Influence of the Contact Opening Speed on DC Vacuum Arc

被引:11
|
作者
Qin, Taotao [1 ]
Dong, Enyuan [1 ]
Wang, Yongxing [1 ]
Zou, Jiyan [1 ]
机构
[1] Dalian Univ Technol, Dept Elect & Elect Engn, Dalian 116024, Peoples R China
基金
中国国家自然科学基金;
关键词
DC interruption; forced current zero; highspeed actuator; image process; vacuum arc;
D O I
10.1109/TPS.2015.2390256
中图分类号
O35 [流体力学]; O53 [等离子体物理学];
学科分类号
070204 ; 080103 ; 080704 ;
摘要
Arc determines whether the vacuum switchgears can break current successfully, so it is significant to study its characteristics. In this paper, a hybrid high-speed actuator was designed, and a method of forced current zero was used to interrupt de in a synthetic test circuit. With the different contact opening speeds, the processes of arc burning and current transferring were observed by a high-speed CMOS camera. Through the arc area obtained by an image processing technology, the influences of the opening speed on arc were researched, including the influences in the initial arc burning stage, in the forced current zero stage, and at the same electrode distance. The results indicate that with the increase of the opening speed in a certain range, the arc area in the forced current zero stage tends to be small, and the one in the initial arc burning stage spreads more quickly. Although the arc area increases with the opening speed in the initial arc burning stage, its impact on the whole de current transferring process is slight when the contact opening speed is high. So, high opening speed is helpful to extinguish arc and transfer current. In addition, there is another discovery in the experiments. In a certain range, when the opening speed is higher, arc burns stably earlier, and the arc area is smaller in the stable burning stage. So, it is beneficial to inject the transferring current in this stage. Experimental results and analysis of the arc images prove that increasing the opening speed is useful to transfer the current successfully and recover the dielectric strength of the electrode distance.
引用
收藏
页码:878 / 883
页数:6
相关论文
共 50 条
  • [1] Influence of Initial Opening Speed on Characteristics of a Drawn Vacuum Arc
    Xiu Shixin
    Ye Zhaoping
    Li Quan
    PLASMA SCIENCE & TECHNOLOGY, 2011, 13 (03) : 376 - 380
  • [2] Investigation of the influence of opening speed on vacuum arc under transverse magnetic field
    Wang, Hongda
    Wang, Lijun
    Ma, Qiang
    Wang, Cong
    Que, Jilei
    PHYSICS OF PLASMAS, 2023, 30 (11)
  • [3] Influence of Contact Materials and Opening Velocity on Various Characteristics of DC High Voltage Arc
    Yoshida, Kiyoshi
    Sawa, Koichiro
    Suzuki, Kenji
    Takaya, Koetsu
    2017 63RD IEEE HOLM CONFERENCE ON ELECTRICAL CONTACTS, 2017, : 209 - 214
  • [4] Operating Characteristics of Superconducting Arc-induction Type DC Circuit Breaker According to Contact Opening Speed
    Park S.-Y.
    Kim J.-H.
    Kim G.-W.
    Jeong J.-S.
    Choi H.-S.
    Transactions of the Korean Institute of Electrical Engineers, 2023, 72 (01): : 138 - 144
  • [5] Ignition and lifetime of low current DC vacuum arc ignited by the opening of the electrodes
    Tsuruta, K
    Tanaka, N
    Kido, H
    Hirai, K
    ISDEIV: XIXTH INTERNATIONAL SYMPOSIUM ON DISCHARGES AND ELECTRICAL INSULATION IN VACUUM, VOLS 1 AND 2, PROCEEDINGS, 2000, 19 : 52 - 55
  • [6] Investigation on anode modes of vacuum arc under different contact opening speeds
    Wang, Hongda
    Wang, Lijun
    Zhang, Runming
    Ma, Qiang
    Wang, Cong
    Zhang, Zhefeng
    Yang, Ze
    Wang, Zhiwei
    PHYSICS OF PLASMAS, 2022, 29 (08)
  • [7] The influence of the contact surface shape on vacuum arc chute performance
    Belkin G.S.
    Lukatskaya I.A.
    Romochkin Yu.G.
    Russian Electrical Engineering, 2007, 78 (04) : 177 - 182
  • [8] Influence of Arc Discharge on Contact Erosion and Contact Resistance in a Hybrid DC Switch
    Ou, Chomrong
    Nakayama, Ryo
    Zen, Shungo
    Takeuchi, Nozomi
    Yasuoka, Koichi
    PROCEEDINGS OF 2018 29TH INTERNATIONAL CONFERENCE ON ELECTRICAL CONTACTS AND 64TH IEEE HOLM CONFERENCE ON ELECTRICAL CONTACTS, 2018, : 184 - 188
  • [9] Opening speed effect on arc duration and extinction gap for usual contact materials
    Sallais, D.
    Carvou, E.
    Jemaa, N. Ben
    PROCEEDINGS OF THE 2ND INTERNATIONAL CONFERENCE ON RELIABILITY OF ELECTRICAL PRODUCTS AND ELECTRICAL CONTACTS, 2007, : 73 - 77
  • [10] Influence of axial magnetic field on DC arc plasma in vacuum breaker
    School of Electrical Engineering, Shenyang University of Technology, Shenyang, China
    不详
    Zhenkong Kexue yu Jishu Xuebao, 11 (1374-1379):