Effect of Protecting with Conduits on Insulation Failure of YJV Cable

被引:0
|
作者
Shu Zhongjun [1 ]
Sun Qinghui [1 ]
Chen Nan [1 ]
Yang Shousheng [1 ]
机构
[1] Chinese Peoples Armed Police Forces Acad, Dept Fire Engn, Langfang 065000, Hebei, Peoples R China
关键词
YJV cable; cable conduit; insulation failure; failure temperature; failure time;
D O I
暂无
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
The insulation failure conditions of YJV cables in different kinds of protecting modes were studied by means of the infrared thermal radiation furnace which could simulate different heat fluxes in fire. The test data showed that YJV cable insulation failure temperature was little influenced by protecting modes and radiation heat, which approximately remained at 523.4(1 +/- 7.8%) degrees C. The cable insulation failure time decreased with the increase of exposure heat flux and increased when cable was protected by conduit evidently. Moreover, the protecting effect of metal conduit was slightly better than flame-retardant PVC conduit.
引用
收藏
页码:1838 / 1844
页数:7
相关论文
共 50 条
  • [1] Insulation Failure Mechanism of Cable in Fire Environment
    Li, Qiang
    Zhang, Jiaqing
    Li, Jinmei
    Yang, Yichen
    Fan, Minghao
    ADVANCED FUNCTIONAL MATERIALS (CMC 2017), 2018, : 909 - 917
  • [2] The protective effect of a fire-retardant coating on the insulation failure of PVC cable
    Wang, Ji
    Shu, Zhong-Jun
    Chen, Zhen
    ENGINEERING FAILURE ANALYSIS, 2013, 34 : 1 - 9
  • [3] Effect of thermal on cable insulation breakdown
    Zhang, Runzu
    Feng, Anhui
    Zhang, Yongbo
    Liu, Ye
    Liu, Pengfei
    Zhou, Zhongzu
    Yang, Weiqing
    Yang, Jiancheng
    Shi, Ya Gang
    2022 9TH INTERNATIONAL FORUM ON ELECTRICAL ENGINEERING AND AUTOMATION, IFEEA, 2022, : 821 - 824
  • [4] Insulation Failure Prediction Model of Power Cable in Fire
    Li, Jin-mei
    Zhang, Jia-qing
    Li, Qiang
    Ren, Shi-jing
    2018 INTERNATIONAL CONFERENCE ON ELECTRICAL ENGINEERING AND GREEN ENERGY (CEEGE 2018), 2018, 72
  • [5] THE MEASUREMENT AND TEMPERATURE PROFILE OF CABLE INSULATION FAILURE DUE TO LOOSE CONNECTION AT THE CABLE TERMINATION
    Abu Zarim, Z. A.
    Ghani, A. B. Abd.
    Tiong, S. K.
    ISEIM 2008: PROCEEDINGS OF 2008 INTERNATIONAL SYMPOSIUM ON ELECTRICAL INSULATING, 2008, : 170 - 170
  • [6] Effect of water on aging of XLPE cable insulation
    Nikolajevic, SV
    Drca, R
    ELECTRIC POWER SYSTEMS RESEARCH, 2001, 60 (01) : 9 - 15
  • [7] The study of inhomogeneities effect on the insulation of a power cable
    Popa, Monica
    Pasca, Sorin
    2019 15TH INTERNATIONAL CONFERENCE ON ENGINEERING OF MODERN ELECTRIC SYSTEMS (EMES), 2019, : 189 - 192
  • [8] Mathematical Modeling of Heat Effect on Cable Insulation
    Eroglu, E.
    Guney, I.
    Gunes, I.
    Sener, E.
    ACTA PHYSICA POLONICA A, 2017, 131 (03) : 539 - 541
  • [9] A Brief Review of Thermal Mechanism of Failure in Power Cable Insulation
    Reddy C.C.
    Journal of Engineering Science and Technology Review, 2022, 14 (07) : 49 - 62
  • [10] Evolution of grounding failure-insulation failure of 10 kV cable joints: Prerequisites of an explosion in enclosed cable trench
    Zhao, Yifeng
    Liu, Gang
    Guo, Yaodong
    Huang, Chenglong
    He, Zhaoming
    Hu, Ran
    IET GENERATION TRANSMISSION & DISTRIBUTION, 2023, 17 (16) : 3751 - 3762