Performance of Dynamic Line Rating Systems for Wind Integration

被引:0
|
作者
Olazarri, J. G. [1 ]
Mazon, A. J. [1 ]
Rementeria, S. [2 ]
Albizu, I. [1 ]
Fernandez, E. [1 ]
机构
[1] Univ Basque Country UPV EHU, Dept Elect Engn, Alda Urquijo S-N, Bilbao 48013, Spain
[2] Arteche Ctr Tecnol, Mungia 48100, Spain
关键词
Ampacity; overhead lines; rating; real-time monitoring;
D O I
暂无
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Different dynamic line rating systems have been developed in order to monitor lines and calculate the actual line rating. In this paper weather, conductor temperature and conductor tension based systems are analyzed. Measurements in two pilot lines were taken. One of them is the 66 kV evacuation line of a wind farm whereas, the other one is a 30 kV distribution line. In the analysis, actual rating values are calculated with the measurements of each system. Due to the fact that DLR results of the conductor temperature and conductor tension systems are inaccurate when differences between conductor temperature and ambient temperature are low, the analysis is made at different temperature ranges.
引用
收藏
页码:567 / 573
页数:7
相关论文
共 50 条
  • [1] Dynamic line rating systems for wind power integration
    Fernandez, E.
    Albizu, I.
    Bedialauneta, M. T.
    Mazon, A. J.
    Leite, P. T.
    [J]. 2012 IEEE POWER ENGINEERING SOCIETY CONFERENCE AND EXPOSITION IN AFRICA (POWERAFRICA), 2012,
  • [2] Review of dynamic line rating systems for wind power integration
    Fernandez, E.
    Albizu, I.
    Bedialauneta, M. T.
    Mazon, A. J.
    Leite, P. T.
    [J]. RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2016, 53 : 80 - 92
  • [3] Impact From Dynamic Line Rating on Wind Power Integration
    Wallnerstrom, Carl Johan
    Huang, Yalin
    Soder, Lennart
    [J]. IEEE TRANSACTIONS ON SMART GRID, 2015, 6 (01) : 343 - 350
  • [4] Dynamic Line Rating of Wind Farm Integration Transmission Lines
    Chen Xiong
    Luo Jianbo
    [J]. 2017 IEEE 7TH ANNUAL INTERNATIONAL CONFERENCE ON CYBER TECHNOLOGY IN AUTOMATION, CONTROL, AND INTELLIGENT SYSTEMS (CYBER), 2017, : 1291 - 1295
  • [5] Dynamic line rating for wind power
    Talpur, Saifal
    Wallnerstrom, Carl Johan
    Flood, Christer
    Hilber, Patrik
    [J]. JOURNAL OF RENEWABLE AND SUSTAINABLE ENERGY, 2016, 8 (01)
  • [6] Dynamic Line Rating Protection for Wind Farm Connections
    Yip, Tony
    An, Chang
    Lloyd, Graeme
    Aten, Martin
    Ferris, Bob
    [J]. 2009 CIGRE/IEEE PES JOINT SYMPOSIUM INTEGRATION OF WIDE-SCALE RENEWABLE RESOURCES INTO THE POWER DELIVERY SYSTEM, 2009, : 330 - 334
  • [7] Influence of the wind variability on the calculation of dynamic line rating
    Gonzalez-Cagigal, M. a.
    Rosendo-Macias, J. A.
    Bachiller-Soler, A.
    Senas-Sanvicente, D.
    [J]. ELECTRIC POWER SYSTEMS RESEARCH, 2022, 211
  • [8] INVESTIGATION OF A DYNAMIC POWER LINE RATING CONCEPT FOR IMPROVED WIND ENERGY INTEGRATION OVER COMPLEX TERRAIN
    Phillips, Tyler B.
    Senocak, Inanc
    Gentle, Jake P.
    Myers, Kurt S.
    Anderson, Phil
    [J]. ASME FLUIDS ENGINEERING DIVISION SUMMER MEETING - 2014, VOL 1D: SYMPOSIA, 2014,
  • [10] Investigating the impact of a dynamic thermal rating on wind farm integration
    Dawson, Leanne
    Knight, Andrew M.
    [J]. IET GENERATION TRANSMISSION & DISTRIBUTION, 2023, 17 (10) : 2449 - 2457