Environmental evaluation of an air-conditioning system supplied by cooling energy from a bore-hole based heat pump system

被引:17
|
作者
Heikkila, Katarina [1 ]
机构
[1] Chalmers, Dept Energy & Environm, Bldg Serv Engn, SE-41296 Gothenburg, Sweden
关键词
environmental assessment; life cycle assessment (LCA); air-conditioning system; bore-hole based heat pump; comfort cooling system; office building;
D O I
10.1016/j.buildenv.2006.11.027
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
An evaluation of the environmental impacts of an air-conditioning system which uses a bore-hole system for heating and cooling is the aim of this case study. To facilitate the evaluation, the bore-hole based air-conditioning system is compared with a reference system that uses a more traditional source of heat (district heating) and cooling energy (refrigeration). Environmental impacts of the system are examined by the life cycle assessment (LCA) method, including the weighting step. Results show that the bore-hole based system performs better in three of the four impact categories investigated: acidification, eutrofication, and global warming potential (GWP) with a 100-year horizon. This is mainly due to the fact that it uses less material in the production phase and less operating energy during the user stage. However, in the category of photochemical ozone creation potential (POCP), it performs four times worse than the more traditional system. Nevertheless, the overall environmental impact of the bore-hole based system, evaluated by common weighting methods, is better than the more traditional system. The most dominant environmental impact of both systems arises from the operating energy, although the energy use in the building studied is low. (C) 2007 Elsevier Ltd. All rights reserved.
引用
收藏
页码:51 / 61
页数:11
相关论文
共 50 条
  • [1] Applicability of sewage heat pump air-conditioning system
    陈金华
    刘猛
    刘勇
    靳鸣
    陈洁
    Journal of Central South University, 2009, 16 (S1) : 183 - 187
  • [2] Applicability of sewage heat pump air-conditioning system
    Chen Jin-hua
    Liu Meng
    Liu Yong
    Jin Ming
    Chen Jie
    JOURNAL OF CENTRAL SOUTH UNIVERSITY OF TECHNOLOGY, 2009, 16 : 183 - 187
  • [3] Dynamic analysis of an air-conditioning system with a heat pump
    Balen, I
    Donjerkovic, P
    Galaso, I
    STROJNISKI VESTNIK-JOURNAL OF MECHANICAL ENGINEERING, 2000, 46 (07): : 413 - 421
  • [4] Dynamic analysis of an air-conditioning system with a heat pump
    Balen, Igor
    Donjerković, Petar
    Galaso, Ivan
    2000, Assn Mech Eng & Technicians of Slovenia, Ljubljana, Slovenia (46):
  • [5] A raw water source heat pump air-conditioning system
    Cho, Yong
    Yun, Rin
    ENERGY AND BUILDINGS, 2011, 43 (11) : 3068 - 3073
  • [6] Efficiency and performance evaluation of a novel EV Air-conditioning and battery cooling system with desiccant-coated heat pump
    Zadeh, Peyman Gholamali
    Chung, Jae Dong
    APPLIED THERMAL ENGINEERING, 2025, 264
  • [7] A new heat recovery technique for air-conditioning/heat-pump system
    Gong, Guangcai
    Zeng, Wei
    Wang, Liping
    Wu, Chih
    APPLIED THERMAL ENGINEERING, 2008, 28 (17-18) : 2360 - 2370
  • [8] Energy simulation approach to air-conditioning system evaluation
    Sekhar, SC
    Yat, CJ
    BUILDING AND ENVIRONMENT, 1998, 33 (06) : 397 - 408
  • [9] Air-conditioning System Energy Efficiency and Energy Consumption Evaluation
    Du, Xiaotong
    Cai, Wenjian
    Jia, Lei
    2010 8TH WORLD CONGRESS ON INTELLIGENT CONTROL AND AUTOMATION (WCICA), 2010, : 1908 - 1913
  • [10] ENERGY SAVING IN A HEAT PUMP AIR-CONDITIONING SYSTEM USING LIQUID DESICCANT AND MEMBRANE CONTACTORS
    Bergero, Stefano
    Chiari, Anna
    PROCEEDINGS OF THE ASME INTERNATIONAL MECHANICAL ENGINEERING CONGRESS AND EXPOSITION, 2011, VOL 1, 2012, : 869 - 878