Hotspot Temperature Prediction of Dry-Type Transformers Based on Particle Filter Optimization with Support Vector Regression

被引:11
|
作者
Sun, Yuanyuan [1 ]
Xu, Gongde [1 ]
Li, Na [1 ]
Li, Kejun [1 ]
Liang, Yongliang [1 ]
Zhong, Hui [1 ]
Zhang, Lina [2 ]
Liu, Ping [3 ]
机构
[1] Shandong Univ, Sch Elect & Engn, Jinan 250061, Peoples R China
[2] CNOOC Res Inst, Engn Res & Design Dept, Beijing 100027, Peoples R China
[3] CNOOC Energy Dev Equipment & Technol Co, Tianjin 300452, Peoples R China
来源
SYMMETRY-BASEL | 2021年 / 13卷 / 08期
关键词
dry-type transformer; overheating fault; hotspot temperature prediction; online monitoring; support vector regression; particle filter; POWER TRANSFORMER; MACHINES;
D O I
10.3390/sym13081320
中图分类号
O [数理科学和化学]; P [天文学、地球科学]; Q [生物科学]; N [自然科学总论];
学科分类号
07 ; 0710 ; 09 ;
摘要
Both poor cooling methods and complex heat dissipation lead to prominent asymmetry in transformer temperature distribution. Both the operating life and load capacity of a power transformer are closely related to the winding hotspot temperature. Realizing accurate prediction of the hotspot temperature of transformer windings is the key to effectively preventing thermal faults in transformers, thus ensuring the reliable operation of transformers and accurately predicting transformer operating lifetimes. In this paper, a hot spot temperature prediction method is proposed based on the transformer operating parameters through the particle filter optimization support vector regression model. Based on the monitored transformer temperature, load rate, transformer cooling type, and ambient temperature, the hotspot temperature of a dry-type transformer can be predicted by a support vector regression method. The hyperparameters of the support vector regression are dynamically optimized here according to the particle filter to improve the optimization accuracy. The validity and accuracy of the proposed method are verified by comparing the proposed method with a traditional support vector regression method based on the real operating data of a 35 kV dry-type transformer.
引用
收藏
页数:19
相关论文
共 50 条
  • [1] Research on Fault Identification Method of Dry-type Transformers Based on Support Vector Machine
    Ji, Ling
    Li, Kunpeng
    Zhang, Pengfei
    Bao, Liwen
    Huang, Yunkai
    2019 22ND INTERNATIONAL CONFERENCE ON ELECTRICAL MACHINES AND SYSTEMS (ICEMS 2019), 2019, : 4497 - 4502
  • [2] Oil temperature prediction of power transformers based on modified support vector regression machine
    Xi, Yu
    Lin, Dong
    Yu, Li
    Chen, Bo
    Jiang, Wenhui
    Chen, Guangqin
    INTERNATIONAL JOURNAL OF EMERGING ELECTRIC POWER SYSTEMS, 2023, 24 (03) : 367 - 375
  • [3] Temperature Protection Based on Temperature Variation Acceleration for Dry-type Transformers: Principle and Algorithm
    Feng, Jianqin
    Dong, Yu
    Song, Hailong
    Huang, Sifang
    Cui, Guangzhao
    RECENT ADVANCES IN ELECTRICAL & ELECTRONIC ENGINEERING, 2016, 9 (02) : 152 - 158
  • [4] FEM-based Modeling and Optimization of Dry-Type Transformers with Metaheuristic Algorithms
    Kul, Seda
    Tezcan, Suleyman Sungur
    Duysak, Huseyin
    Celtek, Seyit Alperen
    TEHNICKI VJESNIK-TECHNICAL GAZETTE, 2022, 29 (05): : 1678 - 1685
  • [5] Earthquake prediction with meteorological data by particle filter-based support vector regression
    Hajikhodaverdikhana, Pouria
    Nazari, Mousa
    Mohsenizadeh, Mehrdad
    Shamshirband, Shahaboddin
    Chau, Kwok-wing
    ENGINEERING APPLICATIONS OF COMPUTATIONAL FLUID MECHANICS, 2018, 12 (01) : 679 - 688
  • [6] Optimization of Mechanical Properties of Insulation Materials for Dry-Type Transformers
    Huang, Jing
    Chen, Bangfa
    Li, Woyang
    2023 IEEE/IAS INDUSTRIAL AND COMMERCIAL POWER SYSTEM ASIA, I&CPS ASIA, 2023, : 184 - 188
  • [7] Fault prediction method of improving particle filter with support vector regression
    Deng, Sen
    Jing, Bo
    Zhou, Hong-Liang
    Jisuanji Jicheng Zhizao Xitong/Computer Integrated Manufacturing Systems, CIMS, 2012, 18 (09): : 2012 - 2017
  • [8] TEMPERATURE RISE VERSUS EFFICIENCY IN DRY-TYPE TRANSFORMERS.
    Bowers, George H.
    Goethe, Paul K.
    Insulation, circuits, 1980, 26 (06):
  • [9] Temperature rise analysis and calculation of cast resin dry-type transformers
    Xiong, L. (lxiong@cqu.edu.cn), 1600, Science Press (39):
  • [10] Analysis of temperature distribution in cast-resin dry-type transformers
    Rahimpour, Ebrahim
    Azizian, Davood
    ELECTRICAL ENGINEERING, 2007, 89 (04) : 301 - 309