Experimental comparative research on electrodialysis regeneration for liquid desiccant with different concentrations in liquid desiccant air-conditioning system

被引:26
|
作者
Cheng, Qing [1 ]
Zhang, Xiaosong [2 ]
Jiao, Shun [1 ]
机构
[1] Nanjing Tech Univ, Sch Energy Sci & Engn, Nanjing 211800, Jiangsu, Peoples R China
[2] Southeast Univ, Sch Energy & Environm, Nanjing 210096, Jiangsu, Peoples R China
关键词
Liquid desiccant; Electrodialysis regeneration; Different concentrations; Comparative research; Experimental study; REFRIGERATION SYSTEM; ENERGY-CONSUMPTION; COOLING SYSTEM; DRIVEN; DEHUMIDIFICATION; PERFORMANCE; DESALINATION; CALCIUM; LITHIUM; STAGE;
D O I
10.1016/j.enbuild.2017.09.055
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
The issue of energy and environment is increasingly prominent, and air-conditioning system costs a lot of energy in the building. The liquid desiccant air-conditioning system is a novel air-conditioner with good energy saving potential, whose energy consumption mainly relies on the regeneration process of liquid desiccant. In this paper, an experimental system of electrodialysis (ED) regenerator was set up to confirm the stability of the ED regenerator for the regeneration of liquid desiccant with different concentrations and the regeneration performance of the ED regenerator for liquid desiccant with different concentrations was investigated. Moreover, the ideal COP of the liquid desiccant air-conditioning system and vapor pressure of the acquired strong desiccant at the exit of the ED regenerator were also evaluated to compare the characteristic of the ED regenerator for liquid desiccant with different concentrations. The result shows that besides high concentration, the low temperature is also very important for liquid desiccant to have high dehumidification capacity. Moreover, the excessive increase of current will be more harmful to the dehumidification capacity of the acquired strong liquid desiccant when liquid desiccant concentration is around 35%. Furthermore, when liquid desiccant concentration is around 35%, the ED regenerator needs more power to achieve liquid desiccant with the same dehumidification capacity. (C) 2017 Elsevier B.V. All rights reserved.
引用
收藏
页码:475 / 483
页数:9
相关论文
共 50 条
  • [1] A solar desiccant pre-treatment electrodialysis regeneration system for liquid desiccant air-conditioning system
    Cheng, Qing
    Zhang, Xiao-Song
    [J]. ENERGY AND BUILDINGS, 2013, 67 : 434 - 444
  • [2] Experimental Research on Liquid Desiccant Air-conditioning Unit
    Feng, Yueyan
    Li, Yinglin
    [J]. 2016 3RD INTERNATIONAL CONFERENCE ON MANUFACTURING AND INDUSTRIAL TECHNOLOGIES, 2016, 70
  • [3] Performance investigation on electrodialysis regeneration of potassium formate desiccant solution for liquid desiccant air-conditioning systems
    Hong, Jeong Kuk
    Hwang, Inchan
    Roh, Chul Woo
    Kim, Min Soo
    [J]. ENERGY AND BUILDINGS, 2022, 266
  • [4] A Review of Regeneration Methods for Liquid Desiccant Air-Conditioning System
    Cheng, Qing
    Zhang, Xiaosong
    [J]. PROCEEDINGS OF THE 2013 INTERNATIONAL CONFERENCE ON MATERIAL SCIENCE AND ENVIRONMENTAL ENGINEERING (MSEE 2013), 2013, : 1 - 5
  • [5] Experimental and theoretical research on the electrical conductivity of a liquid desiccant for the liquid desiccant air-conditioning system: LiCl aqueous solution
    Wang, Han
    Cheng, Qing
    Feng, Wei
    Xu, Wenhao
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2018, 91 : 189 - 198
  • [6] A current efficiency model coupled with desiccant molecular weight for electrodialysis regeneration in liquid desiccant air-conditioning systems
    Cheng, Qing
    Wang, Han
    Zhu, Lin
    Chen, Yao
    [J]. ENERGY & ENVIRONMENT, 2023, 34 (04) : 909 - 926
  • [7] A novel experimental apparatus of a liquid desiccant air-conditioning system
    Zhang, Qing
    Liu, Jianhua
    Gao, Wenzhong
    Zhang, Liang
    [J]. ELECTRICAL POWER & ENERGY SYSTEMS, PTS 1 AND 2, 2012, 516-517 : 1121 - +
  • [8] Performance analysis of a novel multi-function liquid desiccant regeneration system for liquid desiccant air-conditioning system
    Cheng, Qing
    Xu, Wenhao
    [J]. ENERGY, 2017, 140 : 240 - 252
  • [9] Review of solar regeneration methods for liquid desiccant air-conditioning system
    Cheng, Qing
    Zhang, Xiaosong
    [J]. ENERGY AND BUILDINGS, 2013, 67 : 426 - 433
  • [10] Performance comparison on different liquid desiccants in the liquid desiccant air-conditioning using electrodialysis regeneration: LiCl and LiBr aqueous solutions
    Cheng, Qing
    Pei, Wang
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2019, 107 : 1 - 10