Effect of sensor position on the performance of CO2-based demand controlled ventilation

被引:47
|
作者
Pei, Gen [1 ]
Rim, Donghyun [1 ]
Schiavon, Stefano [2 ]
Vannucci, Matthew [2 ]
机构
[1] Penn State Univ, Dept Architectural Engn, University Pk, PA 16802 USA
[2] Univ Calif Berkeley, Ctr Built Environm, Berkeley, CA 94720 USA
关键词
Indoor air quality; CO2; sensing; Computational fluid dynamics; Building energy; Displacement ventilation; INDOOR AIR-QUALITY; DISPLACEMENT VENTILATION; CARBON-DIOXIDE; ENVIRONMENT; VALIDATION; HEALTH; RATES; FLOW; SIMULATION; DISPERSION;
D O I
10.1016/j.enbuild.2019.109358
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
CO2-based demand controlled ventilation (DCV) can save energy while maintaining acceptable indoor air quality. CO2 concentration may vary within an occupied space and it is unclear how sensor location influences the ventilation and energy performances. The objective of the present study is to investigate the effect of CO2 sensor position on the performance of DCV systems under mixing and displacement ventilation. Experimentally validated computational fluid dynamics (CFD) models were simulated under representative indoor ventilation and occupancy conditions. The results show that the ventilation strategy, occupancy level, and air change rate have notable impacts on the CO2 sensing performance. Under mixing ventilation, CO2 sensors placed at the room exhaust can meet the requirements of sensor accuracy defined by ASTM E741 and California Title 24. However, the sensor errors associated with sensor location can be higher than the acceptable threshold under displacement ventilation, which exhibits vertical CO2 stratification with two separated zones (lower transition zone and upper uniform zone). The dividing height of the two zones is highly sensitive to the occupancy level. In such cases, exhaust sensors can overestimate the breathing zone concentration and result in additional energy consumptions for thermal conditioning as well as fan operation, especially for densely occupied buildings. The study findings suggest that for ensuring good performance of CO2-based displacement ventilation, it is necessary to develop quantitative relationships between CO2 concentrations at the breathing height and the room exhaust considering ventilation strategies. (C) 2019 Elsevier B.V. All rights reserved.
引用
收藏
页数:11
相关论文
共 50 条
  • [1] Literature review on CO2-based demand-controlled ventilation
    Emmerich, Steven J.
    Persily, Andrew K.
    [J]. ASHRAE Transactions, 1997, 103 (pt 2): : 229 - 243
  • [2] Energy and IAQ impacts of CO2-based demand-controlled ventilation
    Carpenter, Stephen C.
    [J]. ASHRAE Transactions, 1996, 102 (02): : 80 - 88
  • [3] Energy and IAQ impacts of CO2-based demand-controlled ventilation
    Carpenter, SC
    [J]. ASHRAE TRANSACTIONS 1996, VOL 102, PT 2, 1996, 102 : 80 - 88
  • [4] Experimental validation of CO2-based occupancy detection for demand-controlled ventilation
    Wang, SW
    Burnett, J
    Chong, HS
    [J]. INDOOR AND BUILT ENVIRONMENT, 1999, 8 (06) : 377 - 391
  • [5] CO2-Based Demand-Controlled Ventilation and Its Implications for Interior Design
    Lee, Seunghae
    [J]. JOURNAL OF INTERIOR DESIGN, 2012, 37 (02) : 19 - 33
  • [6] Minimum sensor grid density and configuration to enable CO2-based demand-controlled ventilation in an office building
    Hobson, Brodie W.
    Markus, Andre A.
    Gunay, H. Burak
    Rizvi, Farzeen
    [J]. ENERGY AND BUILDINGS, 2023, 298
  • [7] Demand-controlled ventilation -: CO2-based DCV using 62.1-2004
    Taylor, ST
    [J]. ASHRAE JOURNAL, 2006, 48 (05) : 67 - +
  • [8] ENERGY AND VENTILATION PERFORMANCE ANALYSIS FOR CO2-BASED DEMAND-CONTROLLED VENTILATION IN MULTIPLE ZONE VAV SYSTEMS WITH MULTIPLE RECIRCULATION PATHS
    Lu, Xing
    Yang, Tao
    O'Neill, Zheng
    Zhou, XiaoHui
    [J]. 2020 ASHRAE BUILDING PERFORMANCE ANALYSIS CONFERENCE AND SIMBUILD, 2020, : 308 - 316
  • [9] CO2-Based Demand Controlled Ventilation for Variable Air Volume Systems Serving Multiple Zones
    Lau, Josephine
    [J]. INDOOR AND BUILT ENVIRONMENT, 2013, 22 (05) : 721 - 723
  • [10] Unlocking ventilation flexibility of large airport terminals through an optimal CO2-based demand-controlled ventilation strategy
    Tang, Hao
    Yu, Juan
    Geng, Yang
    Wang, Zhe
    Liu, Xue
    Huang, Zujian
    Lin, Borong
    [J]. BUILDING AND ENVIRONMENT, 2023, 244