Calibrating whole building energy models: Detailed case study using hourly measured data

被引:141
|
作者
Raftery, Paul [1 ]
Keane, Marcus [1 ]
Costa, Andrea [1 ]
机构
[1] Natl Univ Ireland, Informat Res Unit Sustainable Engn, Galway, Ireland
关键词
Simulation; Calibration; EnergyPlus; Whole building energy model; Case study; Hourly data; Visualisation; Version control; SIMULATION PROGRAMS;
D O I
10.1016/j.enbuild.2011.09.039
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
This paper demonstrates a systematic, evidence-based methodology for calibrating whole building energy models. The methodology uses version control software to store a complete history of the calibration process, including the evidence on which decisions were made. This paper details the calibration of a whole building energy model to hourly energy consumption data using the methodology. The case study building was a 30,000m(2). four-floor office building located on Intel's campus in Ireland. The final calibrated model represents the building to a high level of detail using a large number of zones and uses measured lighting and plug load data in the simulation at hourly intervals. The results show excellent correlation with the measured HVAC consumption data for the analysed year (2007), demonstrating the effectiveness of the methodology. Mean Bias Error (MBE) and Cumulative Variation of Root Mean Squared Error (CVRMSE((hourly))) for HVAC electrical consumption were -4.16% and 7.8%, respectively for the final model. This model was then used to investigate Energy Conservation Measures (ECMs) for feasibility. The paper concludes with a discussion of discrepancies remaining in the model, the issues encountered related to the criteria used for determining when a model is calibrated, and recommendations for future calibration case studies. (C) 2011 Elsevier B.V. All rights reserved.
引用
收藏
页码:3666 / 3679
页数:14
相关论文
共 50 条
  • [1] Procedures for calibrating hourly simulation models to measured building energy and environmental data
    Haberl, JS
    Bou-Saada, TE
    [J]. JOURNAL OF SOLAR ENERGY ENGINEERING-TRANSACTIONS OF THE ASME, 1998, 120 (03): : 193 - 204
  • [2] Building energy model calibration: A detailed case study using sub-hourly measured data
    Guyot, Dimitri
    Giraud, Florine
    Simon, Florian
    Corgier, David
    Marvillet, Christophe
    Tremeac, Brice
    [J]. ENERGY AND BUILDINGS, 2020, 223
  • [3] Calibrating whole building energy model: a case study using BEMS data
    Nolan, E.
    Allsopp, J.
    Galata, A.
    Pedone, G.
    Zivkovic, B.
    Sretenovic, A.
    [J]. EWORK AND EBUSINESS IN ARCHITECTURE, ENGINEERING AND CONSTRUCTION 2014, 2015, : 487 - 494
  • [4] An automated optimization method for calibrating building energy simulation models with measured data: Orientation and a case study
    Yang, Tao
    Pan, Yiqun
    Mao, Jiachen
    Wang, Yonglong
    Huang, Zhizhong
    [J]. APPLIED ENERGY, 2016, 179 : 1220 - 1231
  • [5] Calibrating historic building energy models to hourly indoor air and surface temperatures: Methodology and case study
    Roberti, Francesca
    Oberegger, Ulrich Filippi
    Gasparella, Andrea
    [J]. ENERGY AND BUILDINGS, 2015, 108 : 236 - 243
  • [6] Incorporating variable refrigerant flow (VRF) heat pump systems in whole building energy simulation - Detailed case study using measured data
    Kani-Sanchez, Cassandra
    Richman, Russell
    [J]. JOURNAL OF BUILDING ENGINEERING, 2017, 12 : 314 - 324
  • [7] Calibrating detailed building energy simulation programs with measured data - Part II: Application, to three case study office buildings (RP-1051)
    Reddy, T. Agami
    Maor, Itzhak
    Panjapornpon, Chanin
    [J]. HVAC&R RESEARCH, 2007, 13 (02): : 243 - 265
  • [8] BAYESIAN CALIBRATING EDUCATIONAL BUILDING THERMAL MODELS TO HOURLY INDOOR AIR TEMPERATURE: METHODOLOGY AND CASE STUDY
    Hou, Danlin
    Shu, Chang
    Ji, Lili
    Hassan, Ibrahim Galal
    Wang, Liangzhu
    [J]. PROCEEDINGS OF THE 2021 ASME VERIFICATION AND VALIDATION SYMPOSIUM (VVS2021), 2021,
  • [9] Calibrating detailed building energy simulation programs with measured data - Part 1: General methodology (RP-1051)
    Reddy, T. Agami
    Maor, Itzhak
    Panjapornpon, Chanin
    [J]. HVAC&R RESEARCH, 2007, 13 (02): : 221 - 241
  • [10] Calibrating whole building energy models: An evidence-based methodology
    Raftery, Paul
    Keane, Marcus
    O'Donnell, James
    [J]. ENERGY AND BUILDINGS, 2011, 43 (09) : 2356 - 2364