Implementation of DSP based relaying with particular reference to effect of STATCOM on transmission line protection

被引:0
|
作者
Bapiraju, JVV [1 ]
Shenoy, UJ [1 ]
Sheshadri, KG [1 ]
Khincha, HP [1 ]
Thukaram, D [1 ]
机构
[1] Indian Inst Sci, Dept Elect Engn, Bangalore 560012, Karnataka, India
关键词
apparent impedance; distance relays; DSP processor TMS320C50; fourier algorithm; PSCAD/EMTDC; quadrilateral characteristics and STATCOM;
D O I
暂无
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
The presence of Flexible AC Transmission System (FACTS) devices in the loop significantly affects the apparent resistance and reactance seen by a distance relay, as FACTS devices respond to changes in the power system configuration. The objective of this paper is to investigate the effect of mid-point compensation of STATic synchronous COMpensator (STATCOM) on the performance of impedance distance relay under normal load and fault conditions and to implement the adaptive distance relaying scheme for transmission line protection. From the simulation studies carried out in PSCAD software and using analytical calculations, it is identified that there is a need for the distance relay to adapt to the new settings in its characteristic for the detection of fault within the zone of protection of transmission line. Apparent impedance is simulated for different loading and line to ground (L-G) fault conditions at different locations on the power system network. The proposed adaptive distance relay scheme has been implemented on TMS320C50 Digital Signal Processor (DSP) system.
引用
收藏
页码:1381 / 1385
页数:5
相关论文
共 50 条
  • [1] Relaying Scheme for STATCOM Compensated Transmission Line
    Gupta, Om Hari
    Tripathy, Manoj
    2016 IEEE 6TH INTERNATIONAL CONFERENCE ON POWER SYSTEMS (ICPS), 2016,
  • [2] A DWT Based Differential Relaying STATCOM Integrated Wind Fed Transmission Line
    Mishra, S. K.
    Tripathy, L. N.
    Swain, S. C.
    INTERNATIONAL JOURNAL OF RENEWABLE ENERGY RESEARCH, 2018, 8 (01): : 476 - 487
  • [3] Synchrophasors-Based Transmission Line Protection in the Presence of STATCOM
    Ghorbani A.
    Ghorbani M.
    Ebrahimi S.Y.
    Journal of Control, Automation and Electrical Systems, 2017, 28 (1) : 147 - 157
  • [4] Synchrophasors-based transmission line protection in the presence of STATCOM
    Ghorbani, Amir
    Journal of Power Technologies, 2023, 103 (01): : 58 - 71
  • [5] DWT approach based differential relaying scheme for single circuit and double circuit transmission line protection including STATCOM
    Mishra, S. K.
    Tripathy, L. N.
    Swain, S. C.
    AIN SHAMS ENGINEERING JOURNAL, 2019, 10 (01) : 93 - 102
  • [6] A new pilot relaying technique for the STATCOM compensated transmission line
    Gangolu, Suryanarayana
    Sarangi, Saumendra
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2023, 146
  • [7] Synchronized measurement based an adaptive distance relaying scheme for STATCOM compensated transmission line
    Singh, Arvind R.
    Patne, Nita R.
    Kale, Vijay S.
    MEASUREMENT, 2018, 116 : 96 - 105
  • [8] Adaptive Distance Protection in Presence of STATCOM on a Transmission Line
    Kazemi, A.
    Jamali, S.
    Shateri, H.
    2010 IEEE PES TRANSMISSION AND DISTRIBUTION CONFERENCE AND EXPOSITION: SMART SOLUTIONS FOR A CHANGING WORLD, 2010,
  • [9] Taylor series based protection starting element for STATCOM compensated transmission line
    Mundra, Prateek
    Arya, Anoop
    Gawre, Suresh K
    Biswal, Sandeep
    Lopes, Felipe V.
    Malik, Om P.
    Electric Power Systems Research, 2022, 204
  • [10] Taylor series based protection starting element for STATCOM compensated transmission line
    Mundra, Prateek
    Arya, Anoop
    Gawre, Suresh K.
    Biswal, Sandeep
    Lopes, Felipe, V
    Malik, Om P.
    ELECTRIC POWER SYSTEMS RESEARCH, 2022, 204