An experimental study on the thermal characteristics and heating effect of arc-fault from Cu core in residential electrical wiring fires

被引:14
|
作者
Du, Jian-Hua [1 ]
Tu, Ran [1 ]
Zeng, Yi [2 ]
Pan, Leng [1 ]
Zhang, Ren-Cheng [1 ]
机构
[1] Huaqiao Univ, Coll Mech Engn & Automat, Xiamen, Fujian, Peoples R China
[2] Huaqiao Univ, Coll Tourism, Quanzhou, Fujian, Peoples R China
来源
PLOS ONE | 2017年 / 12卷 / 08期
基金
中国国家自然科学基金;
关键词
D O I
10.1371/journal.pone.0182811
中图分类号
O [数理科学和化学]; P [天文学、地球科学]; Q [生物科学]; N [自然科学总论];
学科分类号
07 ; 0710 ; 09 ;
摘要
The characteristics of a series direct current (DC) arc-fault including both electrical and thermal parameters were investigated based on an arc-fault simulator to provide references for multi-parameter electrical fire detection method. Tests on arc fault behavior with three different initial circuit voltages, resistances and arc gaps were conducted, respectively. The influences of circuit conditions on arc dynamic image, voltage, current or power were interpreted. Also, the temperature rises of electrode surface and ambient air were studied. The results showed that, first, significant variations of arc structure and light emitting were observed under different conditions. A thin outer burning layer of vapor generated from electrodes with orange light was found due to the extremely high arc temperature. Second, with the increasing electrode gap in discharging, the arc power was shown to have a non monotonic relationship with arc length for constant initial circuit voltage and resistance. Finally, the temperature rises of electrode surface caused by heat transfer from arc were found to be not sensitive with increasing arc length due to special heat transfer mechanism. In addition, temperature of ambient air showed a large gradient in radial direction of arc.
引用
收藏
页数:14
相关论文
共 7 条
  • [1] New Technology for Preventing Residential Electrical Fires: Arc-Fault Circuit Interrupters (AFCIs)
    Douglas A. Lee
    Andrew M. Trotta
    William H. King
    [J]. Fire Technology, 2000, 36 : 145 - 162
  • [2] New technology for preventing residential electrical fires: Arc-fault circuit interrupters (AFCIs)
    Lee, DA
    Trotta, AM
    King, WH
    [J]. FIRE TECHNOLOGY, 2000, 36 (03) : 145 - 162
  • [3] A study of Time/Current characteristics of the ignition processes in Cellulosic material caused by electrical arcing for application in 240V arc-fault circuit interrupters
    Kolker, D.
    Campolo, S.
    Disalvo, N.
    [J]. PROCEEDINGS OF THE 53RD IEEE HOLM CONFERENCE ON ELECTRICAL CONTACTS, 2007, : 105 - +
  • [4] Experimental study on thermal stratification characteristics in tunnel fires under the effect of canyon cross wind
    Yang, Liliang
    Fan, Chuangang
    Luan, Dia
    Ouyang, Richeng
    Tao, Haowen
    Xu, Zhisheng
    Wang, Feiyue
    [J]. JOURNAL OF WIND ENGINEERING AND INDUSTRIAL AERODYNAMICS, 2021, 218
  • [5] Theoretical and experimental study on the effect of nitrogen content on the thermal characteristics of nitrocellulose under low heating rates
    Hua Chai
    Qiangling Duan
    Lin Jiang
    Liang Gong
    Haodong Chen
    Jinhua Sun
    [J]. Cellulose, 2019, 26 : 763 - 776
  • [6] Theoretical and experimental study on the effect of nitrogen content on the thermal characteristics of nitrocellulose under low heating rates
    Chai, Hua
    Duan, Qiangling
    Jiang, Lin
    Gong, Liang
    Chen, Haodong
    Sun, Jinhua
    [J]. CELLULOSE, 2019, 26 (02) : 763 - 776
  • [7] An Experimental Study of the Distance Effect Away from Earthquake Fault on the Soil Deformation Characteristics
    Liu, Guojun
    Zhang, Yingbin
    Ma, Rongxiao
    Ding, Tianli
    Yang, Yating
    Zhang, Shihao
    [J]. NATURAL GEO-DISASTERS AND RESILIENCY, CREST 2023, 2024, 445 : 15 - 24