Energy use analysis of the variable refrigerant flow (VRF) system versus the multi-split unit using TRNSYS

被引:3
|
作者
Yau, Y. H. [1 ,2 ]
Amir, M. [1 ]
机构
[1] Univ Malaya, Dept Mech Engn, Kuala Lumpur 50603, Malaysia
[2] Univ Malaya, Fac Engn, UM Daikin Lab, Kuala Lumpur 50603, Malaysia
关键词
AIR-CONDITIONING SYSTEM; BIN WEATHER DATA; SIMULATION; TEMPERATURE; PERFORMANCE; VALIDATION; EFFICIENCY; VOLUME;
D O I
10.1007/s00231-019-02726-7
中图分类号
O414.1 [热力学];
学科分类号
摘要
The usage of air - conditioning in the residential and commercial buildings is becoming necessary because of the enormous demand for thermal comfort and healthy indoor environment. In achieving human thermal comfort and healthy indoor environment in a large building, there are many types of air conditioning systems that can be used, including the multi - split type unit and the variable refrigerant flow (VRF) system. The present research analyses the annual energy use of the existing ACMV system (multi - split type ceiling cassette unit) installed in the examined building, which located in the tropical area and compares it with a VRF system. The TRNSYS software is used to simulate both of these systems in accordance with the existing building's characteristics and its operation. The existing building's characteristics and its operation are obtained by conducting the site survey and field measurements in the building. In the current paper, the bin method is used to estimate the annual energy consumption for these systems. Based on the simulation results, the existing ACMV system consumes more energy in comparison to the VRF system by 13.62%. In addition, the annual operating cost of these systems has shown that the VRF system has a lower annual operating cost in comparison to the existing ACMV system by 13.63%. Besides that, the VRF system can accommodate an estimated payback period of around 6.6 years and an internal rate of return of 12.75%. The result has suggested that the VRF system has a great potential in energy savings and could reduce the electricity consumption in a large building significantly.
引用
收藏
页码:671 / 690
页数:20
相关论文
共 33 条
  • [1] Energy use analysis of the variable refrigerant flow (VRF) system versus the multi - split unit using TRNSYS
    Y. H. Yau
    M. ‘Amir
    Heat and Mass Transfer, 2020, 56 : 671 - 690
  • [2] Performance analysis of multi-split variable refrigerant flow (VRF) system with vapor-injection in cold season
    Min, Byungchae
    Na, Sangkyung
    Lee, Taemin
    Jang, Seokhoon
    Bae, Heunghee
    Moon, Cheoreon
    Choi, Gyungmin
    INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2019, 99 : 419 - 428
  • [3] Simulation and optimization of multi-split variable refrigerant flow systems
    Alahmer, Ali
    Alsaqoor, Sameh
    AIN SHAMS ENGINEERING JOURNAL, 2018, 9 (04) : 1705 - 1715
  • [4] Investigation on Current Control Defrosting Method of Multi-split Variable Refrigerant Flow System
    Liu, Min
    Liu, Hexin
    Wang, Meng
    Chen, Hua
    INTERNATIONAL JOURNAL OF THERMODYNAMICS, 2020, 23 (04) : 235 - 243
  • [5] Investigation on current control defrosting method of multi-split variable refrigerant flow system
    Liu M.
    Liu H.
    Wang M.
    Chen H.
    Wang, Meng (wangmeng155@126.com), 1600, International Journal of Thermodynamics (23): : 235 - 243
  • [6] Indoor unit fault detector for a multi-split VRF system in heating mode
    Shin, Younggy
    Karng, Sarng Woo
    Kim, Seo Young
    INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2014, 40 : 152 - 160
  • [7] Simulation of recombined household multi-split variable refrigerant flow system with split-type air conditioners
    Li, Ziai
    Wang, Baolong
    Li, Xianting
    Shi, Wenxing
    Zhang, Shaolong
    Liu, Yunzhong
    APPLIED THERMAL ENGINEERING, 2017, 117 : 343 - 354
  • [8] Performance comparison between bypass cycle and injection cycle for sub-cooling methods in multi-split variable refrigerant flow (VRF) system in hot seasons
    Min, Byungchae
    Jang, Seokhoon
    Lee, Taemin
    Bae, Heunghee
    Moon, Cheoreon
    Choi, Gyungmin
    INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2019, 107 : 202 - 213
  • [9] A general simulation model for variable refrigerant flow multi-split air conditioning system based on graph theory
    Sun, Haoran
    Ding, Guoliang
    Hu, Haitao
    Ren, Tao
    Xia, Guanghui
    Wu, Guoming
    INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2017, 82 : 22 - 35
  • [10] Simulation on effects of subcooler on cooling performance of multi-split variable refrigerant flow systems with different lengths of refrigerant pipeline
    Li, Ziai
    Wang, Baolong
    Li, Xianting
    Shi, Wenxing
    ENERGY AND BUILDINGS, 2016, 126 : 301 - 309