Fluid to liquid membrane energy exchanger for simultaneous liquid desiccant regeneration and desalination applications-Theoretical and experimental analyses

被引:16
|
作者
Naik, B. Kiran [1 ,4 ]
Singh, Bharat [2 ,4 ]
Dutta, Neelam [3 ,4 ]
Subbiah, Senthilmurugan [2 ,3 ,4 ]
Muthukumar, P. [1 ,3 ,4 ]
机构
[1] Indian Inst Technol Guwahati, Dept Mech Engn, Gauhati 781039, Assam, India
[2] Indian Inst Technol Guwahati, Dept Chem Engn, Gauhati 781039, Assam, India
[3] Indian Inst Technol Guwahati, Ctr Energy, Gauhati 781039, Assam, India
[4] Indian Inst Technol Guwahati, Gauhati 781039, Assam, India
关键词
Liquid desiccant regenerator; Energy exchanger; Thermal model; PVDF membrane; Vapour absorption rate; AIR DEHUMIDIFICATION; PERFORMANCE; SYSTEM; MODEL;
D O I
10.1016/j.enconman.2019.112291
中图分类号
O414.1 [热力学];
学科分类号
摘要
In this paper, a thermal model developed for assessing the performance of the fluid to liquid membrane energy exchanger based liquid desiccant regenerator is presented. The model was validated with the experimental data and found accurate. Using the experimental inlet conditions reported in the literature for the structured packing chamber, the performance of the fluid to liquid membrane energy exchanger based liquid desiccant regenerator was theoretically predicted choosing water and air as working fluids and Lithium Chloride as a liquid desiccant. Further, studied the influence of inlet parameters such as working fluid and desiccant inlet temperature's, hot liquid desiccant to cold working fluid ratio and desiccant concentration on vapour absorption rate. From this analysis, it is observed that membrane based liquid desiccant regenerator using water as a working fluid is best suitable for converting the weak desiccant into strong desiccant and for generating the pure water simultaneously (co-generation process). An experimental investigation was carried out for assessing the energy exchange process across the membrane based liquid desiccant regenerator using water as a working fluid. From the experimental analysis, it was found that desiccant temperature has a significant impact on the energy exchange process. The pressure drop across the membrane based liquid desiccant regenerator was also measured at different desiccant flow rates and concentration.
引用
收藏
页数:16
相关论文
共 34 条
  • [1] Experimental and theoretical investigation of nanofiltration membranes for liquid desiccant regeneration in air conditioning applications
    Pasqualin, P.
    Davies, P. A.
    APPLIED THERMAL ENGINEERING, 2023, 221
  • [2] Experimental Study on Vacuum Membrane Distillation Liquid Regeneration of Liquid Desiccant Air Conditioning System
    Zhou, Jun-Ming
    Zhang, Xiao-Song
    Kung Cheng Je Wu Li Hsueh Pao/Journal of Engineering Thermophysics, 2020, 41 (11): : 2635 - 2640
  • [3] Theoretical and experimental investigations of a liquid desiccant filmed cellulose fibre heat and mass exchanger
    Liu, S.
    Zhao, X.
    Riffat, S.
    Yuan, Y.
    INTERNATIONAL JOURNAL OF ENERGY RESEARCH, 2009, 33 (12) : 1076 - 1088
  • [4] Computational and experimental analyses on three fluid operated novel hollow fiber membrane based liquid desiccant dehumidifier
    Tejes, P. K. S.
    Naik, B. Kiran
    THERMAL SCIENCE AND ENGINEERING PROGRESS, 2024, 53
  • [5] Comparative review of membrane-based desalination technologies for energy-efficient regeneration in liquid desiccant air conditioning of greenhouses
    Pasqualin, P.
    Lefers, R.
    Mahmoud, S.
    Davies, P. A.
    RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2022, 154
  • [6] Performance testing of a novel 3-fluid liquid-to-air membrane energy exchanger (3-fluid LAMEE) under desiccant solution regeneration operating conditions
    Abdel-Salam, Mohamed R. H.
    Besant, Robert W.
    Simonson, Carey J.
    INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2016, 95 : 773 - 786
  • [7] Performance investigation of desiccant liquid air membrane energy exchanger: Air and lithium chloride effects
    Sabek, S.
    Ben Nasr, K.
    Tiss, F.
    Chouikh, R.
    Guizani, A.
    INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2017, 80 : 145 - 157
  • [8] An experimental study on dehumidification and regeneration performance of a new nonporous membrane-based heat and mass exchanger using an ionic liquid desiccant
    Wang, Lingshi
    Liu, Xiaobing
    Qu, Ming
    Liu, Xiaoli
    Bahar, Bamdad
    ENERGY AND BUILDINGS, 2022, 254
  • [9] Experimental study and energy efficiency analysis of liquid desiccant regeneration using hot air
    Yin, Yong-Gao
    Pan, Xiong-Wei
    Chen, Yao
    Zhang, Xiao-Song
    Kung Cheng Je Wu Li Hsueh Pao/Journal of Engineering Thermophysics, 2013, 34 (04): : 595 - 600
  • [10] An experimental study on liquid regeneration process of a liquid desiccant air conditioning system (LDACs) based on vacuum membrane distillation
    Zhou, Junming
    Wang, Faming
    Noor, Nuruzzaman
    Zhang, Xiaosong
    ENERGY, 2020, 194 (194)