Optimal location of voltage sags monitors by determining the vulnerable area of network buses

被引:0
|
作者
Jalalat, Hamed [1 ]
Bina, Mohammad Tavakoli [1 ]
Shahirinia, Amir [2 ]
机构
[1] KN Toosi Univ Technol, Elect Engn Dept, Tehran, Iran
[2] Univ Dist Columbia, Elect Engn Dept, Washington, DC USA
关键词
voltage sag; power quality; area of vulnerability (AOV); monitoring buses;
D O I
10.1109/SGC54087.2021.9664120
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
However, to analyze power quality parameters, it is necessary to record information through network buses but in order to save money, a limited number of buses are selected for this purpose. This paper presents the method of determining monitoring buses to observe the voltage sags in all parts of the network for the occurrence of any type of short circuit faults in the network. In this method, the number and location of monitoring buses are selected so that for the minimum number of monitoring buses, all network points are covered due to short circuit faults. For this purpose, first, by determining the vulnerable areas of network buses and then forming a monitor reach matrix for the network, the location and the minimum number of monitoring buses can be determined. The IEEE 14-bus system and 57 bus system are used to implement the proposed method.
引用
下载
收藏
页码:24 / 29
页数:6
相关论文
共 33 条
  • [1] An Approach Based on Analytical Expressions for Optimal Location of Voltage Sags Monitors
    Espinosa-Juarez, Elisa
    Hernandez, Araceli
    Olguin, Gabriel
    IEEE TRANSACTIONS ON POWER DELIVERY, 2009, 24 (04) : 2034 - 2042
  • [2] Optimal Allocation of Monitors by Analyzing the Vulnerability Area Against Voltage Sags
    Kempner, Thais Reggina
    Oleskovicz, Mario
    Santos, Athila Quaresma
    2014 IEEE 16TH INTERNATIONAL CONFERENCE ON HARMONICS AND QUALITY OF POWER (ICHQP), 2014, : 536 - 540
  • [3] Optimal location of voltage sags monitoring buses, based on the correlation rate between network buses with considering the probability distribution of variables
    Jalalat, Hamed
    Liasi, Sahand
    ELECTRICAL ENGINEERING, 2023, 105 (01) : 509 - 518
  • [4] Optimal location of voltage sags monitoring buses, based on the correlation rate between network buses with considering the probability distribution of variables
    Hamed Jalalat
    Sahand Liasi
    Electrical Engineering, 2023, 105 : 509 - 518
  • [5] Optimal Location of Voltage Sag Monitors in Distribution Networks With DGs Using Network Zoning
    Saadat, Amin
    Hooshmand, Rahmat-Allah
    Kiyoumarsi, Arash
    Tadayon, Mahdi
    IEEE TRANSACTIONS ON POWER DELIVERY, 2023, 38 (06) : 4157 - 4165
  • [6] A Generalized Fault Location Method Based on Voltage Sags for Distribution Network
    Awalin, Lilik Jamilatul
    Mokhlis, Hazlie
    Abu Bakar, AbHalim
    Mohamad, Hasmaini
    Illias, Hazlee A.
    IEEJ TRANSACTIONS ON ELECTRICAL AND ELECTRONIC ENGINEERING, 2013, 8 : S38 - S46
  • [7] Fault Location of Voltage Sag based on Optimal Allocation of Monitors
    Liu, Chong
    Tian, Lijun
    Hou, Yanwen
    Gao, Yunxing
    2018 CHINA INTERNATIONAL CONFERENCE ON ELECTRICITY DISTRIBUTION (CICED), 2018, : 726 - 730
  • [8] A generalized fault location method based on voltage sags for distribution network
    Awalin, Lilik Jamilatul
    Mokhlis, Hazlie
    Abu Bakar, Abhalim
    Mohamad, Hasmaini
    Illias, Hazlee A.
    IEEJ Transactions on Electrical and Electronic Engineering, 2013, 8 (SUPL.1):
  • [9] Optimal Placement of Voltage Sag Monitors Based on Fault Location Principle
    Chen, L. P.
    Xu, W. T.
    Cao, K. J.
    2014 INTERNATIONAL CONFERENCE ON POWER SYSTEM TECHNOLOGY (POWERCON), 2014,
  • [10] Improved Fault Location on Distribution Network Based on Multiple Measurements of Voltage Sags Pattern
    Awalin, L. J.
    Mokhlis, H.
    Halim, A. H. A.
    2012 IEEE INTERNATIONAL CONFERENCE ON POWER AND ENERGY (PECON), 2012, : 767 - 772