HIGH-RESISTANCE NEUTRAL GROUNDING IN INDUSTRIAL SYSTEMS AND THE GROUND FAULT PROTECTION

被引:0
|
作者
Bernardi, Gladston A. F. [1 ]
de Carvalho Filho, Jose Maria [1 ]
机构
[1] UNIFEI Univ Fed ltajuba, GQEE Grp Estudos Qualidade Energia Eletr, Itajuba, MG, Brazil
关键词
High-resistance neutral grounding; ground fault location and detection; charging current; sympathetic nuisance tripping;
D O I
暂无
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
The objective of this paper is to present the state-of-the art in the high-resistance neutral grounding practice in LV (480V) and MV (4.16kV) industrial power systems, not still widely known in Brazil, especially regarding the ground fault detection and location systems, and equipment protection with selectivity. This technique is important for the quality of energy and continuity of service in industrial processes. It is also presented a new synthesis for the range of adjustment of the ground-fault protection relays based on the constraints of the first ground-fault coexistence in the power supply system, the ground protection selectivity in the case of a second fault, the effective ground protection of equipment, and on the avoidance of nuisance tripping due to the charging current flow during faults. The possibility of using high-resistance neutral systems up to 4.16kV and beyond is discussed based on today's assumption of the limits of a self-sustainable carbonous arc in motor winding insulation failures and the calculation of charging currents.
引用
收藏
页码:1276 / 1282
页数:7
相关论文
共 50 条
  • [1] HIGH-RESISTANCE GROUNDING AND SELECTIVE GROUND FAULT PROTECTION FOR A MAJOR INDUSTRIAL FACILITY
    WANG, GN
    MOFFATT, WM
    VEGH, LJ
    VEICHT, FJ
    IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 1984, 20 (04) : 978 - 985
  • [2] Applying High-Resistance Neutral Grounding in Medium-Voltage Systems
    Kingrey, Lawrence J.
    Painter, Ralph D.
    Locker, Anthony S.
    IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2011, 47 (03) : 1220 - 1231
  • [3] Flux Linkage Detection Based Ground Fault Identification and System Diagnosis in High-Resistance Grounding Systems
    Hu, Jiangang
    Wei, Lixiang
    McGuire, Jeffrey
    Liu, Zhijun
    IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2017, 53 (03) : 2967 - 2975
  • [4] Directional ground fault indicator for high-resistance grounded systems
    Baldwin, T
    Renovich, F
    Saunders, L
    2002 IEEE INDUSTRIAL AND COMMERCIAL POWER SYSTEMS TECHNICAL CONFERENCE, CONFERENCE RECORD, 2002, : 103 - 109
  • [5] HIGH-RESISTANCE GROUNDING
    BRIDGER, B
    IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 1983, 19 (01) : 15 - 21
  • [6] Conversion of ungrounded systems to high-resistance grounding systems
    Sutherland, Peter E.
    Mansoor, Arshad
    2006 IEEE INDUSTRIAL AND COMMERCIAL POWER SYSTEMS TECHNICAL CONFERENCE, CONFERENCE RECORD, 2006, : 40 - +
  • [7] Directional ground-fault indicator for high-resistance grounded systems
    Baldwin, T
    Renovich, F
    Saunders, LF
    IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2003, 39 (02) : 325 - 332
  • [8] High-resistance grounding fault detector by use of feeding current
    Hase, Shin-Ichi
    Okui, Akinobu
    Sekijima, Shiro
    Sugai, Shunichi
    Akagi, Masataka
    Kimura, Takashi
    Quarterly Report of RTRI (Railway Technical Research Institute) (Japan), 2008, 49 (02): : 108 - 112
  • [9] High-Resistance Grounding Fault Detection and Line Selection in Resonant Grounding Distribution Network
    Yang, Dong
    Lu, Baopeng
    Lu, Huaiwei
    ELECTRONICS, 2023, 12 (19)
  • [10] REALITY OF HIGH-RESISTANCE GROUNDING
    DUNKIJACOBS, JR
    IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 1977, 13 (05) : 469 - 475