Data-based modelling and proportional-integral-plus (pip) control of nitrate in an activated sludge benchmark

被引:2
|
作者
Ghavipanjeh, F [1 ]
Taylor, CJ
Young, PC
Chotai, A
机构
[1] Univ Lancaster, Ctr Res Environm Syst & Stat, Lancaster LA1 4YQ, England
[2] Univ Lancaster, Dept Engn, Lancaster LA1 4YR, England
关键词
activated sludge plant; data-based modelling; nitrogen removal; Proportional Integral Plus control;
D O I
10.2166/wst.2001.0021
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
This paper presents the result of an investigation into the Proportional Integral Plus (PIP) control of nitrate in the second zone of an activated sludge benchmark. A data-based reduced order model is used as the control model and identified using the Simplified Refined Instrumental Variable (SRIV) identification and estimation algorithm. The PIP control design is based on the Non Minimum State Space (NMSS) form and State Variable Feedback (SVF) methodology. The PIP controller is tested against dynamic load disturbances and compared with the response of a well tuned PI controller.
引用
收藏
页码:87 / 94
页数:8
相关论文
共 42 条
  • [1] Proportional-integral-plus (PIP) control of time delay systems
    Taylor, CJ
    Chotai, A
    Young, PC
    [J]. PROCEEDINGS OF THE INSTITUTION OF MECHANICAL ENGINEERS PART I-JOURNAL OF SYSTEMS AND CONTROL ENGINEERING, 1998, 212 (I1) : 37 - 48
  • [2] Proportional-integral-plus (PIP) control of the ALSTOM gasifier problem
    Taylor, CJ
    McCabe, AP
    Young, PC
    Chotai, A
    [J]. PROCEEDINGS OF THE INSTITUTION OF MECHANICAL ENGINEERS PART I-JOURNAL OF SYSTEMS AND CONTROL ENGINEERING, 2000, 214 (I6) : 469 - 480
  • [3] Proportional-integral-plus (PIP) control of non-linear systems
    McCabe, A.P.
    Young, P.
    Chotai, A.
    Taylor, C.J.
    [J]. 2000, Technical University of Wroclaw (26):
  • [4] Continuous time proportional-integral-plus (PIP) control with filtering polynomials
    Taylor, CJ
    Chotai, A
    Young, PC
    [J]. UKACC INTERNATIONAL CONFERENCE ON CONTROL '98, VOLS I&II, 1998, : 1391 - 1396
  • [5] Proportional-integral-plus (PIP) control of ventilation rate in agricultural buildings
    Taylor, CJ
    Leigh, P
    Price, L
    Young, PC
    Vranken, E
    Berckmans, D
    [J]. CONTROL ENGINEERING PRACTICE, 2004, 12 (02) : 225 - 233
  • [6] Multivariable proportional-integral-plus (PIP) control of the ALSTOM nonlinear gasifier simulation
    Taylor, C. J.
    Shaban, E. M.
    [J]. IEE PROCEEDINGS-CONTROL THEORY AND APPLICATIONS, 2006, 153 (03): : 277 - 285
  • [7] Proportional-integral-plus control of an intelligent excavator
    Gu, J
    Taylor, J
    Seward, D
    [J]. COMPUTER-AIDED CIVIL AND INFRASTRUCTURE ENGINEERING, 2004, 19 (01) : 16 - 27
  • [8] Proportional-Integral-Plus (PIP) Control System for Individual Thermal Zones in a Small Ventilated Space
    Youssef, Ali
    Exadaktylos, Vasileios
    Ozcan, Sezin E.
    Berckmans, Daniel
    [J]. ASHRAE: TRANSACTIONS 2011, VOL 117, PT 1, 2011, 117 : 48 - 56
  • [9] Design and implementation of a proportional-integral-plus (PIP) control system for temperature, humidity and carbon dioxide in a glasshouse
    Lees, MJ
    Taylor, J
    Chotai, A
    Young, PC
    Chalabi, ZS
    [J]. SECOND I.F.A.C./I.S.H.S. WORKSHOP ON MATHEMATICAL AND CONTROL APPLICATIONS IN AGRICULTURE AND HORTICULTURE, 1996, (406): : 115 - 123
  • [10] Robustness evaluation and robust design for proportional-integral-plus control
    Wilson, Emma D.
    Clairon, Quentin
    Henderson, Robin
    Taylor, C. James