Investigation on large turbo-generator stator end winding dynamic characteristics based on response surface method

被引:2
|
作者
Zhao, Yang [1 ,2 ,3 ,4 ]
Xiao, Yang [1 ]
Lu, Sheng [1 ,4 ]
Sun, Hao [2 ]
Huo, Wenhao [2 ]
Liao, Yong [3 ]
机构
[1] Chongqing Univ Posts & Telecommun, Sch Adv Mfg Engn, Chongqing, Peoples R China
[2] Chongqing Gen Ind Grp Co Ltd, Chongqing, Peoples R China
[3] Chongqing Univ, Sch Elect Engn, Chongqing, Peoples R China
[4] Xi An Jiao Tong Univ, State Key Lab Strength & Vibrat Mech Struct, Xian, Peoples R China
基金
中国国家自然科学基金;
关键词
Dynamic characteristics; Response surface method; Stator end winding; Turbo-generator; Finite-element analysis;
D O I
10.1007/s43236-021-00296-8
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The natural frequencies corresponding to the particular mode shapes of a large turbo-generator must not be in the resonance region before delivery. Different parameters may clearly affect these dynamic characteristics. Different from other studies, this paper introduces a method for obtaining the inherent characteristics of end winding in a short period of time under multiple simultaneously changing parameters. The proposed process is based on the response surface method (RSM). In this method, the main concerned natural frequencies were taken as the critical index to describe the dynamic behaviors of the end winding, with which the mathematical relationship between the dynamic characteristics and design variables was analyzed. First, the stiffness of the rings, stiffness of the radial braces and number of pins bonded to the radial braces were used as samples for orthogonal experimental design. Then, the natural modes and frequencies of 25 different samples were acquired by conducting modal analysis with ABAQUS software. Utilizing these dynamic results, a second-order polynomial response surface model was established to describe the relationships between natural frequencies and these three different parameters. Then, the quality of this model was verified by calculating the valuating indexes for comparison with support vector regression (SVR). With the response surface model, the variation regularities of the natural frequencies and modes due to the above parameters were discussed. The method proposed in this paper can enable natural frequencies in the whole design space to be quickly determined without finite-element analysis, greatly improving the development efficiency and laying a foundation for dynamic response prediction during normal operation with different parameters and additional large turbo-generator stator end winding optimization.
引用
收藏
页码:1473 / 1483
页数:11
相关论文
共 50 条
  • [1] Investigation on large turbo-generator stator end winding dynamic characteristics based on response surface method
    Yang Zhao
    Yang Xiao
    Sheng Lu
    Hao Sun
    Wenhao Huo
    Yong Liao
    [J]. Journal of Power Electronics, 2021, 21 : 1473 - 1483
  • [2] Dynamic response prediction of large turbo-generator stator end winding based on approximate model
    Zhao, Yang
    He, Le
    Liu, Jinhui
    Chen, Xiang
    Ma, Ying
    [J]. Zhendong yu Chongji/Journal of Vibration and Shock, 2023, 42 (21): : 81 - 87
  • [3] Electromagnetic vibration of integrity end winding of large turbo-generator stator
    Hu, Yu-Da
    Qiu, Jia-Jun
    Qing, Guang-Hui
    [J]. Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering, 2003, 23 (07): : 93 - 98
  • [4] Nonlinear electromagnetic vibration of turbo-generator stator end winding
    Hu, YD
    Qiu, JJ
    Ta, N
    [J]. ELEVENTH WORLD CONGRESS IN MECHANISM AND MACHINE SCIENCE, VOLS 1-5, PROCEEDINGS, 2004, : 1470 - 1474
  • [5] Application of Dynamic Characteristic Analysis Technology for Stator End-winding of Large Capacity Turbo-generator
    Gao, Shuyou
    Wen, Lu
    Liao, Wei
    [J]. 2009 THIRD INTERNATIONAL SYMPOSIUM ON INTELLIGENT INFORMATION TECHNOLOGY APPLICATION, VOL 1, PROCEEDINGS, 2009, : 669 - 671
  • [6] Analytical Investigation of Dynamic Characteristic for Stator End-winding of Turbo-generator of 600MW
    Liao Wei
    Gao Yongge
    Zhang Haijun
    [J]. 2009 INTERNATIONAL CONFERENCE ON MEASURING TECHNOLOGY AND MECHATRONICS AUTOMATION, VOL III, 2009, : 19 - 21
  • [7] Digital mechanism modeling and vibration characteristic analysis for stator end winding of large turbo-generator
    Wang, Ting
    Wang, Hui
    Zhao, Yang
    Li, Xinghong
    [J]. Zhendong yu Chongji/Journal of Vibration and Shock, 2023, 42 (07): : 143 - 153
  • [8] Diagnosis of interturn fault in stator winding of turbo-generator
    Faiz, Jawad
    Mahmoodi, Ali
    Keravand, Mehran
    Davarpanah, Mahdi
    [J]. INTERNATIONAL TRANSACTIONS ON ELECTRICAL ENERGY SYSTEMS, 2019, 29 (12):
  • [9] RETRACTED: Research on Dynamic Characteristics of Stator core of Large Turbo-Generator (Retracted Article)
    Wang Yixuan
    Wang Ying
    [J]. 2010 ASIA-PACIFIC POWER AND ENERGY ENGINEERING CONFERENCE (APPEEC), 2010,
  • [10] Prediction of Electromagnetic Characteristics in Stator End Parts of a Turbo-Generator Based on MLP and SVR
    Wang, Likun
    Sun, Yutian
    Kou, Baoquan
    Bi, Xiaoshuai
    Guo, Hai
    Marignetti, Fabrizio
    Zhang, Huibo
    [J]. ENERGIES, 2021, 14 (18)