A combined passive-active sensor fault detection and isolation approach for air handling units

被引:35
|
作者
Padilla, Miguel [1 ]
Choiniere, Daniel [1 ]
机构
[1] CanmetENERGY, Nat Resources Canada, Varennes, PQ J3X 1S6, Canada
关键词
DIAGNOSTIC-TOOL; PCA;
D O I
10.1016/j.enbuild.2015.04.035
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
A combined passive/active fault detection and isolation approach is presented based on the use of data-driven models to detect faults, and Active Functional Testing (AFT) to isolate them in air handling units (AHU). A model developed in Modelica allows for simulation of the dynamic behavior of the system under different operating conditions. Four case studies are presented for the supply air temperature sensor under different sensor biases. Two steps are followed in the proposed strategy to identify the cause of the abnormal operation in the system: the first step is to detect the fault or a set of potential faults based on the principal components analysis (PCA) method; the second step is to isolate the effective fault among possible candidates by applying AFT. Simulation results and site experiments show that this approach is able to effectively detect and isolate faults in AHUs. Crown Copyright (C) 2015 Published by Elsevier B.V. All rights reserved.
引用
收藏
页码:214 / 219
页数:6
相关论文
共 50 条
  • [1] A combined passive-active method for diagnosing multiplicative fault
    Zhou, Jinming
    Zhu, Yucai
    Shao, Zhijiang
    [J]. PROCESS SAFETY AND ENVIRONMENTAL PROTECTION, 2023, 178 : 959 - 975
  • [2] Passive-active fault detection of Boolean control networks
    Zhao, Rong
    Feng, Jun-e
    Wang, Biao
    [J]. JOURNAL OF THE FRANKLIN INSTITUTE-ENGINEERING AND APPLIED MATHEMATICS, 2022, 359 (13): : 7196 - 7218
  • [3] Biological aerosol detection with combined passive-active infrared measurements
    Ifarraguerri, A
    Vanderbeek, R
    Ben-David, A
    [J]. CHEMICAL AND BIOLOGICAL STANDOFF DETECTION II, 2004, 5584 : 85 - 92
  • [4] A sensor fault detection strategy for air handling units using cluster analysis
    Yan, Rui
    Ma, Zhenjun
    Kokogiannakis, Georgios
    Zhao, Yang
    [J]. AUTOMATION IN CONSTRUCTION, 2016, 70 : 77 - 88
  • [5] Sequential rule based algorithms for temperature sensor fault detection in air handling units
    Yang, Hooncheul
    Cho, Soo
    Tae, Choon-Seob
    Zaheeruddin, M.
    [J]. ENERGY CONVERSION AND MANAGEMENT, 2008, 49 (08) : 2291 - 2306
  • [6] Robust Passive-Active Mounts for vibration isolation
    Su, JHS
    [J]. SMART STRUCTURES AND MATERIALS 1999: PASSIVE DAMPING AND ISOLATION, 1999, 3672 : 144 - 155
  • [7] Research on Fault Detection Method for Air Handling Units System
    Sun, Liangliang
    Li, Yupeng
    Jia, Haiqi
    Ying, Yu
    [J]. IFAC PAPERSONLINE, 2019, 52 (03): : 79 - 84
  • [8] Integrated Control and Fault Detection of Air-Handling Units
    Seem, John E.
    House, John M.
    [J]. HVAC&R RESEARCH, 2009, 15 (01): : 25 - 55
  • [9] Unsupervised learning for fault detection and diagnosis of air handling units
    Yan, Ke
    Huang, Jing
    Shen, Wen
    Ji, Zhiwei
    [J]. ENERGY AND BUILDINGS, 2020, 210
  • [10] Evaluation of the performance of a passive-active vibration isolation system
    Sun, L. L.
    Hansen, C. H.
    Doolan, C.
    [J]. MECHANICAL SYSTEMS AND SIGNAL PROCESSING, 2015, 50-51 : 480 - 497