Energy and exergy analysis of an absorption system with working pairs LiBr-H2O and Carrol-H2O at applications of cooling and heating

被引:7
|
作者
Zheng, J. [1 ]
Castro, J. [1 ]
Oliva, A. [1 ]
Oliet, C. [1 ]
机构
[1] Univ Politecn Catalunya BarcelonaTech UPC, Ctr Tecnol Transferencia Calor CTTC, ESEIAAT, Colom 11, E-08222 Barcelona, Spain
关键词
Numerical modelling; Absorption; Refrigeration; Heat pump; LiBr; Carrol; HOT-WATER DRIVEN; LITHIUM-BROMIDE; THERMODYNAMIC ANALYSIS; SMALL CAPACITY; TRANSFORMER; ELECTROLYTE; SINGLE; TEMPERATURES; PERFORMANCE; EQUILIBRIA;
D O I
10.1016/j.ijrefrig.2021.09.011
中图分类号
O414.1 [热力学];
学科分类号
摘要
In this work, an air-cooled, single effect solar-driven absorption system is being evaluated from the point of view of 1st and 2nd thermodynamic principles for two different applications: absorption chiller and heat pump. One of the most widely used working pairs, LiBr-H2O, is applied in this study due to its high performance in the absorption cycle. Their performance is compared with another working pair Carrol-H2O (Carrol contains LiBr and EG-Ethylene glycol- with a mass ratio of 4.5:1). The Carrol solution has the advantage of reducing the crystallization risk at the high concentration solution that enters the absorber. The numerical modelling was implemented on a modular object-oriented simulation platform (NEST platform tool), which allows linking different components, considered objects. In the simulations performed, the heat source temperature in the system is in the range of 70-90 degrees C, and the inlet temperature at evaporator secondary circuit at chiller application is fixed in two values, 9 degrees C and 14 degrees C, and for heat pump application in 0 degrees C and -5 degrees C. Moreover, EG is added to the evaporator at heat pump application to prevent the refrigerant water from freezing below zero. The studied mass concentration range of EG of 10-40%. The result shows the COP of an absorption chiller and heat pump are around 0.7 and 1.6, respectively, and the COP EX values are 0.2-0.6 at chiller application and 0.5-1.5 at heat pump application. When compared with LiBr system, Carrol system has about 6.4% higher COP, about 6.3% higher COPEX , and a decrease of about 19% of cooling capacity. In the heat pump application, the heat source temperature should be lower than 90 degrees C, and EG concentration at evaporator has been chosen as 30% as an optimal value. According to the operation condition, this EG concentration has been determined to avoid freezing in the evaporator in the studied working range. However, too much EG significantly decreases the pressure in the evaporator and increases the viscosity, hence will increase the maintenance of equipment as more vacuum tightness is required.
引用
收藏
页码:156 / 171
页数:16
相关论文
共 50 条
  • [1] Exergetic and energetic comparison of LiCl-H2O and LiBr-H2O working pairs in a solar absorption cooling system
    Bellos, Evangelos
    Tzivanidis, Christos
    Antonopoulos, Kimon A.
    [J]. ENERGY CONVERSION AND MANAGEMENT, 2016, 123 : 453 - 461
  • [2] Performance Enhancement in LiCl-H2O and LiBr-H2O Absorption Cooling Systems Through an Advanced Exergy Analysis
    Mody, Parth
    Patel, Jatin
    Modi, Nishant
    Pandya, Bhargav
    [J]. INTERNATIONAL JOURNAL OF AIR-CONDITIONING AND REFRIGERATION, 2021, 29 (01)
  • [3] Energy and exergy analysis of a double effect LiBr-H2O and LiCl-H2O chillers
    Kilic, M.
    Ravul, H. B.
    [J]. BULGARIAN CHEMICAL COMMUNICATIONS, 2016, 48 : 312 - 317
  • [4] ENERGY AND EXERGY ANALYSES OF A LIBR-H2O SOLAR ABSORPTION COOLING SYSTEM: A CASE STUDY FOR BRAZILIAN PUBLIC BUILDINGS
    Pinto, Gabriel
    de Souza, Tulio
    Coronado, Christian
    [J]. ENVIRONMENTAL ENGINEERING AND MANAGEMENT JOURNAL, 2022, 21 (06): : 939 - 950
  • [5] Energy, exergy, and economic analysis of single and double effect LiBr-H2O absorption chillers
    Avanessian, T.
    Ameri, M.
    [J]. ENERGY AND BUILDINGS, 2014, 73 : 26 - 36
  • [6] Performance of a Single Effect Solar Absorption Cooling System (Libr-H2O)
    Ketfi, Omar
    Merzouk, Mustapha
    Merzouk, Nachida Kasbadji
    El Metenan, Said
    [J]. INTERNATIONAL CONFERENCE ON TECHNOLOGIES AND MATERIALS FOR RENEWABLE ENERGY, ENVIRONMENT AND SUSTAINABILITY -TMREES15, 2015, 74 : 130 - 138
  • [7] EXERGY ANALYSIS OF A LiBr-H2O VAPOR ABSORPTION REFRIGERATION PLANT: A CASE STUDY
    Anand, Sanjeev
    Gupta, Ankush
    Tyagi, Sudhir Kumar
    [J]. INTERNATIONAL JOURNAL OF AIR-CONDITIONING AND REFRIGERATION, 2014, 22 (02)
  • [8] Stationary analysis of a solar LiBr-H2O absorption refrigeration system
    Monne, C.
    Alonso, S.
    Palacin, F.
    Guallar, J.
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2011, 34 (02): : 518 - 526
  • [9] A novel low-grade heat-driven absorption refrigeration system with LiCl-H2O and LiBr-H2O working pairs
    She, Xiaohui
    Yin, Yonggao
    Xu, Mengfei
    Zhang, Xiaosong
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2015, 58 : 219 - 234
  • [10] Thermodynamic performance and comparison of solar assisted double effect absorption cooling system with LiCl-H2O and LiBr-H2O working fluid
    Pandya, Bhargav
    Modi, Nishant
    Upadhyai, Ravi
    Patel, Jatin
    [J]. BUILDING SIMULATION, 2019, 12 (06) : 1063 - 1075