Transient behavior assessments of a single-effect ammonia-water absorption heat pump system: Development of an efficient experimentally validated numerical framework

被引:1
|
作者
Dehghan, B. Babak [1 ]
Aprile, Marcello [1 ]
Pistocchini, Lorenzo [1 ]
Toppi, Tommaso [1 ]
Motta, Mario [1 ]
机构
[1] Politecn Milan, Dept Energy, I-20156 Milan, Italy
关键词
Dynamic performance; Absorption heat pump; Gas heat pump; Discretized finite volume; Tray column heat exchanger; DYNAMIC SIMULATION-MODEL; CHILLER PERFORMANCE; ENERGY;
D O I
10.1016/j.ijheatmasstransfer.2021.121252
中图分类号
O414.1 [热力学];
学科分类号
摘要
In this study, the long-term transient response of a single-effect ammonia-water gas-fired absorption heat pump prototype is investigated both numerically and experimentally. For the numerical model, heat and mass transfer components are divided into four groups; (a) tubular heat exchangers comprising condenser, evaporator, absorber, solution and refrigerant heat exchangers, (b) tray column heat exchanger comprising gas-fired generator, (c) refrigerant and solution tanks, (d) solution pump and restrictors. Components of groups a-c are modelled based on discretized volumes in which the unsteady mass, species and energy conservation equations are imposed, whereas solution pump and restrictors are idealized as algebraic models. The experimental analysis covers a period of over 10 h, during which various step changes are applied to system inputs like gas power, inlet water temperature, solution and refrigerant flow rates, and brine inlet temperature. The results of the numerical model are compared with the experimental data which show good agreement in both transient and near steady state operation. Results show that, during transient operation average deviations are less than 2.94% and near steady-state conditions are less than 1.70%. The accuracy of the numerical model in predicting both the transient response and the steady-state values of the measurable outputs, makes it a valuable tool to gain insight on the internal dynamics of ammonia-water absorption heat pumps and cut down costs on time-consuming optimization experiments, such as the fine-tuning of initial solution charge, the implementation of a suitable concentration control strategy and the performance optimization at full and partial loads. (c) 2021 Elsevier Ltd. All rights reserved.
引用
收藏
页数:19
相关论文
共 11 条
  • [1] Dynamic simulation of a single-effect ammonia-water absorption chiller
    Kim, Byongjoo
    Park, Jongil
    INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2007, 30 (03): : 535 - 545
  • [2] Performance characteristics of an ammonia-water absorption heat pump system
    Gadalla, Mohamed A.
    Ibrahim, Talaat A.
    Hassan, Mohamed A. M.
    INTERNATIONAL JOURNAL OF ENERGY RESEARCH, 2013, 37 (14) : 1917 - 1927
  • [3] DEVELOPMENT OF AMMONIA-WATER ABSORPTION HEAT PUMP WATER HEATER FOR RESIDENTIAL AND COMMERCIAL APPLICATIONS
    Garrabrant, Michael
    Stout, Roger
    Glanville, Paul
    Keinath, Chris
    Garimella, Srinivas
    PROCEEDINGS OF THE ASME 7TH INTERNATIONAL CONFERENCE ON ENERGY SUSTAINABILITY, 2013, 2014,
  • [4] The effect of lithium bromide on the performance of ammonia-water absorption-resorption heat pump system
    Jin, Zhenghao
    Li, Shuhong
    Xu, Mengkai
    Xu, Chengcheng
    Feng, Lijie
    Du, Kai
    APPLIED THERMAL ENGINEERING, 2020, 181
  • [5] Development of a novel unbalanced ammonia-water absorption-resorption heat pump cycle for space heating
    Jia, Teng
    Dai, Yanjun
    ENERGY, 2018, 161 : 251 - 265
  • [6] Graphical analysis on internal heat recovery of a single stage ammonia-water absorption refrigeration system
    Du, S.
    Wang, R. Z.
    Xia, Z. Z.
    ENERGY, 2015, 80 : 687 - 694
  • [7] Thermodynamic analysis of an ammonia-water solution cross-type absorption-resorption heat pump system
    Feng, Lijie
    Jin, Zhenghao
    Zhou, Runfa
    Xu, Mengkai
    Qin, Luwen
    Li, Shuhong
    APPLIED THERMAL ENGINEERING, 2021, 198
  • [8] Development and demonstration of a compact ammonia-water absorption heat pump prototype with microscale features for space-conditioning applications
    Garimella, Srinivas
    Keinath, Christopher M.
    Delahanty, Jared C.
    Hoysall, Dhruv C.
    Staedter, Marcel A.
    Goyal, Anurag
    Garrabrant, Michael A.
    APPLIED THERMAL ENGINEERING, 2016, 102 : 557 - 564
  • [9] Downsizing strategy for an air-cooled indirect-fired single-effect ammonia-water absorption chiller in part-load operation in hot climates
    Palacios-Lorenzo, Maria Esther
    Marcos, Jose Daniel
    CASE STUDIES IN THERMAL ENGINEERING, 2024, 53
  • [10] Optimal design of solid oxide fuel cell, ammonia-water single effect absorption cycle and Rankine steam cycle hybrid system
    Mehrpooya, Mehdi
    Dehghani, Hossein
    Moosavian, S. M. Ali
    JOURNAL OF POWER SOURCES, 2016, 306 : 107 - 123