Post-arc current simulation based on measurement in vacuum circuit breaker with a one-dimensional particle-in-cell model

被引:13
|
作者
Jia, Shenli [1 ]
Mo, Yongpeng [1 ]
Shi, Zongqian [1 ]
Li, Junliang [1 ]
Wang, Lijun [1 ]
机构
[1] Xi An Jiao Tong Univ, State Key Lab Elect Insulat & Power Equipment, Xian 710049, Shaanxi, Peoples R China
基金
美国国家科学基金会;
关键词
HIGH-CURRENT INTERRUPTION; SHEATH DYNAMICS; PLASMA;
D O I
10.1063/1.5004180
中图分类号
O35 [流体力学]; O53 [等离子体物理学];
学科分类号
070204 ; 080103 ; 080704 ;
摘要
The post-arc dielectric recovery process has a decisive effect on the current interruption performance in a vacuum circuit breaker. The dissipation of residual plasma at the moment of current zero under the transient recovery voltage, which is the first stage of the post-arc dielectric recovery process and forms the post-arc current, has attracted many concerns. A one-dimensional particlein-cell model is developed to simulate the measured post-arc current in the vacuum circuit breaker in this paper. At first, the parameters of the residual plasma are estimated roughly by the waveform of the post-arc current which is taken from measurements. After that, different components of the post-arc current, which are formed by the movement of charged particles in the residual plasma, are discussed. Then, the residual plasma density is adjusted according to the proportion of electrons and ions absorbed by the post-arc anode derived from the particle-in-cell simulation. After this adjustment, the post-arc current waveform obtained from the simulation is closer to that obtained from measurements.
引用
收藏
页数:7
相关论文
共 50 条
  • [1] One-dimensional particle-in-cell simulation on the influence of electron and ion temperature on the sheath expansion process in the post-arc stage of vacuum circuit breaker
    Mo, Yongpeng
    Shi, Zongqian
    Jia, Shenli
    Wang, Lijun
    [J]. PHYSICS OF PLASMAS, 2015, 22 (02)
  • [2] Post-arc Sheath Simulation in Vacuum Circuit Breaker with One-dimensional Particle in Cell-Monte Carlo Collisions Method
    Mo, Y. P.
    Shi, Z. Q.
    Jia, S. L.
    Wang, L. J.
    [J]. PROCEEDINGS OF THE 2014 26TH INTERNATIONAL SYMPOSIUM ON DISCHARGES AND ELECTRICAL INSULATION IN VACUUM (ISDEIV-2014), 2014, : 185 - 188
  • [3] Research on Measurement of Post-Arc Current of Mechanical Vacuum DC Circuit Breaker
    Cheng X.
    Xu P.
    Ge G.
    Li X.
    Tian X.
    [J]. Diangong Jishu Xuebao/Transactions of China Electrotechnical Society, 2021, 36 (16): : 3516 - 3524
  • [4] Two-dimensional simulation of the post-arc phase of a vacuum circuit breaker
    Sarrailh, Pierre
    Garrigues, Laurent
    Hagelaar, Gerjan J. M.
    Boeuf, Jean-Pierre
    Sandolache, Gabriela
    Rowe, Stephan W.
    Jusselin, Benoit
    [J]. IEEE TRANSACTIONS ON PLASMA SCIENCE, 2008, 36 (04) : 1046 - 1047
  • [5] STUDY OF THE DISSIPATION OF RESIDUAL PLASMA WITH A ONE-DIMENSIONAL PARTICLE-IN-CELL MODEL IN A VACUUM CIRCUIT BREAKER
    Mo, Yongpeng
    Sw, Zongqian
    Jia, Shenli
    Wang, Lijun
    [J]. 2016 43RD IEEE INTERNATIONAL CONFERENCE ON PLASMA SCIENCE (ICOPS), 2016,
  • [6] Two-Dimensional Particle-in-Cell/Monte Carlo Collisional Simulation of the Post-Arc Breakdown in Vacuum Circuit Breakers
    Wang, Lijun
    Chen, Zhuo
    Wang, Dan
    Lian, Zhuoxi
    Wang, Zhiwei
    Zhang, Runming
    [J]. IEEE Transactions on Plasma Science, 2024, 52 (08) : 3228 - 3236
  • [7] Experimental investigations on the post-arc current of the vacuum circuit breaker in an active mechanical DC circuit breaker
    Jia, Shenli
    Tang, Qiang
    Shi, Zongqian
    Mo, Yongpeng
    [J]. AIP ADVANCES, 2021, 11 (05)
  • [8] Simulation of post-arc dielectric recovery characteristics of DC vacuum circuit breaker
    Liu, Xiaoming
    Yu, Deen
    Zou, Jiyan
    [J]. Zhenkong Kexue yu Jishu Xuebao/Journal of Vacuum Science and Technology, 2014, 34 (12): : 1285 - 1289
  • [9] Post-arc current reconstruction based on actual circuit breaker measurements
    Schavemaker, PH
    van der Sluis, L
    Pharmatrisanti, A
    [J]. IEE PROCEEDINGS-SCIENCE MEASUREMENT AND TECHNOLOGY, 2002, 149 (01) : 17 - 21
  • [10] Post-arc current in low voltage vacuum circuit breaker: Measurements and physical peculiarities
    Pavelescu, D
    Nitu, S
    Dumitrescu, G
    Anghelita, P
    [J]. ISDEIV: XXTH INTERNATIONAL SYMPOSIUM ON DISCHARGES AND ELECTRICAL INSULATION IN VACUUM, PROCEEDINGS, 2002, 20 : 67 - 70