Metallic particle dynamics in a single phase gas insulated busduct with coated electrodes under lightning impulse superimposed on power frequency voltage

被引:2
|
作者
Kumar, Gundavarapu Venkata Nagesh [1 ]
Amarnath, Jinka [2 ]
机构
[1] VSEZ, Visakhapatnam 530046, Andhra Pradesh, India
[2] Jawahar Lal Nehru Technol Univ, Hyderabad 500085, Andhra Pradesh, India
来源
关键词
electric field; gas insulated substations; metallic particles; particle contamination; gas insulated switchgear; lightning impulse;
D O I
10.1002/etep.351
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Conducting particles in transmission and switching equipment insulated by compressed sulphur hexafluoride (SF(6)) can result in loss of as much as 90% of the gas dielectric strength. These particles may be free to move in the electric field or may be fixed on the conductors, thus enhancing local surface fields. In a horizontal coaxial system with particles resting on the inside surface of the enclosure, the motion of such particles is random The power industry has utilized several methods to control and minimize the effect of particle contamination in GIS. One such technique is to apply a dielectric coating to the inside surface of the outer GIS enclosure. The electric field necessary to lift a particle resting on the inside surface of GIS enclosure is much increased due to the coating. Transient over voltages due to lightning and switching surges cause steep build-up of voltage on transmission lines and other electrical apparatus, therefore it is necessary for the GIS also to withstand such voltages without breakdown of insulation. Lightning impulse voltage of 1050 kV is superimposed on power frequency voltages of 75 kV, 100 kV, 132 kV and 145 kV are applied to I-Phase Gas Insulated Bus (I-Phase GIB) and the maximum movement of aluminum, copper, and silver particles is determined. The movement patterns are also determined with and without Monte-Carlo simulation for movement of particle in axial and radial directions. The results an presented and analyzed. Copyright (C) 2009 John Wiley & Sons, Ltd.
引用
收藏
页码:650 / 660
页数:11
相关论文
共 31 条
  • [1] Insulation Characteristics of Gas Insulated Switchgear under Lightning Impulse and AC Superimposed Voltage
    Ueta, Genyo
    Tsuboi, Toshihiro
    Takami, Jun
    Okabe, Shigemitsu
    Ametani, Akihiro
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2014, 21 (03) : 1026 - 1034
  • [2] Movement Patterns of Metallic Particles in a Single Phase Gas Insulated Busduct with Superimposed Lighting and Switching Impulses
    Rao, M. Venu Gopala
    Kumar, G. V. Nagesh
    Amarnath, J.
    Kamakshaiah, S.
    Srivastava, K. D.
    ICHVE 2008: 2008 INTERNATIONAL CONFERENCE ON HIGH VOLTAGE ENGINEERING AND APPLICATION, 2008, : 549 - +
  • [3] Dielectric Behavior of Compact Design Three Phase Coated Gas Insulated Busduct with Metallic Particle Contamination
    Padmavathi, D.
    Kumar, G. V. Nagesh
    Amarnath, J.
    Chowdary, D. Deepak
    ICHVE 2008: 2008 INTERNATIONAL CONFERENCE ON HIGH VOLTAGE ENGINEERING AND APPLICATION, 2008, : 399 - +
  • [4] Insulation integrity of single phase gas insulated busduct with protrusion and depression defects under particle contamination
    Nagaraju, A.
    Reddy, N. Ravi Sankar
    Kiranmayi, R.
    AIN SHAMS ENGINEERING JOURNAL, 2022, 13 (04)
  • [5] Influence of unbalanced voltages on the movement of metallic particle in a three phase common enclosure gas insulated busduct
    Kumar, G. V. Nagesh
    Amarnath, J.
    Singh, B. P.
    Chowdary, D. Deepak
    SADHANA-ACADEMY PROCEEDINGS IN ENGINEERING SCIENCES, 2010, 35 (04): : 393 - 406
  • [6] Insulation Integrity of Metallic Particles in a Gas Insulated Busduct using SF6 and N2 Gas Mixture under the Influence of Power frequency and Impulse Voltages
    Nagabhushan, P.
    Amarnath, J.
    Subbarayudu, D.
    2011 14TH INTERNATIONAL SYMPOSIUM ON ELECTRETS (ISE), 2011, : 195 - +
  • [7] Dynamics of Metallic Particle Contamination in A Gas Insulated Busduct With SF6 And N2 Gas Mixtures
    Rao, M. Raghavendra
    Amarnath, J.
    2010 ANNUAL REPORT CONFERENCE ON ELECTRICAL INSULATION AND DIELECTIC PHENOMENA, 2010,
  • [8] Research on the Effectiveness of Detecting Metal Spike Defects in GIS Under Lightning Impulse Superimposed Power Frequency Voltage
    Sun H.
    Li X.
    Li J.
    Lü Y.
    Zhao K.
    Zhang Q.
    Dianwang Jishu/Power System Technology, 2022, 46 (02): : 795 - 802
  • [9] Simulation of Particle movement in a Single Phase Isolated Gas Insulated Busduct with Image Charge Effect
    Sahu, K. B. Madhu
    Amarnath, J.
    Murthy, K. S. Linga
    Singh, B. P.
    ICHVE 2008: 2008 INTERNATIONAL CONFERENCE ON HIGH VOLTAGE ENGINEERING AND APPLICATION, 2008, : 466 - 469
  • [10] The impact of Particle on FGM insulator in a single phase gas insulated busduct on electric field stress
    Nagaraju, A.
    Reddy, N. Ravi Shankar
    Kiranmayi, R.
    JOURNAL OF APPLIED SCIENCE AND ENGINEERING, 2022, 25 (05): : 833 - 844