MECHANICAL ENGINEERING, 1969, 91 (10) : 79 - &
  • [5] NDT OF HIGH VOLTAGE TRANSMISSION LINES.
    Carter, R.A.
    Quick, D.G.
    Non-Destructive Testing - Australia, 1979, 16 (1-2): : 23 - 25
  • [6] Locating defects in high voltage transmission lines
    Jaensch, G
    Hoffmann, H
    Markees, A
    ESMO '98 PROCEEDINGS: ESMO '98 - 1998 IEEE 8TH INTERNATIONAL CONFERENCE ON TRANSMISSION & DISTRIBUTION CONSTRUCTION, OPERATION & LIVE-LINE MAINTENANCE PROCEEDINGS, 1996, : 179 - 186
  • [7] Mechanistic insights into the ageing of EPDM micro/hybrid composites for high voltage insulation application
    Rizwan, Mohammed
    Chandan, Mohammed Rehaan
    POLYMER DEGRADATION AND STABILITY, 2022, 204
  • [8] Structural optimization of a new-style insulator used in high-voltage transmission lines
    Peng, Zongren
    Liu, Peng
    Yu, Peng
    ICPASM 2005: PROCEEDINGS OF THE 8TH INTERNATIONAL CONFERENCE ON PROPERTIES AND APPLICATIONS OF DIELECTRIC MATERIALS, VOLS 1 AND 2, 2006, : 832 - +
  • [9] Magnetic coupling between high voltage transmission lines and communications lines
    Amer, GM
    UPEC 2004: 39th International Universitities Power Engineering Conference, Vols 1-3, Conference Proceedings, 2005, : 75 - 78
  • [10] Modeling of Corona at Ultra High Voltage Transmission Lines
    Sui, Dongpeng
    Kang, Jiyang
    Li, Xuebin
    Huang, Fucun
    Bin, Luo
    PROCEEDINGS OF THE 3RD INTERNATIONAL CONFERENCE ON MECHANICAL ENGINEERING AND INTELLIGENT SYSTEMS (ICMEIS 2015), 2015, 26 : 700 - 706